Not a member of Pastebin yet?
Sign Up,
it unlocks many cool features!
- # WARNING: This file was auto-generated using snmp_exporter generator, manual changes will be lost.
- auths:
- public_v1:
- community: public
- security_level: noAuthNoPriv
- auth_protocol: MD5
- priv_protocol: DES
- version: 1
- public_v2:
- community: public
- security_level: noAuthNoPriv
- auth_protocol: MD5
- priv_protocol: DES
- version: 2
- modules:
- apcups:
- walk:
- - 1.3.6.1.4.1.318.1.1.1.12
- - 1.3.6.1.4.1.318.1.1.1.2
- - 1.3.6.1.4.1.318.1.1.1.3
- - 1.3.6.1.4.1.318.1.1.1.4
- - 1.3.6.1.4.1.318.1.1.1.7.2
- - 1.3.6.1.4.1.318.1.1.10.2.3.2
- - 1.3.6.1.4.1.318.1.1.26.10.2.2
- - 1.3.6.1.4.1.318.1.1.26.4.3
- - 1.3.6.1.4.1.318.1.1.26.6.3
- - 1.3.6.1.4.1.318.1.1.26.8.3
- get:
- - 1.3.6.1.4.1.318.1.1.1.8.1.0
- metrics:
- - name: upsOutletGroupStatusTableSize
- oid: 1.3.6.1.4.1.318.1.1.1.12.1.1
- type: gauge
- help: The number of outlet groups for the UPS. - 1.3.6.1.4.1.318.1.1.1.12.1.1
- - name: upsOutletGroupStatusIndex
- oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.1
- type: gauge
- help: The index to the outlet group entry. - 1.3.6.1.4.1.318.1.1.1.12.1.2.1.1
- indexes:
- - labelname: upsOutletGroupStatusIndex
- type: gauge
- lookups:
- - labels:
- - upsOutletGroupStatusIndex
- labelname: upsOutletGroupStatusName
- oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.2
- type: DisplayString
- - labels: []
- labelname: upsOutletGroupStatusIndex
- - name: upsOutletGroupStatusName
- oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.2
- type: DisplayString
- help: The name of the outlet group - 1.3.6.1.4.1.318.1.1.1.12.1.2.1.2
- indexes:
- - labelname: upsOutletGroupStatusIndex
- type: gauge
- lookups:
- - labels:
- - upsOutletGroupStatusIndex
- labelname: upsOutletGroupStatusName
- oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.2
- type: DisplayString
- - labels: []
- labelname: upsOutletGroupStatusIndex
- - name: upsOutletGroupStatusGroupState
- oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.3
- type: gauge
- help: Getting this variable will return the outlet group state - 1.3.6.1.4.1.318.1.1.1.12.1.2.1.3
- indexes:
- - labelname: upsOutletGroupStatusIndex
- type: gauge
- lookups:
- - labels:
- - upsOutletGroupStatusIndex
- labelname: upsOutletGroupStatusName
- oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.2
- type: DisplayString
- - labels: []
- labelname: upsOutletGroupStatusIndex
- enum_values:
- 1: upsOutletGroupStatusOn
- 2: upsOutletGroupStatusOff
- 3: upsOutletGroupStatusUnknown
- - name: upsOutletGroupStatusCommandPending
- oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.4
- type: gauge
- help: Getting this variable will return the command pending state of the outlet
- group - 1.3.6.1.4.1.318.1.1.1.12.1.2.1.4
- indexes:
- - labelname: upsOutletGroupStatusIndex
- type: gauge
- lookups:
- - labels:
- - upsOutletGroupStatusIndex
- labelname: upsOutletGroupStatusName
- oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.2
- type: DisplayString
- - labels: []
- labelname: upsOutletGroupStatusIndex
- enum_values:
- 1: upsOutletGroupCommandPending
- 2: upsOutletGroupNoCommandPending
- - name: upsOutletGroupStatusOutletType
- oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.5
- type: gauge
- help: Getting this variable will return the type of outlet group - 1.3.6.1.4.1.318.1.1.1.12.1.2.1.5
- indexes:
- - labelname: upsOutletGroupStatusIndex
- type: gauge
- lookups:
- - labels:
- - upsOutletGroupStatusIndex
- labelname: upsOutletGroupStatusName
- oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.2
- type: DisplayString
- - labels: []
- labelname: upsOutletGroupStatusIndex
- enum_values:
- 1: upsSwitchedOutletGroup
- 2: upsMainOutletGroup
- - name: upsOutletGroupStatusGroupFullState
- oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.6
- type: DisplayString
- help: An ASCII string containing the 32 flags representing the current state(s)
- of the outlet group - 1.3.6.1.4.1.318.1.1.1.12.1.2.1.6
- indexes:
- - labelname: upsOutletGroupStatusIndex
- type: gauge
- lookups:
- - labels:
- - upsOutletGroupStatusIndex
- labelname: upsOutletGroupStatusName
- oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.2
- type: DisplayString
- - labels: []
- labelname: upsOutletGroupStatusIndex
- - name: upsOutletGroupConfigTableSize
- oid: 1.3.6.1.4.1.318.1.1.1.12.2.1
- type: gauge
- help: The number of outlet groups for the UPS. - 1.3.6.1.4.1.318.1.1.1.12.2.1
- - name: upsOutletGroupConfigIndex
- oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.1
- type: gauge
- help: The index to the outlet group entry. - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.1
- indexes:
- - labelname: upsOutletGroupConfigIndex
- type: gauge
- - name: upsOutletGroupConfigName
- oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.2
- type: DisplayString
- help: The name of the outlet group. - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.2
- indexes:
- - labelname: upsOutletGroupConfigIndex
- type: gauge
- - name: upsOutletGroupConfigPowerOnDelay
- oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.3
- type: gauge
- help: The amount of time (seconds) the outlet group will delay powering on when
- the delayed on, reboot, or shutdown command is applied - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.3
- indexes:
- - labelname: upsOutletGroupConfigIndex
- type: gauge
- - name: upsOutletGroupConfigPowerOffDelay
- oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.4
- type: gauge
- help: The amount of time (seconds) the outlet group will delay powering off
- when the delayed off, reboot, or shutdown command is applied - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.4
- indexes:
- - labelname: upsOutletGroupConfigIndex
- type: gauge
- - name: upsOutletGroupConfigRebootDuration
- oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.5
- type: gauge
- help: During a reboot sequence, power is turned off and then back on - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.5
- indexes:
- - labelname: upsOutletGroupConfigIndex
- type: gauge
- - name: upsOutletGroupConfigMinReturnRuntime
- oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.6
- type: gauge
- help: In an Outlet Group shutdown sequence, the Outlet Group cycles power off
- then on - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.6
- indexes:
- - labelname: upsOutletGroupConfigIndex
- type: gauge
- - name: upsOutletGroupConfigOutletType
- oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.7
- type: gauge
- help: Getting this variable will return the type of outlet group - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.7
- indexes:
- - labelname: upsOutletGroupConfigIndex
- type: gauge
- enum_values:
- 1: upsSwitchedOutletGroup
- 2: upsMainOutletGroup
- - name: upsOutletGroupConfigLoadShedControlSkipOffDelay
- oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.8
- type: gauge
- help: Configures whether the outlet group's off delay setting (upsOutletGroupConfigPowerOffDelay)
- will be used in a load shedding situation, where applicable. - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.8
- indexes:
- - labelname: upsOutletGroupConfigIndex
- type: gauge
- enum_values:
- 1: upsOutletGroupConfigSkipOffDelay
- 2: upsOutletGroupConfigUseOffDelay
- - name: upsOutletGroupConfigLoadShedControlAutoRestart
- oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.9
- type: gauge
- help: Configures whether the outlet group will automatically restart after a
- load shedding situation, where applicable. - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.9
- indexes:
- - labelname: upsOutletGroupConfigIndex
- type: gauge
- enum_values:
- 1: upsOutletGroupConfigAutoRestart
- 2: upsOutletGroupConfigManualRestart
- - name: upsOutletGroupConfigLoadShedControlTimeOnBattery
- oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.10
- type: gauge
- help: Configures whether the outlet group will load shed (turn off) after the
- UPS device's time on battery has exceeded the upsOutletGroupConfigLoadShedTimeOnBattery
- OID setting - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.10
- indexes:
- - labelname: upsOutletGroupConfigIndex
- type: gauge
- enum_values:
- 1: upsOutletGroupConfigDisableTimeOnBatteryLoadShed
- 2: upsOutletGroupConfigEnableTimeOnBatteryLoadShed
- - name: upsOutletGroupConfigLoadShedControlRuntimeRemaining
- oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.11
- type: gauge
- help: Configures whether the outlet group will load shed (turn off) when the
- UPS is on battery and the remaining runtime is less than the upsOutletGroupConfigLoadShedRuntimeRemaining
- OID setting - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.11
- indexes:
- - labelname: upsOutletGroupConfigIndex
- type: gauge
- enum_values:
- 1: upsOutletGroupConfigDisableRuntimeRemainingLoadShed
- 2: upsOutletGroupConfigEnableRuntimeRemainingLoadShed
- - name: upsOutletGroupConfigLoadShedControlInOverload
- oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.12
- type: gauge
- help: Configures whether the outlet group will load shed (turn off) when the
- UPS is in an overload condition - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.12
- indexes:
- - labelname: upsOutletGroupConfigIndex
- type: gauge
- enum_values:
- 1: upsOutletGroupConfigDisableInOverloadLoadShed
- 2: upsOutletGroupConfigEnableInOverloadLoadShed
- - name: upsOutletGroupConfigLoadShedTimeOnBattery
- oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.13
- type: gauge
- help: When the UPS has been on battery for more time than this value, the outlet
- group will turn off if this condition is enabled by the upsOutletGroupConfigLoadShedControlTimeOnBattery
- OID - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.13
- indexes:
- - labelname: upsOutletGroupConfigIndex
- type: gauge
- - name: upsOutletGroupConfigLoadShedRuntimeRemaining
- oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.14
- type: gauge
- help: When the runtime remaining is less than this value, the outlet group will
- turn off if this condition is enabled by the upsOutletGroupConfigLoadShedControlRuntimeRemaining
- OID - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.14
- indexes:
- - labelname: upsOutletGroupConfigIndex
- type: gauge
- - name: upsOutletGroupControlTableSize
- oid: 1.3.6.1.4.1.318.1.1.1.12.3.1
- type: gauge
- help: The number of outlet groups for the UPS. - 1.3.6.1.4.1.318.1.1.1.12.3.1
- - name: upsOutletGroupControlIndex
- oid: 1.3.6.1.4.1.318.1.1.1.12.3.2.1.1
- type: gauge
- help: The index to the outlet group entry. - 1.3.6.1.4.1.318.1.1.1.12.3.2.1.1
- indexes:
- - labelname: upsOutletGroupControlIndex
- type: gauge
- - name: upsOutletGroupControlName
- oid: 1.3.6.1.4.1.318.1.1.1.12.3.2.1.2
- type: DisplayString
- help: The name of the outlet group - 1.3.6.1.4.1.318.1.1.1.12.3.2.1.2
- indexes:
- - labelname: upsOutletGroupControlIndex
- type: gauge
- - name: upsOutletGroupControlCommand
- oid: 1.3.6.1.4.1.318.1.1.1.12.3.2.1.3
- type: gauge
- help: Getting this variable will return the outlet group state - 1.3.6.1.4.1.318.1.1.1.12.3.2.1.3
- indexes:
- - labelname: upsOutletGroupControlIndex
- type: gauge
- enum_values:
- 1: upsOutletGroupImmediateOn
- 2: upsOutletGroupImmediateOff
- 3: upsOutletGroupImmediateRebootWithOrWithoutAC
- 4: upsOutletGroupDelayedOn
- 5: upsOutletGroupDelayedOff
- 6: upsOutletGroupDelayedRebootWithOrWithoutAC
- 7: upsOutletGroupCancelPendingCommand
- 8: upsOutletGroupControlUnknown
- 9: upsOutletGroupImmediateRebootShutdown
- 10: upsOutletGroupDelayedRebootShutdown
- - name: upsOutletGroupControlOutletType
- oid: 1.3.6.1.4.1.318.1.1.1.12.3.2.1.4
- type: gauge
- help: Getting this variable will return the type of outlet group - 1.3.6.1.4.1.318.1.1.1.12.3.2.1.4
- indexes:
- - labelname: upsOutletGroupControlIndex
- type: gauge
- enum_values:
- 1: upsSwitchedOutletGroup
- 2: upsMainOutletGroup
- - name: upsBasicBatteryStatus
- oid: 1.3.6.1.4.1.318.1.1.1.2.1.1
- type: gauge
- help: The status of the UPS batteries - 1.3.6.1.4.1.318.1.1.1.2.1.1
- enum_values:
- 1: unknown
- 2: batteryNormal
- 3: batteryLow
- 4: batteryInFaultCondition
- 5: noBatteryPresent
- - name: upsBasicBatteryTimeOnBattery
- oid: 1.3.6.1.4.1.318.1.1.1.2.1.2
- type: gauge
- help: The elapsed time since the UPS has switched to battery power. - 1.3.6.1.4.1.318.1.1.1.2.1.2
- - name: upsBasicBatteryLastReplaceDate
- oid: 1.3.6.1.4.1.318.1.1.1.2.1.3
- type: DisplayString
- help: The date when the UPS system's batteries were last replaced in mm/dd/yy
- (or yyyy) format - 1.3.6.1.4.1.318.1.1.1.2.1.3
- - name: upsAdvBatteryCapacity
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.1
- type: gauge
- help: The remaining battery capacity expressed in percent of full capacity -
- 1.3.6.1.4.1.318.1.1.1.2.2.1
- - name: upsAdvBatteryTemperature
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.2
- type: gauge
- help: The current internal UPS temperature expressed in Celsius - 1.3.6.1.4.1.318.1.1.1.2.2.2
- - name: upsAdvBatteryRunTimeRemaining
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.3
- type: gauge
- help: The UPS battery run time remaining before battery exhaustion. - 1.3.6.1.4.1.318.1.1.1.2.2.3
- - name: upsAdvBatteryReplaceIndicator
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.4
- type: gauge
- help: Indicates whether the UPS batteries need replacing. - 1.3.6.1.4.1.318.1.1.1.2.2.4
- enum_values:
- 1: noBatteryNeedsReplacing
- 2: batteryNeedsReplacing
- - name: upsAdvBatteryNumOfBattPacks
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.5
- type: gauge
- help: The number of external battery packs connected to the UPS - 1.3.6.1.4.1.318.1.1.1.2.2.5
- - name: upsAdvBatteryNumOfBadBattPacks
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.6
- type: gauge
- help: The number of external battery packs connected to the UPS that are defective
- - 1.3.6.1.4.1.318.1.1.1.2.2.6
- - name: upsAdvBatteryNominalVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.7
- type: gauge
- help: The nominal battery voltage in Volts. - 1.3.6.1.4.1.318.1.1.1.2.2.7
- - name: upsAdvBatteryActualVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.8
- type: gauge
- help: The actual battery bus voltage in Volts - 1.3.6.1.4.1.318.1.1.1.2.2.8
- - name: upsAdvBatteryCurrent
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.9
- type: gauge
- help: The battery current in Amps - 1.3.6.1.4.1.318.1.1.1.2.2.9
- - name: upsAdvTotalDCCurrent
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.10
- type: gauge
- help: The total DC current in Amps. - 1.3.6.1.4.1.318.1.1.1.2.2.10
- - name: upsAdvBatteryFullCapacity
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.11
- type: gauge
- help: The full chargeable capacity of the battery which is expressed in percentage.
