Advertisement
Guest User

Untitled

a guest
Aug 30th, 2018
126
0
Never
Not a member of Pastebin yet? Sign Up, it unlocks many cool features!
text 0.67 KB | None | 0 0
  1. [battery.charge.low]
  2. Remaining battery level when UPS switches to LB (percent)
  3. Type: STRING
  4. Maximum length: 10
  5. Value: 10
  6.  
  7. [battery.runtime.low]
  8. Remaining battery runtime when UPS switches to LB (seconds)
  9. Type: STRING
  10. Maximum length: 10
  11. Value: 120
  12.  
  13. [input.sensitivity]
  14. Input power sensitivity
  15. Type: STRING
  16. Maximum length: 10
  17. Value: medium
  18.  
  19. [input.transfer.high]
  20. High voltage transfer point (V)
  21. Type: STRING
  22. Maximum length: 10
  23. Value: 288
  24.  
  25. [input.transfer.low]
  26. Low voltage transfer point (V)
  27. Type: STRING
  28. Maximum length: 10
  29. Value: 176
  30.  
  31. [ups.delay.shutdown]
  32. Interval to wait after shutdown with delay command (seconds)
  33. Type: STRING
  34. Maximum length: 10
  35. Value: 20
Advertisement