j0h

interestting

j0h
Apr 16th, 2026
145
0
Never
Not a member of Pastebin yet? Sign Up, it unlocks many cool features!
text 1.47 KB | None | 0 0
  1. D8032 to D8035, D8214, D8215: Interrupt Input Jump Destination Label No.
  2. Jump destination label numbers for interrupt inputs are written to these registers. When using interrupt inputs, write the label
  3. number that corresponds to the special data register that has been allocated to the interrupt input. For details on interrupt
  4. inputs, see "Interrupt Input" on page 5-37.
  5. D8032 = I1
  6. D8033 = I3
  7. D8034 = I4
  8. D8035 = I6
  9. D8214 = I7
  10. D8215 = I0
  11.  
  12. FC6A SERIES MICROSMART USER’S MANUAL FC9Y-B1722
  13. 5-37
  14. 5: FUNCTIONS AND SETTINGS
  15. Interrupt Input
  16. When a quick response to an external input is required, such as positioning control, the interrupt input can call a subroutine to
  17. execute an interrupt program.
  18. Six inputs I0, I1, I3, I4, I6, and I7 can be designated to execute interrupt at a rising and/or falling edge of input pulses. When an
  19. interrupt is initiated by inputs I0, I1, I3, I4, I6 and I7, program execution immediately jumps to a predetermined label number
  20. stored in special data registers D8215, D8032 through D8035, and D8214 respectively. The Function Area Settings dialog box is
  21. used to designate inputs I0, I1, I3, I4, I6 and I7 as an interrupt input, normal input, high-speed counter input, or catch input.
  22. Normal input signals to input terminals are read when the END instruction is executed at the end of a scan.
  23. Since these settings relate to the user program, the user program must be downloaded to the FC6A Series MICROSmart after
  24. changing any of these settings.