- - 1.3.6.1.4.1.318.1.1.1.2.2.11
- - name: upsAdvBatteryActualVoltageTableIndex
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.12.1.1
- type: gauge
- help: The Battery Frame identifier - 1.3.6.1.4.1.318.1.1.1.2.2.12.1.1
- indexes:
- - labelname: upsAdvBatteryActualVoltageTableIndex
- type: gauge
- - name: upsAdvBatteryActualVoltagePolarity
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.12.1.2
- type: gauge
- help: The selected Battery Voltage Polarity - 1.3.6.1.4.1.318.1.1.1.2.2.12.1.2
- indexes:
- - labelname: upsAdvBatteryActualVoltageTableIndex
- type: gauge
- enum_values:
- 0: positive
- 1: negative
- - name: upsAdvBatteryFrameActualVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.12.1.3
- type: gauge
- help: The actual battery bus voltage in Volts. - 1.3.6.1.4.1.318.1.1.1.2.2.12.1.3
- indexes:
- - labelname: upsAdvBatteryActualVoltageTableIndex
- type: gauge
- - name: upsAdvTotalDCCurrentTableIndex
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.13.1.1
- type: gauge
- help: The Battery Frame identifier - 1.3.6.1.4.1.318.1.1.1.2.2.13.1.1
- indexes:
- - labelname: upsAdvTotalDCCurrentTableIndex
- type: gauge
- - name: upsAdvTotalDCCurrentPolarity
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.13.1.2
- type: gauge
- help: The selected Battery Current Polarity - 1.3.6.1.4.1.318.1.1.1.2.2.13.1.2
- indexes:
- - labelname: upsAdvTotalDCCurrentTableIndex
- type: gauge
- enum_values:
- 0: positive
- 1: negative
- - name: upsAdvTotalFrameDCCurrent
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.13.1.3
- type: gauge
- help: The Total DC Current of battery in Amperes. - 1.3.6.1.4.1.318.1.1.1.2.2.13.1.3
- indexes:
- - labelname: upsAdvTotalDCCurrentTableIndex
- type: gauge
- - name: upsAdvBatteryCurrentTableIndex
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.14.1.1
- type: gauge
- help: The Battery Frame identifier - 1.3.6.1.4.1.318.1.1.1.2.2.14.1.1
- indexes:
- - labelname: upsAdvBatteryCurrentTableIndex
- type: gauge
- - labelname: upsAdvBatteryCurrentIndex
- type: gauge
- - name: upsAdvBatteryCurrentIndex
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.14.1.2
- type: gauge
- help: The battery frame identifier. - 1.3.6.1.4.1.318.1.1.1.2.2.14.1.2
- indexes:
- - labelname: upsAdvBatteryCurrentTableIndex
- type: gauge
- - labelname: upsAdvBatteryCurrentIndex
- type: gauge
- - name: upsAdvBatteryCurrentPolarity
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.14.1.3
- type: gauge
- help: The selected Battery current polarity - 1.3.6.1.4.1.318.1.1.1.2.2.14.1.3
- indexes:
- - labelname: upsAdvBatteryCurrentTableIndex
- type: gauge
- - labelname: upsAdvBatteryCurrentIndex
- type: gauge
- enum_values:
- 0: positive
- 1: negative
- - name: upsAdvBatteryFrameCurrent
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.14.1.4
- type: gauge
- help: The Battery current measured in Amperes - 1.3.6.1.4.1.318.1.1.1.2.2.14.1.4
- indexes:
- - labelname: upsAdvBatteryCurrentTableIndex
- type: gauge
- - labelname: upsAdvBatteryCurrentIndex
- type: gauge
- - name: upsAdvBatteryEstimatedChargeTime
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.15
- type: gauge
- help: The estimated remaining time required to charge the UPS to a full state
- of charge. - 1.3.6.1.4.1.318.1.1.1.2.2.15
- - name: upsAdvBatteryPower
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.16
- type: gauge
- help: The measured battery power in kW. - 1.3.6.1.4.1.318.1.1.1.2.2.16
- - name: upsAdvBatteryChargerStatus
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.17
- type: EnumAsStateSet
- help: The status of the battery charger - 1.3.6.1.4.1.318.1.1.1.2.2.17
- enum_values:
- 1: unknown
- 2: ok
- 3: inFaultCondition
- 4: floatCharging
- 5: boostCharging
- 6: resting
- 7: notCharging
- 8: equalizationCharging
- 9: testInProgress
- 10: cyclicFloatCharging
- - name: upsAdvBatteryInternalSKU
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.19
- type: DisplayString
- help: The SKU of the internal battery. - 1.3.6.1.4.1.318.1.1.1.2.2.19
- - name: upsAdvBatteryExternalSKU
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.20
- type: DisplayString
- help: The SKU of the external battery. - 1.3.6.1.4.1.318.1.1.1.2.2.20
- - name: upsAdvBatteryRecommendedReplaceDate
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.21
- type: DisplayString
- help: The recommended replacement date for the battery based on the UPS internal
- battery life algorithm. - 1.3.6.1.4.1.318.1.1.1.2.2.21
- - name: upsAdvBatteryNominalBackupTime
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.22
- type: gauge
- help: Defines the runtime of the user supplied battery in minutes, when battery
- is new. - 1.3.6.1.4.1.318.1.1.1.2.2.22
- - name: upsAdvBatteryCondition
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.23
- type: EnumAsStateSet
- help: Health of the battries based on the battery test. - 1.3.6.1.4.1.318.1.1.1.2.2.23
- enum_values:
- 1: unknown
- 2: ok
- 3: weak
- 4: poor
- - name: upsAdvBatteryChargingCurrentRestricted
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.24
- type: EnumAsStateSet
- help: Indicates whether battery charging current is restricted or not - 1.3.6.1.4.1.318.1.1.1.2.2.24
- enum_values:
- 1: "yes"
- 2: "no"
- - name: upsAdvBatteryTotalCapacity
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.25
- type: gauge
- help: The actual available battery capacity of the system expressed in ampere
- hours (Ah) - 1.3.6.1.4.1.318.1.1.1.2.2.25
- - name: upsAdvBatteryFuseStatus
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.26
- type: gauge
- help: If battery system has one common fuse for the battery system, the status
- is given by this value - 1.3.6.1.4.1.318.1.1.1.2.2.26
- enum_values:
- 1: fuseOpen
- 2: fuseOk
- 3: notPresent
- - name: upsAdvBatteryBreakerStatus
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.27
- type: gauge
- help: The value indicates the aggregated status of the battery breakers in the
- system - 1.3.6.1.4.1.318.1.1.1.2.2.27
- enum_values:
- 1: disconnected
- 2: closed
- 3: notPresent
- - name: upsAdvBatteryWiringConfiguration
- oid: 1.3.6.1.4.1.318.1.1.1.2.2.28
- type: gauge
- help: The value indicates the wiring configuration, whether the battery is 2-wire
- or 3-wire - 1.3.6.1.4.1.318.1.1.1.2.2.28
- enum_values:
- 1: twoWire
- 2: threeWire
- - name: upsHighPrecBatteryCapacity
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.1
- type: gauge
- help: The remaining battery capacity expressed in tenths of percent of full
- capacity. - 1.3.6.1.4.1.318.1.1.1.2.3.1
- - name: upsHighPrecBatteryTemperature
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.2
- type: gauge
- help: The current internal UPS temperature expressed in tenths of degrees Celsius
- - 1.3.6.1.4.1.318.1.1.1.2.3.2
- - name: upsHighPrecBatteryNominalVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.3
- type: gauge
- help: The nominal battery voltage in tenths of Volts. - 1.3.6.1.4.1.318.1.1.1.2.3.3
- - name: upsHighPrecBatteryActualVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.4
- type: gauge
- help: The actual battery bus voltage in tenths of Volts. - 1.3.6.1.4.1.318.1.1.1.2.3.4
- - name: upsHighPrecBatteryCurrent
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.5
- type: gauge
- help: The battery current in tenths of Amps - 1.3.6.1.4.1.318.1.1.1.2.3.5
- - name: upsHighPrecTotalDCCurrent
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.6
- type: gauge
- help: The total DC current in tenths of Amps. - 1.3.6.1.4.1.318.1.1.1.2.3.6
- - name: upsHighPrecBatteryActualVoltageTableIndex
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.7.1.1
- type: gauge
- help: The Battery Frame identifier - 1.3.6.1.4.1.318.1.1.1.2.3.7.1.1
- indexes:
- - labelname: upsHighPrecBatteryActualVoltageTableIndex
- type: gauge
- - name: upsHighPrecBatteryActualVoltagePolarity
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.7.1.2
- type: gauge
- help: The selected Battery Voltage polarity - 1.3.6.1.4.1.318.1.1.1.2.3.7.1.2
- indexes:
- - labelname: upsHighPrecBatteryActualVoltageTableIndex
- type: gauge
- enum_values:
- 0: positive
- 1: negative
- - name: upsHighPrecBatteryVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.7.1.3
- type: gauge
- help: The actual battery bus voltage expressed as tenths of Volts - 1.3.6.1.4.1.318.1.1.1.2.3.7.1.3
- indexes:
- - labelname: upsHighPrecBatteryActualVoltageTableIndex
- type: gauge
- - name: upsHighPrecTotalDCCurrentTableIndex
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.8.1.1
- type: gauge
- help: The Battery Frame identifier - 1.3.6.1.4.1.318.1.1.1.2.3.8.1.1
- indexes:
- - labelname: upsHighPrecTotalDCCurrentTableIndex
- type: gauge
- - name: upsHighPrecTotalDCCurrentPolarity
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.8.1.2
- type: gauge
- help: The selected Battery Current polarity - 1.3.6.1.4.1.318.1.1.1.2.3.8.1.2
- indexes:
- - labelname: upsHighPrecTotalDCCurrentTableIndex
- type: gauge
- enum_values:
- 0: positive
- 1: negative
- - name: upsHighPrecTotalDCFrameCurrent
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.8.1.3
- type: gauge
- help: The total DC current in tenths of Amperes. - 1.3.6.1.4.1.318.1.1.1.2.3.8.1.3
- indexes:
- - labelname: upsHighPrecTotalDCCurrentTableIndex
- type: gauge
- - name: upsHighPrecBatteryCurrentTableIndex
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.9.1.1
- type: gauge
- help: The Battery frame identifier - 1.3.6.1.4.1.318.1.1.1.2.3.9.1.1
- indexes:
- - labelname: upsHighPrecBatteryCurrentTableIndex
- type: gauge
- - labelname: upsHighPrecBatteryCurrentIndex
- type: gauge
- - name: upsHighPrecBatteryCurrentIndex
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.9.1.2
- type: gauge
- help: The Battery frame identifier - 1.3.6.1.4.1.318.1.1.1.2.3.9.1.2
- indexes:
- - labelname: upsHighPrecBatteryCurrentTableIndex
- type: gauge
- - labelname: upsHighPrecBatteryCurrentIndex
- type: gauge
- - name: upsHighPrecBatteryCurrentPolarity
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.9.1.3
- type: gauge
- help: The selected Battery Current polarity - 1.3.6.1.4.1.318.1.1.1.2.3.9.1.3
- indexes:
- - labelname: upsHighPrecBatteryCurrentTableIndex
- type: gauge
- - labelname: upsHighPrecBatteryCurrentIndex
- type: gauge
- enum_values:
- 0: positive
- 1: negative
- - name: upsHighPrecBatteryFrameCurrent
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.9.1.4
- type: gauge
- help: The Battery current in tenths of Amperes. - 1.3.6.1.4.1.318.1.1.1.2.3.9.1.4
- indexes:
- - labelname: upsHighPrecBatteryCurrentTableIndex
- type: gauge
- - labelname: upsHighPrecBatteryCurrentIndex
- type: gauge
- - name: upsHighPrecBatteryPackTableSize
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.1
- type: gauge
- help: The number of entries in the upsHighPrecBatteryPacks. - 1.3.6.1.4.1.318.1.1.1.2.3.10.1
- - name: upsHighPrecBatteryPackIndex
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.1
- type: gauge
- help: The battery pack identifier. - 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.1
- indexes:
- - labelname: upsHighPrecBatteryPackIndex
- type: gauge
- - labelname: upsHighPrecBatteryCartridgeIndex
- type: gauge
- - name: upsHighPrecBatteryCartridgeIndex
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.2
- type: gauge
- help: The battery cartridge identifier. - 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.2
- indexes:
- - labelname: upsHighPrecBatteryPackIndex
- type: gauge
- - labelname: upsHighPrecBatteryCartridgeIndex
- type: gauge
- - name: upsHighPrecBatteryPackFirmwareRevision
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.3
- type: DisplayString
- help: The battery pack firmware revision. - 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.3
- indexes:
- - labelname: upsHighPrecBatteryPackIndex
- type: gauge
- - labelname: upsHighPrecBatteryCartridgeIndex
- type: gauge
- - name: upsHighPrecBatteryPackSerialNumber
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.4
- type: DisplayString
- help: The battery pack serial number. - 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.4
- indexes:
- - labelname: upsHighPrecBatteryPackIndex
- type: gauge
- - labelname: upsHighPrecBatteryCartridgeIndex
- type: gauge
- - name: upsHighPrecBatteryPackTemperature
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.5
- type: gauge
- help: The battery pack temperature measured in 10ths of degree Celcius - 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.5
- indexes:
- - labelname: upsHighPrecBatteryPackIndex
- type: gauge
- - labelname: upsHighPrecBatteryCartridgeIndex
- type: gauge
- - name: upsHighPrecBatteryPackStatus
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.6
- type: OctetString
- help: The battery status for the pack only - 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.6
- indexes:
- - labelname: upsHighPrecBatteryPackIndex
- type: gauge
- - labelname: upsHighPrecBatteryCartridgeIndex
- type: gauge
- - name: upsHighPrecBatteryPackCartridgeHealth
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7
- type: OctetString
- help: The battery cartridge health - 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7
- indexes:
- - labelname: upsHighPrecBatteryPackIndex
- type: gauge
- - labelname: upsHighPrecBatteryCartridgeIndex
- type: gauge
- - name: upsHighPrecBatteryPackCartridgeReplaceDate
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8
- type: DisplayString
- help: The battery cartridge estimated battery replace date. - 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8
- indexes:
- - labelname: upsHighPrecBatteryPackIndex
- type: gauge
- - labelname: upsHighPrecBatteryCartridgeIndex
- type: gauge
- - name: upsHighPrecBatteryPackCartridgeInstallDate
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.9
- type: DisplayString
- help: The battery cartridge install date. - 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.9
- indexes:
- - labelname: upsHighPrecBatteryPackIndex
- type: gauge
- - labelname: upsHighPrecBatteryCartridgeIndex
- type: gauge
- - name: upsHighPrecBatteryPackCartridgeStatus
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.10
- type: OctetString
- help: The battery cartridge status - 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.10
- indexes:
- - labelname: upsHighPrecBatteryPackIndex
- type: gauge
- - labelname: upsHighPrecBatteryCartridgeIndex
- type: gauge
- - name: upsHighPrecBatteryPackOnlyTableSize
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.3
- type: gauge
- help: The number of entries in the upsHighPrecBatteryPacks. - 1.3.6.1.4.1.318.1.1.1.2.3.10.3
- - name: upsHighPrecBatteryPackOnlyIndex
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.1
- type: gauge
- help: The battery pack identifier. - 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.1
- indexes:
- - labelname: upsHighPrecBatteryPackOnlyIndex
- type: gauge
- - name: upsHighPrecBatteryPackOnlyFirmwareRevision
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.2
- type: DisplayString
- help: The battery pack firmware revision. - 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.2
- indexes:
- - labelname: upsHighPrecBatteryPackOnlyIndex
- type: gauge
- - name: upsHighPrecBatteryPackOnlySerialNumber
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.3
- type: DisplayString
- help: The battery pack serial number. - 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.3
- indexes:
- - labelname: upsHighPrecBatteryPackOnlyIndex
- type: gauge
- - name: upsHighPrecBatteryPackOnlyTemperature
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.4
- type: gauge
- help: The battery pack temperature measured in 10ths of degree Celcius - 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.4
- indexes:
- - labelname: upsHighPrecBatteryPackOnlyIndex
- type: gauge
- - name: upsHighPrecBatteryPackOnlyStatus
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.5
- type: OctetString
- help: The battery status for the pack only - 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.5
- indexes:
- - labelname: upsHighPrecBatteryPackOnlyIndex
- type: gauge
- - name: upsHighPrecBatteryPackOnlyHealth
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.6
- type: OctetString
- help: The battery pack health - 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.6
- indexes:
- - labelname: upsHighPrecBatteryPackOnlyIndex
- type: gauge
- - name: upsHighPrecBatteryPackOnlyReplaceDate
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.7
- type: DisplayString
- help: The battery pack estimated battery replace date. - 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.7
- indexes:
- - labelname: upsHighPrecBatteryPackOnlyIndex
- type: gauge
- - name: upsHighPrecBatteryPackOnlyInstallDate
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.8
- type: DisplayString
- help: The battery pack install date. - 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.8
- indexes:
- - labelname: upsHighPrecBatteryPackOnlyIndex
- type: gauge
- - name: upsHighPrecBatteryPackOnlyManufactureDate
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.9
- type: DisplayString
- help: The battery pack manufacture date. - 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.9
- indexes:
- - labelname: upsHighPrecBatteryPackOnlyIndex
- type: gauge
- - name: upsHighPrecBatteryPackOnlySKU
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.10
- type: DisplayString
- help: The battery pack SKU. - 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.10
- indexes:
- - labelname: upsHighPrecBatteryPackOnlyIndex
- type: gauge
- - name: upsHighPrecBatteryHealth
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.11
- type: OctetString
- help: The battery health - 1.3.6.1.4.1.318.1.1.1.2.3.11
- - name: upsHighPrecActivePower
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.12
- type: gauge
- help: Active Power of Battery in tenths of kW - 1.3.6.1.4.1.318.1.1.1.2.3.12
- - name: upsHighPrecExtdBatteryTemperature
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.13
- type: gauge
- help: The current internal UPS temperature expressed in tenths of degrees Celsius
- - 1.3.6.1.4.1.318.1.1.1.2.3.13
- - name: upsHighPrecMaximumModuleTemperature
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.14
- type: gauge
- help: The current maximum temperature across all battery modules in tenths of
- degrees Celsius - 1.3.6.1.4.1.318.1.1.1.2.3.14
- - name: upsHighPrecMinimumModuleTemperature
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.15
- type: gauge
- help: The current minimum temperature across all battery modules in tenths of
- degrees Celsius - 1.3.6.1.4.1.318.1.1.1.2.3.15
- - name: upsHighPrecMaximumCellVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.16
- type: gauge
- help: The current maximum cell voltage in mVDC across all batteries. - 1.3.6.1.4.1.318.1.1.1.2.3.16
- - name: upsHighPrecMinimumCellVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.2.3.17
- type: gauge
- help: The current minimum cell voltage in mVDC across all batteries. - 1.3.6.1.4.1.318.1.1.1.2.3.17
- - name: upsBatteryNumberOfCabinets
- oid: 1.3.6.1.4.1.318.1.1.1.2.4
- type: gauge
- help: The value indicates the number of battery cabinets in total, internal
- and external - 1.3.6.1.4.1.318.1.1.1.2.4
- - name: upsBatteryCabinetIndex
- oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.1
- type: gauge
- help: The Battery Cabinet identifier - 1.3.6.1.4.1.318.1.1.1.2.5.1.1
- indexes:
- - labelname: upsBatteryCabinetIndex
- type: gauge
- - name: upsBatteryCabinetLocalIndex
- oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.2
- type: gauge
- help: The identification number for the actual battery cabinet in the system
- - 1.3.6.1.4.1.318.1.1.1.2.5.1.2
- indexes:
- - labelname: upsBatteryCabinetIndex
- type: gauge
- - name: upsBatteryCabinetWiringConfiguration
- oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.3
- type: gauge
- help: The value indicates the wiring configuration, whether the battery is 2-wire
- or 3-wire - 1.3.6.1.4.1.318.1.1.1.2.5.1.3
- indexes:
- - labelname: upsBatteryCabinetIndex
- type: gauge
- enum_values:
- 1: twoWire
- 2: threeWire
- - name: upsBatteryCabinetVoltagePolarity1
- oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.4
- type: gauge
- help: The battery voltage - 1.3.6.1.4.1.318.1.1.1.2.5.1.4
- indexes:
- - labelname: upsBatteryCabinetIndex
- type: gauge
- - name: upsBatteryCabinetVoltagePolarity2
- oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.5
- type: gauge
- help: The voltage for the second side/half of the battery in a split battery
- system - 1.3.6.1.4.1.318.1.1.1.2.5.1.5
- indexes:
- - labelname: upsBatteryCabinetIndex
- type: gauge
- - name: upsBatteryCabinetCurrentPolarity1
- oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.6
- type: gauge
- help: The battery current - 1.3.6.1.4.1.318.1.1.1.2.5.1.6
- indexes:
- - labelname: upsBatteryCabinetIndex
- type: gauge
- - name: upsBatteryCabinetCurrentPolarity2
- oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.7
- type: gauge
- help: The current for the second side/half of the battery in a split battery
- system - 1.3.6.1.4.1.318.1.1.1.2.5.1.7
- indexes:
- - labelname: upsBatteryCabinetIndex
- type: gauge
- - name: upsBatteryCabinetTemperature
- oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.8
- type: gauge
- help: The measured temperature of the battery cabinet in tenths of degrees Celcius
- - 1.3.6.1.4.1.318.1.1.1.2.5.1.8
- indexes:
- - labelname: upsBatteryCabinetIndex
- type: gauge
- - name: upsBatteryCabinetMaxTemperature
- oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.9
- type: gauge
- help: The highest temperature measured for the battery in the battery cabinet
- in tenths of degrees Celcius - 1.3.6.1.4.1.318.1.1.1.2.5.1.9
- indexes:
- - labelname: upsBatteryCabinetIndex
- type: gauge
- - name: upsBatteryCabinetMinTemperature
- oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.10
- type: gauge
- help: The lowest temperature measured for the battery in the battery cabinet
- in tenths of degrees Celcius - 1.3.6.1.4.1.318.1.1.1.2.5.1.10
- indexes:
- - labelname: upsBatteryCabinetIndex
- type: gauge
- - name: upsBatteryCabinetAverageTemperature
- oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.11
- type: gauge
- help: The average temperature for all the battery sensors in the battery cabinet
- and for the battery strings, if battery strings are present - 1.3.6.1.4.1.318.1.1.1.2.5.1.11
- indexes:
- - labelname: upsBatteryCabinetIndex
- type: gauge
- - name: upsBatteryCabinetFuse
- oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.12
- type: gauge
- help: If the battery cabinet has a common fuse, the status is given by this
- value - 1.3.6.1.4.1.318.1.1.1.2.5.1.12
- indexes:
- - labelname: upsBatteryCabinetIndex
- type: gauge
- enum_values:
- 1: fuseOpen
- 2: fuseOk
- 3: notPresent
- - name: upsBatteryCabinetBreaker
- oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.13
- type: gauge
- help: The value indicates the battery cabinet breaker status - 1.3.6.1.4.1.318.1.1.1.2.5.1.13
- indexes:
- - labelname: upsBatteryCabinetIndex
- type: gauge
- enum_values:
- 1: noBreaker
- 2: unknown
- 3: breakerOpen
- 4: breakerClosed
- - name: upsBatteryCabinetNumberOfStrings
- oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.14
- type: gauge
- help: The number of battery strings in the battery cabinet - 1.3.6.1.4.1.318.1.1.1.2.5.1.14
- indexes:
- - labelname: upsBatteryCabinetIndex
- type: gauge
- - name: upsBatteryCabinetNumberOfVerticalPositions
- oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.15
- type: gauge
- help: The number of vertical levels or shelves for battery blocks/modules -
- 1.3.6.1.4.1.318.1.1.1.2.5.1.15
- indexes:
- - labelname: upsBatteryCabinetIndex
- type: gauge
- - name: upsBatteryCabinetNumberOfHorizontalPositions
- oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.16
- type: gauge
- help: The number of horizontal positions for battery blocks/modules - 1.3.6.1.4.1.318.1.1.1.2.5.1.16
- indexes:
- - labelname: upsBatteryCabinetIndex
- type: gauge
- - name: upsBatteryCabStringIndex
- oid: 1.3.6.1.4.1.318.1.1.1.2.6.1.1
- type: gauge
- help: The battery cabinet string identifier - 1.3.6.1.4.1.318.1.1.1.2.6.1.1
- indexes:
- - labelname: upsBatteryCabStringIndex
- type: gauge
- - name: upsBatteryCabStringCabReference
- oid: 1.3.6.1.4.1.318.1.1.1.2.6.1.2
- type: gauge
- help: Reference to the global battery cabinet index where the battery string
- is placed. - 1.3.6.1.4.1.318.1.1.1.2.6.1.2
- indexes:
- - labelname: upsBatteryCabStringIndex
- type: gauge
- - name: upsBatteryCabStringLocalIndex
- oid: 1.3.6.1.4.1.318.1.1.1.2.6.1.3
- type: gauge
- help: Local battery string identification index in the actual battery cabinet
- (e.g - 1.3.6.1.4.1.318.1.1.1.2.6.1.3
- indexes:
- - labelname: upsBatteryCabStringIndex
- type: gauge
- - name: upsBatteryCabStringCurrent
- oid: 1.3.6.1.4.1.318.1.1.1.2.6.1.4
- type: gauge
- help: The current in a battery string or battery halfstring, in tenths of Amps.
- - 1.3.6.1.4.1.318.1.1.1.2.6.1.4
- indexes:
- - labelname: upsBatteryCabStringIndex
- type: gauge
- - name: upsBatteryCabStringAverageTemperature
- oid: 1.3.6.1.4.1.318.1.1.1.2.6.1.5
- type: gauge
- help: Temperature of the battery string or the average of the aggregated temperature
- of each battery block/module (in tenths of degrees Celcius). - 1.3.6.1.4.1.318.1.1.1.2.6.1.5
- indexes:
- - labelname: upsBatteryCabStringIndex
- type: gauge
- - name: upsBatteryCabStringMaxTemperature
- oid: 1.3.6.1.4.1.318.1.1.1.2.6.1.6
- type: gauge
- help: The actual highest battery temperature measurement for the battery blocks/modules
- (in tenths of degrees Celcius). - 1.3.6.1.4.1.318.1.1.1.2.6.1.6
- indexes:
- - labelname: upsBatteryCabStringIndex
- type: gauge
- - name: upsBatteryCabStringMinTemperature
- oid: 1.3.6.1.4.1.318.1.1.1.2.6.1.7
- type: gauge
- help: The actual lowest battery temperature measurement for the battery blocks/modules
- (in tenths of degrees Celcius). - 1.3.6.1.4.1.318.1.1.1.2.6.1.7
- indexes:
- - labelname: upsBatteryCabStringIndex
- type: gauge
- - name: upsBatteryCabStringFuseStatus
- oid: 1.3.6.1.4.1.318.1.1.1.2.6.1.8
- type: gauge
- help: If the battery string has a common fuse, the status is given by this value
- - 1.3.6.1.4.1.318.1.1.1.2.6.1.8
- indexes:
- - labelname: upsBatteryCabStringIndex
- type: gauge
- enum_values:
- 1: fuseOpen
- 2: fuseOk
- 3: notPresent
- - name: upsBatteryCabStringNumberOfBlocks
- oid: 1.3.6.1.4.1.318.1.1.1.2.6.1.9
- type: gauge
- help: The number of battery blocks/modules in a battery string - 1.3.6.1.4.1.318.1.1.1.2.6.1.9
- indexes:
- - labelname: upsBatteryCabStringIndex
- type: gauge
- - name: upsBatteryCabBlockIndex
- oid: 1.3.6.1.4.1.318.1.1.1.2.7.1.1
- type: gauge
- help: The battery cabinet block identifier - 1.3.6.1.4.1.318.1.1.1.2.7.1.1
- indexes:
- - labelname: upsBatteryCabBlockIndex
- type: gauge
- - name: upsBatteryCabBlockStringReference
- oid: 1.3.6.1.4.1.318.1.1.1.2.7.1.2
- type: gauge
- help: Reference to the specific global battery string index - 1.3.6.1.4.1.318.1.1.1.2.7.1.2
- indexes:
- - labelname: upsBatteryCabBlockIndex
- type: gauge
- - name: upsBatteryCabBlockLocalIndex
- oid: 1.3.6.1.4.1.318.1.1.1.2.7.1.3
- type: gauge
- help: Local battery block/module identification index in the actual battery
- string (e.g - 1.3.6.1.4.1.318.1.1.1.2.7.1.3
- indexes:
- - labelname: upsBatteryCabBlockIndex
- type: gauge
- - name: upsBatteryCabBlockPresent
- oid: 1.3.6.1.4.1.318.1.1.1.2.7.1.4
- type: gauge
- help: Value indicates if battery block/module is present in the system - 1.3.6.1.4.1.318.1.1.1.2.7.1.4
- indexes:
- - labelname: upsBatteryCabBlockIndex
- type: gauge
- enum_values:
- 1: present
- 2: notPresent
- 3: notAvailable
- - name: upsBatteryCabBlockType
- oid: 1.3.6.1.4.1.318.1.1.1.2.7.1.5
- type: DisplayString
- help: Text string value, showing the vendor and model of the battery in the
- battery block/module - 1.3.6.1.4.1.318.1.1.1.2.7.1.5
- indexes:
- - labelname: upsBatteryCabBlockIndex
- type: gauge
- - name: upsBatteryCabBlockTemperature
- oid: 1.3.6.1.4.1.318.1.1.1.2.7.1.6
- type: gauge
- help: The temperature for the battery block/module in tenths of degrees Celcius
- - 1.3.6.1.4.1.318.1.1.1.2.7.1.6
- indexes:
- - labelname: upsBatteryCabBlockIndex
- type: gauge
- - name: upsBatteryCabBlockFuseStatus
- oid: 1.3.6.1.4.1.318.1.1.1.2.7.1.7
- type: gauge
- help: If the battery module has a fuse, the status is given by this value -
- 1.3.6.1.4.1.318.1.1.1.2.7.1.7
- indexes:
- - labelname: upsBatteryCabBlockIndex
- type: gauge
- enum_values:
- 1: fuseOpen
- 2: fuseOk
- 3: notPresent
- - name: upsBatteryCabBlockVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.2.7.1.8
- type: gauge
- help: The voltage of the battery block/module - 1.3.6.1.4.1.318.1.1.1.2.7.1.8
- indexes:
- - labelname: upsBatteryCabBlockIndex
- type: gauge
- - name: upsBatteryCabBlockNumberOfCells
- oid: 1.3.6.1.4.1.318.1.1.1.2.7.1.9
- type: gauge
- help: The number of cells in the battery block/module - 1.3.6.1.4.1.318.1.1.1.2.7.1.9
- indexes:
- - labelname: upsBatteryCabBlockIndex
- type: gauge
- - name: upsBatteryCabBlockVerticalPosition
- oid: 1.3.6.1.4.1.318.1.1.1.2.7.1.10
- type: gauge
- help: The vertical position of the battery block/module in the actual battery
- cabinet (e.g - 1.3.6.1.4.1.318.1.1.1.2.7.1.10
- indexes:
- - labelname: upsBatteryCabBlockIndex
- type: gauge
- - name: upsBatteryCabBlockHorizontalPosition
- oid: 1.3.6.1.4.1.318.1.1.1.2.7.1.11
- type: gauge
- help: The horizontal position of the battery block/module in the actual battery
- cabinet (e.g - 1.3.6.1.4.1.318.1.1.1.2.7.1.11
- indexes:
- - labelname: upsBatteryCabBlockIndex
- type: gauge
- - name: upsBatteryCabBlockCellIndex
- oid: 1.3.6.1.4.1.318.1.1.1.2.8.1.1
- type: gauge
- help: The battery block cell identifier - 1.3.6.1.4.1.318.1.1.1.2.8.1.1
- indexes:
- - labelname: upsBatteryCabBlockCellIndex
- type: gauge
- - name: upsBatteryCabBlockCellReference
- oid: 1.3.6.1.4.1.318.1.1.1.2.8.1.2
- type: gauge
- help: Reference to the specific global battery block/module index. - 1.3.6.1.4.1.318.1.1.1.2.8.1.2
- indexes:
- - labelname: upsBatteryCabBlockCellIndex
- type: gauge
- - name: upsBatteryCabBlockCellLocalIndex
- oid: 1.3.6.1.4.1.318.1.1.1.2.8.1.3
- type: gauge
- help: Local battery block/module identification index in the actual battery
- block (e.g - 1.3.6.1.4.1.318.1.1.1.2.8.1.3
- indexes:
- - labelname: upsBatteryCabBlockCellIndex
- type: gauge
- - name: upsBatteryCabBlockCellVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.2.8.1.4
- type: gauge
- help: The measured battery cell voltage - 1.3.6.1.4.1.318.1.1.1.2.8.1.4
- indexes:
- - labelname: upsBatteryCabBlockCellIndex
- type: gauge
- - name: upsBatteryCabBlockCellTemperature
- oid: 1.3.6.1.4.1.318.1.1.1.2.8.1.5
- type: gauge
- help: The temperature for the battery cell in tenths of degrees Celcius - 1.3.6.1.4.1.318.1.1.1.2.8.1.5
- indexes:
- - labelname: upsBatteryCabBlockCellIndex
- type: gauge
- - name: upsBasicInputPhase
- oid: 1.3.6.1.4.1.318.1.1.1.3.1.1
- type: gauge
- help: The current AC input phase. - 1.3.6.1.4.1.318.1.1.1.3.1.1
- - name: upsAdvInputLineVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.1
- type: gauge
- help: The current utility line voltage in VAC. - 1.3.6.1.4.1.318.1.1.1.3.2.1
- - name: upsAdvInputMaxLineVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.2
- type: gauge
- help: The maximum utility line voltage in VAC over the previous 1 minute period.
- - 1.3.6.1.4.1.318.1.1.1.3.2.2
- - name: upsAdvInputMinLineVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.3
- type: gauge
- help: The minimum utility line voltage in VAC over the previous 1 minute period.
- - 1.3.6.1.4.1.318.1.1.1.3.2.3
- - name: upsAdvInputFrequency
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.4
- type: gauge
- help: The current input frequency to the UPS system in Hz. - 1.3.6.1.4.1.318.1.1.1.3.2.4
- - name: upsAdvInputLineFailCause
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.5
- type: gauge
- help: The reason for the occurrence of the last transfer to UPS battery power
- - 1.3.6.1.4.1.318.1.1.1.3.2.5
- enum_values:
- 1: noTransfer
- 2: highLineVoltage
- 3: brownout
- 4: blackout
- 5: smallMomentarySag
- 6: deepMomentarySag
- 7: smallMomentarySpike
- 8: largeMomentarySpike
- 9: selfTest
- 10: rateOfVoltageChange
- - name: upsAdvInputNominalFrequency
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.6
- type: gauge
- help: The nominal input frequency of the UPS system in Hz. - 1.3.6.1.4.1.318.1.1.1.3.2.6
- - name: upsAdvInputNominalVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.7
- type: gauge
- help: The nominal input voltage of the UPS system in VAC. - 1.3.6.1.4.1.318.1.1.1.3.2.7
- - name: upsAdvInputBypassNominalFrequency
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.8
- type: gauge
- help: The nominal bypass input frequency of the UPS system in Hz. - 1.3.6.1.4.1.318.1.1.1.3.2.8
- - name: upsAdvInputBypassNominalVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.9
- type: gauge
- help: The nominal bypass input voltage of the UPS system in VAC. - 1.3.6.1.4.1.318.1.1.1.3.2.9
- - name: upsAdvInputStatisticsIndex
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.10.1.1
- type: gauge
- help: The input identifier. - 1.3.6.1.4.1.318.1.1.1.3.2.10.1.1
- indexes:
- - labelname: upsAdvInputStatisticsIndex
- type: gauge
- - name: upsAdvInputApparentPower
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.10.1.2
- type: gauge
- help: The input apparent power(sum of all of the three phases) measured in kVA.
- - 1.3.6.1.4.1.318.1.1.1.3.2.10.1.2
- indexes:
- - labelname: upsAdvInputStatisticsIndex
- type: gauge
- - name: upsAdvInputVoltageTHD
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.10.1.3
- type: gauge
- help: The input voltage Total Harmonic Distortion in percent. - 1.3.6.1.4.1.318.1.1.1.3.2.10.1.3
- indexes:
- - labelname: upsAdvInputStatisticsIndex
- type: gauge
- - name: upsAdvInputBypassVoltageTHD
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.10.1.4
- type: gauge
- help: The bypass input voltage Total Harmonic Distortion in percent. - 1.3.6.1.4.1.318.1.1.1.3.2.10.1.4
- indexes:
- - labelname: upsAdvInputStatisticsIndex
- type: gauge
- - name: upsAdvInputPeakCurrent
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.10.1.5
- type: gauge
- help: The input peak current in Amperes. - 1.3.6.1.4.1.318.1.1.1.3.2.10.1.5
- indexes:
- - labelname: upsAdvInputStatisticsIndex
- type: gauge
- - name: upsAdvInputBypassPeakCurrent
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.10.1.6
- type: gauge
- help: The bypass input peak current in Amperes. - 1.3.6.1.4.1.318.1.1.1.3.2.10.1.6
- indexes:
- - labelname: upsAdvInputStatisticsIndex
- type: gauge
- - name: upsAdvInputActivePower
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.10.1.7
- type: gauge
- help: The input active power measured in kW. - 1.3.6.1.4.1.318.1.1.1.3.2.10.1.7
- indexes:
- - labelname: upsAdvInputStatisticsIndex
- type: gauge
- - name: upsAdvInputTotalApparentPower
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.11
- type: gauge
- help: The input total apparent power(sum of all three phases) of the UPS system
- in kVA. - 1.3.6.1.4.1.318.1.1.1.3.2.11
- - name: upsAdvInputTotalActivePower
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.12
- type: gauge
- help: The input total active power(sum of all three phases) of the UPS system
- in kW - 1.3.6.1.4.1.318.1.1.1.3.2.12
- - name: upsAdvInputBypassTotalApparentPower
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.13
- type: gauge
- help: The input bypass total apparent power(sum of all three phases) of the
- UPS system in kVA. - 1.3.6.1.4.1.318.1.1.1.3.2.13
- - name: upsAdvInputBypassTotalActivePower
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.14
- type: gauge
- help: The input bypass total active power(sum of all three phases) of the UPS
- system in kW. - 1.3.6.1.4.1.318.1.1.1.3.2.14
- - name: upsAdvInputEnergyUsage
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.15
- type: gauge
- help: The input energy usage of the UPS in kWh. - 1.3.6.1.4.1.318.1.1.1.3.2.15
- - name: upsAdvInputDCVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.16
- type: gauge
- help: The DC input voltage in Volts. - 1.3.6.1.4.1.318.1.1.1.3.2.16
- - name: upsAdvInputDCCurrent
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.17
- type: gauge
- help: The DC input current in Amps. - 1.3.6.1.4.1.318.1.1.1.3.2.17
- - name: upsAdvInputNominalDCVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.3.2.18
- type: gauge
- help: The nominal input DC voltage of the inverter in Volts - 1.3.6.1.4.1.318.1.1.1.3.2.18
- - name: upsHighPrecInputLineVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.3.3.1
- type: gauge
- help: The current utility line voltage in tenths of VAC. - 1.3.6.1.4.1.318.1.1.1.3.3.1
- - name: upsHighPrecInputMaxLineVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.3.3.2
- type: gauge
- help: The maximum utility line voltage in tenths of VAC over the previous 1
- minute period. - 1.3.6.1.4.1.318.1.1.1.3.3.2
- - name: upsHighPrecInputMinLineVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.3.3.3
- type: gauge
- help: The minimum utility line voltage in tenths of VAC over the previous 1
- minute period. - 1.3.6.1.4.1.318.1.1.1.3.3.3
- - name: upsHighPrecInputFrequency
- oid: 1.3.6.1.4.1.318.1.1.1.3.3.4
- type: gauge
- help: The current input frequency to the UPS system in tenths of Hz. - 1.3.6.1.4.1.318.1.1.1.3.3.4
- - name: upsHighPrecInputEnergyUsage
- oid: 1.3.6.1.4.1.318.1.1.1.3.3.5
- type: gauge
- help: The input energy usage of the UPS in hundredths of kWh. - 1.3.6.1.4.1.318.1.1.1.3.3.5
- - name: upsHighPrecInputBypassVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.3.3.6
- type: gauge
- help: The current bypass line voltage in tenths of VAC. - 1.3.6.1.4.1.318.1.1.1.3.3.6
- - name: upsHighPrecInputBypassFrequency
- oid: 1.3.6.1.4.1.318.1.1.1.3.3.7
- type: gauge
- help: The current input bypass frequency to the UPS system in tenths of Hz.
- - 1.3.6.1.4.1.318.1.1.1.3.3.7
- - name: upsHighPrecInputDCVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.3.3.8
- type: gauge
- help: The DC input voltage, in tenths, of Volts on the inverter - 1.3.6.1.4.1.318.1.1.1.3.3.8
- - name: upsHighPrecInputDCCurrent
- oid: 1.3.6.1.4.1.318.1.1.1.3.3.9
- type: gauge
- help: The DC input current, in tenths of amperes, of the inverter. - 1.3.6.1.4.1.318.1.1.1.3.3.9
- - name: upsBasicOutputStatus
- oid: 1.3.6.1.4.1.318.1.1.1.4.1.1
- type: gauge
- help: The current state of the UPS - 1.3.6.1.4.1.318.1.1.1.4.1.1
- enum_values:
- 1: unknown
- 2: onLine
- 3: onBattery
- 4: onSmartBoost
- 5: timedSleeping
- 6: softwareBypass
- 7: "off"
- 8: rebooting
- 9: switchedBypass
- 10: hardwareFailureBypass
- 11: sleepingUntilPowerReturn
- 12: onSmartTrim
- 13: ecoMode
- 14: hotStandby
- 15: onBatteryTest
- 16: emergencyStaticBypass
- 17: staticBypassStandby
- 18: powerSavingMode
- 19: spotMode
- 20: eConversion
- 21: chargerSpotmode
- 22: inverterSpotmode
- 23: activeLoad
- 24: batteryDischargeSpotmode
- 25: inverterStandby
- 26: chargerOnly
- 27: distributedEnergyReserve
- 28: selfTest
- - name: upsBasicOutputPhase
- oid: 1.3.6.1.4.1.318.1.1.1.4.1.2
- type: gauge
- help: The actual number of output phases in a UPS - 1.3.6.1.4.1.318.1.1.1.4.1.2
- - name: upsBasicSystemStatus
- oid: 1.3.6.1.4.1.318.1.1.1.4.1.3
- type: gauge
- help: Current state for the whole system (UPS and surrounding breakers) - 1.3.6.1.4.1.318.1.1.1.4.1.3
- enum_values:
- 1: unknown
- 2: onLine
- 3: onBattery
- 4: onSmartBoost
- 5: timedSleeping
- 6: softwareBypass
- 7: "off"
- 8: rebooting
- 9: switchedBypass
- 10: hardwareFailureBypass
- 11: sleepingUntilPowerReturn
- 12: onSmartTrim
- 13: ecoMode
- 14: inverter
- 15: eConversion
- 16: staticBypassStandby
- 17: efficiencyBoosterMode
- - name: upsBasicSystemInternalTemperature
- oid: 1.3.6.1.4.1.318.1.1.1.4.1.4
- type: gauge
- help: The actual internal temperature of the UPS system in Celsius. - 1.3.6.1.4.1.318.1.1.1.4.1.4
- - name: upsBasicSystemInverterStatus
- oid: 1.3.6.1.4.1.318.1.1.1.4.1.5
- type: gauge
- help: The current state of the UPS inverter - 1.3.6.1.4.1.318.1.1.1.4.1.5
- enum_values:
- 1: unknown
- 2: ok
- 3: inFaultCondition
- - name: upsBasicSystemPFCStatus
- oid: 1.3.6.1.4.1.318.1.1.1.4.1.6
- type: gauge
- help: The general status of the power factor correction (AC input stage of the
- UPS) - 1.3.6.1.4.1.318.1.1.1.4.1.6
- enum_values:
- 1: unknown
- 2: ok
- 3: inFaultCondition
- - name: upsBasicOutputACwiringConfiguration
- oid: 1.3.6.1.4.1.318.1.1.1.4.1.7
- type: gauge
- help: Indicates if neutral wire on output side of the UPS is used (load wired
- line to neutral) - 1.3.6.1.4.1.318.1.1.1.4.1.7
- enum_values:
- 1: unknown
- 2: noNeutralWiredonSystem
- 3: neutralUsedforSupplyingLoad
- - name: upsAdvOutputVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.1
- type: gauge
- help: The output voltage of the UPS system in VAC. - 1.3.6.1.4.1.318.1.1.1.4.2.1
- - name: upsAdvOutputFrequency
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.2
- type: gauge
- help: The current output frequency of the UPS system in Hz. - 1.3.6.1.4.1.318.1.1.1.4.2.2
- - name: upsAdvOutputLoad
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.3
- type: gauge
- help: The current UPS load expressed in percent of rated capacity. - 1.3.6.1.4.1.318.1.1.1.4.2.3
- - name: upsAdvOutputCurrent
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.4
- type: gauge
- help: The current in amperes drawn by the load on the UPS. - 1.3.6.1.4.1.318.1.1.1.4.2.4
- - name: upsAdvOutputRedundancy
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.5
- type: gauge
- help: The number of power modules which can fail or be removed without causing
- the UPS to generate a Minimum Redundancy Lost event. - 1.3.6.1.4.1.318.1.1.1.4.2.5
- - name: upsAdvOutputKVACapacity
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.6
- type: gauge
- help: The maximum load that this UPS can support - 1.3.6.1.4.1.318.1.1.1.4.2.6
- - name: upsAdvOutputNominalFrequency
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.7
- type: gauge
- help: The nominal output frequency of the UPS system in Hz. - 1.3.6.1.4.1.318.1.1.1.4.2.7
- - name: upsAdvOutputActivePower
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.8
- type: gauge
- help: The total output active power of the UPS system in W - 1.3.6.1.4.1.318.1.1.1.4.2.8
- - name: upsAdvOutputApparentPower
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.9
- type: gauge
- help: The total output apparent power of all phases of the UPS system in VA
- - 1.3.6.1.4.1.318.1.1.1.4.2.9
- - name: upsAdvOutputStatisticsIndex
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.10.1.1
- type: gauge
- help: The output identifier. - 1.3.6.1.4.1.318.1.1.1.4.2.10.1.1
- indexes:
- - labelname: upsAdvOutputStatisticsIndex
- type: gauge
- - name: upsAdvOutputPeakCurrent
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.10.1.2
- type: gauge
- help: The output peak current in Amperes. - 1.3.6.1.4.1.318.1.1.1.4.2.10.1.2
- indexes:
- - labelname: upsAdvOutputStatisticsIndex
- type: gauge
- - name: upsAdvOutputCurrentTHD
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.10.1.3
- type: gauge
- help: The output current Total Harmonic Distortion in percent. - 1.3.6.1.4.1.318.1.1.1.4.2.10.1.3
- indexes:
- - labelname: upsAdvOutputStatisticsIndex
- type: gauge
- - name: upsAdvOutputCrestFactor
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.10.1.4
- type: gauge
- help: The output current crest factor expressed in tenths. - 1.3.6.1.4.1.318.1.1.1.4.2.10.1.4
- indexes:
- - labelname: upsAdvOutputStatisticsIndex
- type: gauge
- - name: upsAdvOutputNeutralCurrent
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.11
- type: gauge
- help: The neutral current in amperes. - 1.3.6.1.4.1.318.1.1.1.4.2.11
- - name: upsAdvOutputEnergyUsage
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.12
- type: gauge
- help: The output energy usage of the UPS in kWh. - 1.3.6.1.4.1.318.1.1.1.4.2.12
- - name: upsAdvOutputSourceSynchronization
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.13
- type: gauge
- help: Indicates the synchronization source for the inverter output frequency
- - 1.3.6.1.4.1.318.1.1.1.4.2.13
- - name: upsAdvOutputInverterFrequency
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.14
- type: gauge
- help: Output frequency in Hz measured at the output of inverter. - 1.3.6.1.4.1.318.1.1.1.4.2.14
- - name: upsAdvOutputInverterLoad
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.15
- type: gauge
- help: The total active power at the output of all inverter modules in percent
- of rated system power (% of kW) If not supported, return -1. - 1.3.6.1.4.1.318.1.1.1.4.2.15
- - name: upsAdvOutputPercentPower
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.16
- type: gauge
- help: The relative active power at the output of the inverter system (static
- switch output) in percent of rated system power (% of kW) - 1.3.6.1.4.1.318.1.1.1.4.2.16
- - name: upsAdvOutputInverterActivePower
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.17
- type: gauge
- help: The total active power at the output of all inverter modules in kW - 1.3.6.1.4.1.318.1.1.1.4.2.17
- - name: upsAdvOutputPercentLoad
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.18
- type: gauge
- help: The relative apparent power at the output of the inverter system (static
- switch output) in percent of rated system load (% of kVA) If not supported,
- return -1. - 1.3.6.1.4.1.318.1.1.1.4.2.18
- - name: upsAdvOutputInverterCurrent
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.19
- type: gauge
- help: The current, in amperes, drawn by the load on the inverter. - 1.3.6.1.4.1.318.1.1.1.4.2.19
- - name: upsAdvOutputReactivePower
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.20
- type: gauge
- help: The total output reactive power of all phases of the UPS system in VAR
- - 1.3.6.1.4.1.318.1.1.1.4.2.20
- - name: upsAdvOutputInverterVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.21
- type: gauge
- help: The output voltage of the inverter in VAC. - 1.3.6.1.4.1.318.1.1.1.4.2.21
- - name: upsAdvOutputUpperAcceptPowerSettingPct
- oid: 1.3.6.1.4.1.318.1.1.1.4.2.22
- type: gauge
- help: Upper acceptable voltage as percent of nominal voltage - 1.3.6.1.4.1.318.1.1.1.4.2.22
- - name: upsHighPrecOutputVoltage
- oid: 1.3.6.1.4.1.318.1.1.1.4.3.1
- type: gauge
- help: The output voltage of the UPS system in tenths of VAC. - 1.3.6.1.4.1.318.1.1.1.4.3.1
- - name: upsHighPrecOutputFrequency
- oid: 1.3.6.1.4.1.318.1.1.1.4.3.2
- type: gauge
- help: The current output frequency of the UPS system in tenths of Hz. - 1.3.6.1.4.1.318.1.1.1.4.3.2
- - name: upsHighPrecOutputLoad
- oid: 1.3.6.1.4.1.318.1.1.1.4.3.3
- type: gauge
- help: The current UPS load expressed in tenths of percent of rated capacity.
- - 1.3.6.1.4.1.318.1.1.1.4.3.3
- - name: upsHighPrecOutputCurrent
- oid: 1.3.6.1.4.1.318.1.1.1.4.3.4
- type: gauge
- help: The current in tenths of amperes drawn by the load on the UPS. - 1.3.6.1.4.1.318.1.1.1.4.3.4
- - name: upsHighPrecOutputEfficiency
- oid: 1.3.6.1.4.1.318.1.1.1.4.3.5
- type: gauge
- help: The positive values represent efficiency of the UPS in tenths of percent
- - 1.3.6.1.4.1.318.1.1.1.4.3.5
- - name: upsHighPrecOutputEnergyUsage
- oid: 1.3.6.1.4.1.318.1.1.1.4.3.6
- type: gauge
- help: The output energy usage of the UPS in hundredths of kWh. - 1.3.6.1.4.1.318.1.1.1.4.3.6
- - name: upsAdvTestDiagnosticSchedule
- oid: 1.3.6.1.4.1.318.1.1.1.7.2.1
- type: gauge
- help: The UPS system's automatic battery test schedule. - 1.3.6.1.4.1.318.1.1.1.7.2.1
- enum_values:
- 1: unknown
- 2: biweekly
- 3: weekly
- 4: atTurnOn
- 5: never
- 6: fourWeeks
- 7: twelveWeeks
- 8: biweeklySinceLastTest
- 9: weeklySinceLastTest
- 10: eightWeeks
- 11: twentysixWeeks
- 12: fiftytwoWeeks
- - name: upsAdvTestDiagnostics
- oid: 1.3.6.1.4.1.318.1.1.1.7.2.2
- type: gauge
- help: Setting this variable to testDiagnostics(2) causes the UPS to perform
- a diagnostic self test - 1.3.6.1.4.1.318.1.1.1.7.2.2
- enum_values:
- 1: noTestDiagnostics
- 2: testDiagnostics
- - name: upsAdvTestDiagnosticsResults
- oid: 1.3.6.1.4.1.318.1.1.1.7.2.3
- type: gauge
- help: The results of the last UPS diagnostics test performed. - 1.3.6.1.4.1.318.1.1.1.7.2.3
- enum_values:
- 1: ok
- 2: failed
- 3: invalidTest
- 4: testInProgress
- - name: upsAdvTestLastDiagnosticsDate
- oid: 1.3.6.1.4.1.318.1.1.1.7.2.4
- type: DisplayString
- help: The date the last UPS diagnostics test was performed in mm/dd/yy format.
- - 1.3.6.1.4.1.318.1.1.1.7.2.4
- - name: upsAdvTestRuntimeCalibration
- oid: 1.3.6.1.4.1.318.1.1.1.7.2.5
- type: gauge
- help: Setting this variable to performCalibration(2) causes the UPS to discharge
- to calibrate the UPS - 1.3.6.1.4.1.318.1.1.1.7.2.5
- enum_values:
- 1: noPerformCalibration
- 2: performCalibration
- 3: cancelCurrentCalibration
- - name: upsAdvTestCalibrationResults
- oid: 1.3.6.1.4.1.318.1.1.1.7.2.6
- type: gauge
- help: The results of the last runtime calibration - 1.3.6.1.4.1.318.1.1.1.7.2.6
- enum_values:
- 1: ok
- 2: invalidCalibration
- 3: calibrationInProgress
- 4: refused
- 5: aborted
- 6: pending
- 7: unknown
- - name: upsAdvTestCalibrationDate
- oid: 1.3.6.1.4.1.318.1.1.1.7.2.7
- type: DisplayString
- help: The date the last UPS runtime calibration was performed in mm/dd/yy format.
- - 1.3.6.1.4.1.318.1.1.1.7.2.7
- - name: upsAdvTestDiagnosticTime
- oid: 1.3.6.1.4.1.318.1.1.1.7.2.8
- type: DisplayString
- help: The time of the day to perform automatic battery test - 1.3.6.1.4.1.318.1.1.1.7.2.8
- - name: upsAdvTestDiagnosticDay
- oid: 1.3.6.1.4.1.318.1.1.1.7.2.9
- type: gauge
- help: The day of the week to perform automatic battery test. - 1.3.6.1.4.1.318.1.1.1.7.2.9
- enum_values:
- 1: monday
- 2: tuesday
- 3: wednesday
- 4: thursday
- 5: friday
- 6: saturday
- 7: sunday
- - name: upsAdvTestBatteryInterval
- oid: 1.3.6.1.4.1.318.1.1.1.7.2.10
- type: DisplayString
- help: The UPS system's automatic battery test period. - 1.3.6.1.4.1.318.1.1.1.7.2.10
- - name: upsAdvTestCalibrationLastSuccessfulDate
- oid: 1.3.6.1.4.1.318.1.1.1.7.2.11
- type: DisplayString
- help: The latest date when the UPS performed a successful runtime calibration
- test - 1.3.6.1.4.1.318.1.1.1.7.2.11
- - name: upsAdvTestBatteryLastSuccessfulDate
- oid: 1.3.6.1.4.1.318.1.1.1.7.2.12
- type: DisplayString
- help: The latest date when the UPS performed a successful battery diagnostic
- test (battery monitoring test) - 1.3.6.1.4.1.318.1.1.1.7.2.12
- - name: upsAdvTestBatteryLastDate
- oid: 1.3.6.1.4.1.318.1.1.1.7.2.13
- type: DisplayString
- help: The latest date when the UPS performed a battery diagnostic test (battery
- monitoring test), regardless of the test result.The format is YYYY-MM-DD -
- 1.3.6.1.4.1.318.1.1.1.7.2.13
- - name: upsAdvTestBatteryProcessStatus
- oid: 1.3.6.1.4.1.318.1.1.1.7.2.14
- type: gauge
- help: The results of the latest battery diagnostic test (battery monitoring
- test) - 1.3.6.1.4.1.318.1.1.1.7.2.14
- enum_values:
- 1: ok
- 2: preconditionNotMeet
- 3: batteryTestInProgress
- 4: refused
- 5: aborted
- 6: pending
- 7: unknown
- 8: noBatteryPresent
- - name: upsAdvTestBatteryConditionStatus
- oid: 1.3.6.1.4.1.318.1.1.1.7.2.15
- type: gauge
- help: Result of the latest successful test 1 = unknown 2 = battery OK 3 = battery
- capacity decreased 4 = battery defect 5 = indicate that no battery is present
- (no battery, battery breaker open,..) to perform the battery diagnostic test
- - 1.3.6.1.4.1.318.1.1.1.7.2.15
- enum_values:
- 1: unknown
- 2: batteryOK
- 3: batteryCapacityDecreased
- 4: batteryDefect
- 5: noBatteryPresent
- - name: upsAdvTestDiagnosticsBatteryInterval
- oid: 1.3.6.1.4.1.318.1.1.1.7.2.16
- type: gauge
- help: The battery test is a diagnostic test (also referred to as battery monitoring
- test) - 1.3.6.1.4.1.318.1.1.1.7.2.16
- enum_values:
- 1: never
- 2: weekly
- 3: biweekly
- 4: every4weeks
- 5: every8weeks
- 6: every12weeks
- 7: every26weeks
- 8: every52weeks
- - name: upsCommStatus
- oid: 1.3.6.1.4.1.318.1.1.1.8.1
- type: gauge
- help: The status of agent's communication with UPS. - 1.3.6.1.4.1.318.1.1.1.8.1
- enum_values:
- 1: ok
- 2: noComm
- - name: iemStatusProbeNumber
- oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.1
- type: gauge
- help: The index of the probe. - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.1
- indexes:
- - labelname: iemStatusProbeNumber
- type: gauge
- - name: iemStatusProbeName
- oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.2
- type: DisplayString
- help: A descriptive name for the probe set by the user. - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.2
- indexes:
- - labelname: iemStatusProbeNumber
- type: gauge
- - name: iemStatusProbeStatus
- oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.3
- type: gauge
- help: The connected status of the probe, either disconnected(1) or connected(2).
- - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.3
- indexes:
- - labelname: iemStatusProbeNumber
- type: gauge
- enum_values:
- 1: disconnected
- 2: connected
- - name: iemStatusProbeCurrentTemp
- oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.4
- type: gauge
- help: The current temperature reading from the probe displayed in the units
- shown in the 'iemStatusProbeTempUnits' OID (Celsius or Fahrenheit). - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.4
- indexes:
- - labelname: iemStatusProbeNumber
- type: gauge
- - name: iemStatusProbeTempUnits
- oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.5
- type: gauge
- help: The temperature scale used to display the temperature thresholds of the
- probe, Celsius(1) or Fahrenheit(2) - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.5
- indexes:
- - labelname: iemStatusProbeNumber
- type: gauge
- enum_values:
- 1: celsius
- 2: fahrenheit
- - name: iemStatusProbeCurrentHumid
- oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.6
- type: gauge
- help: The current humidity reading from the probe in percent relative humidity.
- - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.6
- indexes:
- - labelname: iemStatusProbeNumber
- type: gauge
- - name: iemStatusProbeHighTempViolation
- oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.7
- type: gauge
- help: The high temperature violation status of the probe temperature reading
- - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.7
- indexes:
- - labelname: iemStatusProbeNumber
- type: gauge
- enum_values:
- 1: noViolation
- 2: highTempViolation
- 3: disabled
- - name: iemStatusProbeLowTempViolation
- oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.8
- type: gauge
- help: The high temperature violation status of the probe temperature reading
- - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.8
- indexes:
- - labelname: iemStatusProbeNumber
- type: gauge
- enum_values:
- 1: noViolation
- 2: lowTempViolation
- 3: disabled
- - name: iemStatusProbeHighHumidViolation
- oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.9
- type: gauge
- help: The high humidity violation status of the probe humidity reading - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.9
- indexes:
- - labelname: iemStatusProbeNumber
- type: gauge
- enum_values:
- 1: noViolation
- 2: highHumidViolation
- 3: disabled
- - name: iemStatusProbeLowHumidViolation
- oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.10
- type: gauge
- help: The low humidity violation status of the probe humidity reading - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.10
- indexes:
- - labelname: iemStatusProbeNumber
- type: gauge
- enum_values:
- 1: noViolation
- 2: lowHumidViolation
- 3: disabled
- - name: iemStatusProbeMaxTempViolation
- oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.11
- type: gauge
- help: The max temperature violation status of the probe temperature reading
- - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.11
- indexes:
- - labelname: iemStatusProbeNumber
- type: gauge
- enum_values:
- 1: noViolation
- 2: maxTempViolation
- 3: disabled
- - name: iemStatusProbeMinTempViolation
- oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.12
- type: gauge
- help: The minimum temperature violation status of the probe temperature reading
- - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.12
- indexes:
- - labelname: iemStatusProbeNumber
- type: gauge
- enum_values:
- 1: noViolation
- 2: minTempViolation
- 3: disabled
- - name: iemStatusProbeMaxHumidViolation
- oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.13
- type: gauge
- help: The maximum humidity violation status of the probe humidity reading -
- 1.3.6.1.4.1.318.1.1.10.2.3.2.1.13
- indexes:
- - labelname: iemStatusProbeNumber
- type: gauge
- enum_values:
- 1: noViolation
- 2: maxHumidViolation
- 3: disabled
- - name: iemStatusProbeMinHumidViolation
- oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.14
- type: gauge
- help: The minimum humidity violation status of the probe humidity reading -
- 1.3.6.1.4.1.318.1.1.10.2.3.2.1.14
- indexes:
- - labelname: iemStatusProbeNumber
- type: gauge
- enum_values:
- 1: noViolation
- 2: minHumidViolation
- 3: disabled
- - name: iemStatusProbeLocation
- oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.15
- type: DisplayString
- help: A descriptive location for the probe set by the user. - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.15
- indexes:
- - labelname: iemStatusProbeNumber
- type: gauge
- - name: rPDU2SensorTempHumidityStatusIndex
- oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.1
- type: gauge
- help: The index to the temperature-humidity status data table entry - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.1
- indexes:
- - labelname: rPDU2SensorTempHumidityStatusIndex
- type: gauge
- - name: rPDU2SensorTempHumidityStatusModule
- oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.2
- type: gauge
- help: The user-defined Rack PDU numeric ID - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.2
- indexes:
- - labelname: rPDU2SensorTempHumidityStatusIndex
- type: gauge
- - name: rPDU2SensorTempHumidityStatusName
- oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.3
- type: DisplayString
- help: The user-defined temperature-humidity sensor ID string - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.3
- indexes:
- - labelname: rPDU2SensorTempHumidityStatusIndex
- type: gauge
- - name: rPDU2SensorTempHumidityStatusNumber
- oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.4
- type: gauge
- help: The temperature-humidity sensor numeric ID - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.4
- indexes:
- - labelname: rPDU2SensorTempHumidityStatusIndex
- type: gauge
- - name: rPDU2SensorTempHumidityStatusType
- oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.5
- type: gauge
- help: The type of the sensor - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.5
- indexes:
- - labelname: rPDU2SensorTempHumidityStatusIndex
- type: gauge
- enum_values:
- 1: temperatureOnly
- 2: temperatureHumidity
- 3: commsLost
- 4: notInstalled
- - name: rPDU2SensorTempHumidityStatusCommStatus
- oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.6
- type: gauge
- help: The communications status of the sensor - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.6
- indexes:
- - labelname: rPDU2SensorTempHumidityStatusIndex
- type: gauge
- enum_values:
- 1: notInstalled
- 2: commsOK
- 3: commsLost
- - name: rPDU2SensorTempHumidityStatusTempF
- oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.7
- type: gauge
- help: Sensor temperature reading in tenths of degrees Fahrenheit - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.7
- indexes:
- - labelname: rPDU2SensorTempHumidityStatusIndex
- type: gauge
- - name: rPDU2SensorTempHumidityStatusTempC
- oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.8
- type: gauge
- help: Sensor temperature reading in tenths of degrees Celsius - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.8
- indexes:
- - labelname: rPDU2SensorTempHumidityStatusIndex
- type: gauge
- - name: rPDU2SensorTempHumidityStatusTempStatus
- oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.9
- type: gauge
- help: This OID reports the current state of the temperature probe - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.9
- indexes:
- - labelname: rPDU2SensorTempHumidityStatusIndex
- type: gauge
- enum_values:
- 1: notPresent
- 2: belowMin
- 3: belowLow
- 4: normal
- 5: aboveHigh
- 6: aboveMax
- - name: rPDU2SensorTempHumidityStatusRelativeHumidity
- oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.10
- type: gauge
- help: Sensor humidity reading in percent relative humidity - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.10
- indexes:
- - labelname: rPDU2SensorTempHumidityStatusIndex
- type: gauge
- - name: rPDU2SensorTempHumidityStatusHumidityStatus
- oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.11
- type: gauge
- help: This OID reports the current state of the humidity probe - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.11
- indexes:
- - labelname: rPDU2SensorTempHumidityStatusIndex
- type: gauge
- enum_values:
- 1: notPresent
- 2: belowMin
- 3: belowLow
- 4: normal
- 5: aboveHigh
- 6: aboveMax
- - name: rPDU2SensorTempHumidityStatusTempPeakF
- oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.12
- type: gauge
- help: Sensor peak temperature in tenths of degrees Fahrenheit - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.12
- indexes:
- - labelname: rPDU2SensorTempHumidityStatusIndex
- type: gauge
- - name: rPDU2SensorTempHumidityStatusTempPeakC
- oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.13
- type: gauge
- help: Sensor peak temperature in tenths of degrees Celsius - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.13
- indexes:
- - labelname: rPDU2SensorTempHumidityStatusIndex
- type: gauge
- - name: rPDU2SensorTempHumidityStatusTempPeakTimestamp
- oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.14
- type: DisplayString
- help: Indicates the date and time that the peak temperature occurred - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.14
- indexes:
- - labelname: rPDU2SensorTempHumidityStatusIndex
- type: gauge
- - name: rPDU2SensorTempHumidityStatusTempPeakStartTime
- oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.15
- type: DisplayString
- help: Indicates the date and time of the last temperature peak reset - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.15
- indexes:
- - labelname: rPDU2SensorTempHumidityStatusIndex
- type: gauge
- - name: rPDU2DeviceStatusIndex
- oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.1
- type: gauge
- help: The index to the Rack PDU status table entry - 1.3.6.1.4.1.318.1.1.26.4.3.1.1
- indexes:
- - labelname: rPDU2DeviceStatusIndex
- type: gauge
- - name: rPDU2DeviceStatusModule
- oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.2
- type: gauge
- help: The user-defined Rack PDU numeric ID - 1.3.6.1.4.1.318.1.1.26.4.3.1.2
- indexes:
- - labelname: rPDU2DeviceStatusIndex
- type: gauge
- - name: rPDU2DeviceStatusName
- oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.3
- type: DisplayString
- help: A user-defined string identifying the Rack PDU - 1.3.6.1.4.1.318.1.1.26.4.3.1.3
- indexes:
- - labelname: rPDU2DeviceStatusIndex
- type: gauge
- - name: rPDU2DeviceStatusLoadState
- oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.4
- type: gauge
- help: Indicates the present load status of the Rack PDU - 1.3.6.1.4.1.318.1.1.26.4.3.1.4
- indexes:
- - labelname: rPDU2DeviceStatusIndex
- type: gauge
- enum_values:
- 1: lowLoad
- 2: normal
- 3: nearOverload
- 4: overload
- 5: notsupported
- - name: rPDU2DeviceStatusPower
- oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.5
- type: gauge
- help: The power consumption of the Rack PDU load in hundredths of kilowatts
- - 1.3.6.1.4.1.318.1.1.26.4.3.1.5
- indexes:
- - labelname: rPDU2DeviceStatusIndex
- type: gauge
- - name: rPDU2DeviceStatusPeakPower
- oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.6
- type: gauge
- help: The peak power consumption of the Rack PDU load in hundredths of kilowatts
- - 1.3.6.1.4.1.318.1.1.26.4.3.1.6
- indexes:
- - labelname: rPDU2DeviceStatusIndex
- type: gauge
- - name: rPDU2DeviceStatusPeakPowerTimestamp
- oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.7
- type: DisplayString
- help: Indicates the date and time that peak power consumption occurred - 1.3.6.1.4.1.318.1.1.26.4.3.1.7
- indexes:
- - labelname: rPDU2DeviceStatusIndex
- type: gauge
- - name: rPDU2DeviceStatusPeakPowerStartTime
- oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.8
- type: DisplayString
- help: Indicates the date and time of the last device peak power reset - 1.3.6.1.4.1.318.1.1.26.4.3.1.8
- indexes:
- - labelname: rPDU2DeviceStatusIndex
- type: gauge
- - name: rPDU2DeviceStatusEnergy
- oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.9
- type: gauge
- help: A user resettable energy meter measuring Rack PDU load energy consumption
- in tenths of kilowatt-hours - 1.3.6.1.4.1.318.1.1.26.4.3.1.9
- indexes:
- - labelname: rPDU2DeviceStatusIndex
- type: gauge
- - name: rPDU2DeviceStatusEnergyStartTime
- oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.10
- type: DisplayString
- help: Indicates the date and time of the last device energy meter reset - 1.3.6.1.4.1.318.1.1.26.4.3.1.10
- indexes:
- - labelname: rPDU2DeviceStatusIndex
- type: gauge
- - name: rPDU2DeviceStatusCommandPending
- oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.11
- type: gauge
- help: Indicates whether or not the device is processing a pending command -
- 1.3.6.1.4.1.318.1.1.26.4.3.1.11
- indexes:
- - labelname: rPDU2DeviceStatusIndex
- type: gauge
- enum_values:
- 1: commandPending
- 2: noCommandPending
- 3: commandPendingUnknown
- - name: rPDU2DeviceStatusPowerSupplyAlarm
- oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.12
- type: gauge
- help: Indicates a power supply alarm is active when value equals alarm (2) -
- 1.3.6.1.4.1.318.1.1.26.4.3.1.12
- indexes:
- - labelname: rPDU2DeviceStatusIndex
- type: gauge
- enum_values:
- 1: normal
- 2: alarm
- - name: rPDU2DeviceStatusPowerSupply1Status
- oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.13
- type: gauge
- help: Indicates whether or not an alarm is active in Power Supply 1 - 1.3.6.1.4.1.318.1.1.26.4.3.1.13
- indexes:
- - labelname: rPDU2DeviceStatusIndex
- type: gauge
- enum_values:
- 1: normal
- 2: alarm
- 3: notInstalled
- - name: rPDU2DeviceStatusPowerSupply2Status
- oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.14
- type: gauge
- help: Indicates whether or not an alarm is active in Power Supply 2 - 1.3.6.1.4.1.318.1.1.26.4.3.1.14
- indexes:
- - labelname: rPDU2DeviceStatusIndex
- type: gauge
- enum_values:
- 1: normal
- 2: alarm
- 3: notInstalled
- - name: rPDU2DeviceStatusOutletsEnergyStartTime
- oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.15
- type: DisplayString
- help: Indicates the date and time of the last outlets energy meter reset - 1.3.6.1.4.1.318.1.1.26.4.3.1.15
- indexes:
- - labelname: rPDU2DeviceStatusIndex
- type: gauge
- - name: rPDU2DeviceStatusApparentPower
- oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.16
- type: gauge
- help: The apparent power consumption of the Rack PDU load in hundredths of kiloVoltAmps
- (kVA) - 1.3.6.1.4.1.318.1.1.26.4.3.1.16
- indexes:
- - labelname: rPDU2DeviceStatusIndex
- type: gauge
- - name: rPDU2DeviceStatusPowerFactor
- oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.17
- type: gauge
- help: The power factor of the Rack PDU load in hundredths - 1.3.6.1.4.1.318.1.1.26.4.3.1.17
- indexes:
- - labelname: rPDU2DeviceStatusIndex
- type: gauge
- - name: rPDU2DeviceStatusNPSType
- oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.18
- type: gauge
- help: 'The device NPS status: notNPS (1) indicates the Rack PDU is not in an
- NPS group - 1.3.6.1.4.1.318.1.1.26.4.3.1.18'
- indexes:
- - labelname: rPDU2DeviceStatusIndex
- type: gauge
- enum_values:
- 1: notNPS
- 2: host
- 3: guest
- - name: rPDU2PhaseStatusIndex
- oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.1
- type: gauge
- help: The index to the Rack PDU phase status table entry - 1.3.6.1.4.1.318.1.1.26.6.3.1.1
- indexes:
- - labelname: rPDU2PhaseStatusIndex
- type: gauge
- - name: rPDU2PhaseStatusModule
- oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.2
- type: gauge
- help: The user-defined Rack PDU numeric ID - 1.3.6.1.4.1.318.1.1.26.6.3.1.2
- indexes:
- - labelname: rPDU2PhaseStatusIndex
- type: gauge
- - name: rPDU2PhaseStatusNumber
- oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.3
- type: gauge
- help: The numeric phase ID - 1.3.6.1.4.1.318.1.1.26.6.3.1.3
- indexes:
- - labelname: rPDU2PhaseStatusIndex
- type: gauge
- - name: rPDU2PhaseStatusLoadState
- oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.4
- type: gauge
- help: Indicates the present load status of the Rack PDU phase being queried
- - 1.3.6.1.4.1.318.1.1.26.6.3.1.4
- indexes:
- - labelname: rPDU2PhaseStatusIndex
- type: gauge
- enum_values:
- 1: lowLoad
- 2: normal
- 3: nearOverload
- 4: overload
- - name: rPDU2PhaseStatusCurrent
- oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.5
- type: gauge
- help: Indicates the current draw, in tenths of Amps, of the load on the Rack
- PDU phase being queried - 1.3.6.1.4.1.318.1.1.26.6.3.1.5
- indexes:
- - labelname: rPDU2PhaseStatusIndex
- type: gauge
- - name: rPDU2PhaseStatusVoltage
- oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.6
- type: gauge
- help: Indicates the Voltage, in Volts, of the Rack PDU phase being queried -
- 1.3.6.1.4.1.318.1.1.26.6.3.1.6
- indexes:
- - labelname: rPDU2PhaseStatusIndex
- type: gauge
- - name: rPDU2PhaseStatusPower
- oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.7
- type: gauge
- help: Indicates the load power, in hundredths of kilowatts (kW), consumed on
- the Rack PDU phase being queried - 1.3.6.1.4.1.318.1.1.26.6.3.1.7
- indexes:
- - labelname: rPDU2PhaseStatusIndex
- type: gauge
- - name: rPDU2PhaseStatusApparentPower
- oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.8
- type: gauge
- help: Indicates the load apparent power, in hundredths of kiloVoltAmps (kVA),
- consumed on the Rack PDU phase being queried - 1.3.6.1.4.1.318.1.1.26.6.3.1.8
- indexes:
- - labelname: rPDU2PhaseStatusIndex
- type: gauge
- - name: rPDU2PhaseStatusPowerFactor
- oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.9
- type: gauge
- help: Indicates the load power factor, in hundredths, of the Rack PDU phase
- being queried - 1.3.6.1.4.1.318.1.1.26.6.3.1.9
- indexes:
- - labelname: rPDU2PhaseStatusIndex
- type: gauge
- - name: rPDU2PhaseStatusPeakCurrent
- oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.10
- type: gauge
- help: The peak current of the Rack PDU phase load in tenths of Amps - 1.3.6.1.4.1.318.1.1.26.6.3.1.10
- indexes:
- - labelname: rPDU2PhaseStatusIndex
- type: gauge
- - name: rPDU2PhaseStatusPeakCurrentTimestamp
- oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.11
- type: DisplayString
- help: Indicates the date and time that the peak current occurred - 1.3.6.1.4.1.318.1.1.26.6.3.1.11
- indexes:
- - labelname: rPDU2PhaseStatusIndex
- type: gauge
- - name: rPDU2PhaseStatusPeakCurrentStartTime
- oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.12
- type: DisplayString
- help: Indicates the date and time of the last phase peak current reset - 1.3.6.1.4.1.318.1.1.26.6.3.1.12
- indexes:
- - labelname: rPDU2PhaseStatusIndex
- type: gauge
- - name: rPDU2BankStatusIndex
- oid: 1.3.6.1.4.1.318.1.1.26.8.3.1.1
- type: gauge
- help: The index to the Rack PDU bank status table entry - 1.3.6.1.4.1.318.1.1.26.8.3.1.1
- indexes:
- - labelname: rPDU2BankStatusIndex
- type: gauge
- - name: rPDU2BankStatusModule
- oid: 1.3.6.1.4.1.318.1.1.26.8.3.1.2
- type: gauge
- help: The user-defined Rack PDU numeric ID - 1.3.6.1.4.1.318.1.1.26.8.3.1.2
- indexes:
- - labelname: rPDU2BankStatusIndex
- type: gauge
- - name: rPDU2BankStatusNumber
- oid: 1.3.6.1.4.1.318.1.1.26.8.3.1.3
- type: gauge
- help: The numeric bank ID - 1.3.6.1.4.1.318.1.1.26.8.3.1.3
- indexes:
- - labelname: rPDU2BankStatusIndex
- type: gauge
- - name: rPDU2BankStatusLoadState
- oid: 1.3.6.1.4.1.318.1.1.26.8.3.1.4
- type: EnumAsStateSet
- help: Indicates the present load status of the Rack PDU bank being queried -
- 1.3.6.1.4.1.318.1.1.26.8.3.1.4
- indexes:
- - labelname: rPDU2BankStatusIndex
- type: gauge
- enum_values:
- 1: lowLoad
- 2: normal
- 3: nearOverload
- 4: overload
- - name: rPDU2BankStatusCurrent
- oid: 1.3.6.1.4.1.318.1.1.26.8.3.1.5
- type: gauge
- help: Indicates the current draw, in tenths of Amps, of the load on the Rack
- PDU bank being queried - 1.3.6.1.4.1.318.1.1.26.8.3.1.5
- indexes:
- - labelname: rPDU2BankStatusIndex
- type: gauge
- - name: rPDU2BankStatusPeakCurrent
- oid: 1.3.6.1.4.1.318.1.1.26.8.3.1.6
- type: gauge
- help: The peak current of the Rack PDU bank load in tenths of Amps - 1.3.6.1.4.1.318.1.1.26.8.3.1.6
- indexes:
- - labelname: rPDU2BankStatusIndex
- type: gauge
- - name: rPDU2BankStatusPeakCurrentTimestamp
- oid: 1.3.6.1.4.1.318.1.1.26.8.3.1.7
- type: DisplayString
- help: Indicates the date and time the bank peak current occurred - 1.3.6.1.4.1.318.1.1.26.8.3.1.7
- indexes:
- - labelname: rPDU2BankStatusIndex
- type: gauge
- - name: rPDU2BankStatusPeakCurrentStartTime
- oid: 1.3.6.1.4.1.318.1.1.26.8.3.1.8
- type: DisplayString
- help: Indicates the date and time of the last bank peak current reset - 1.3.6.1.4.1.318.1.1.26.8.3.1.8
- indexes:
- - labelname: rPDU2BankStatusIndex
- type: gauge
- if_mib:
- walk:
- - 1.3.6.1.2.1.2
- - 1.3.6.1.2.1.31.1.1
- get:
- - 1.3.6.1.2.1.1.3.0
- metrics:
- - name: sysUpTime
- oid: 1.3.6.1.2.1.1.3
- type: gauge
- help: The time (in hundredths of a second) since the network management portion
- of the system was last re-initialized. - 1.3.6.1.2.1.1.3
- - name: ifNumber
- oid: 1.3.6.1.2.1.2.1
- type: gauge
- help: The number of network interfaces (regardless of their current state) present
- on this system. - 1.3.6.1.2.1.2.1
- - name: ifIndex
- oid: 1.3.6.1.2.1.2.2.1.1
- type: gauge
- help: A unique value, greater than zero, for each interface - 1.3.6.1.2.1.2.2.1.1
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifType
- oid: 1.3.6.1.2.1.2.2.1.3
- type: EnumAsInfo
- help: The type of interface - 1.3.6.1.2.1.2.2.1.3
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- enum_values:
- 1: other
- 2: regular1822
- 3: hdh1822
- 4: ddnX25
- 5: rfc877x25
- 6: ethernetCsmacd
- 7: iso88023Csmacd
- 8: iso88024TokenBus
- 9: iso88025TokenRing
- 10: iso88026Man
- 11: starLan
- 12: proteon10Mbit
- 13: proteon80Mbit
- 14: hyperchannel
- 15: fddi
- 16: lapb
- 17: sdlc
- 18: ds1
- 19: e1
- 20: basicISDN
- 21: primaryISDN
- 22: propPointToPointSerial
- 23: ppp
- 24: softwareLoopback
- 25: eon
- 26: ethernet3Mbit
- 27: nsip
- 28: slip
- 29: ultra
- 30: ds3
- 31: sip
- 32: frameRelay
- 33: rs232
- 34: para
- 35: arcnet
- 36: arcnetPlus
- 37: atm
- 38: miox25
- 39: sonet
- 40: x25ple
- 41: iso88022llc
- 42: localTalk
- 43: smdsDxi
- 44: frameRelayService
- 45: v35
- 46: hssi
- 47: hippi
- 48: modem
- 49: aal5
- 50: sonetPath
- 51: sonetVT
- 52: smdsIcip
- 53: propVirtual
- 54: propMultiplexor
- 55: ieee80212
- 56: fibreChannel
- 57: hippiInterface
- 58: frameRelayInterconnect
- 59: aflane8023
- 60: aflane8025
- 61: cctEmul
- 62: fastEther
- 63: isdn
- 64: v11
- 65: v36
- 66: g703at64k
- 67: g703at2mb
- 68: qllc
- 69: fastEtherFX
- 70: channel
- 71: ieee80211
- 72: ibm370parChan
- 73: escon
- 74: dlsw
- 75: isdns
- 76: isdnu
- 77: lapd
- 78: ipSwitch
- 79: rsrb
- 80: atmLogical
- 81: ds0
- 82: ds0Bundle
- 83: bsc
- 84: async
- 85: cnr
- 86: iso88025Dtr
- 87: eplrs
- 88: arap
- 89: propCnls
- 90: hostPad
- 91: termPad
- 92: frameRelayMPI
- 93: x213
- 94: adsl
- 95: radsl
- 96: sdsl
- 97: vdsl
- 98: iso88025CRFPInt
- 99: myrinet
- 100: voiceEM
- 101: voiceFXO
- 102: voiceFXS
- 103: voiceEncap
- 104: voiceOverIp
- 105: atmDxi
- 106: atmFuni
- 107: atmIma
- 108: pppMultilinkBundle
- 109: ipOverCdlc
- 110: ipOverClaw
- 111: stackToStack
- 112: virtualIpAddress
- 113: mpc
- 114: ipOverAtm
- 115: iso88025Fiber
- 116: tdlc
- 117: gigabitEthernet
- 118: hdlc
- 119: lapf
- 120: v37
- 121: x25mlp
- 122: x25huntGroup
- 123: transpHdlc
- 124: interleave
- 125: fast
- 126: ip
- 127: docsCableMaclayer
- 128: docsCableDownstream
- 129: docsCableUpstream
- 130: a12MppSwitch
- 131: tunnel
- 132: coffee
- 133: ces
- 134: atmSubInterface
- 135: l2vlan
- 136: l3ipvlan
- 137: l3ipxvlan
- 138: digitalPowerline
- 139: mediaMailOverIp
- 140: dtm
- 141: dcn
- 142: ipForward
- 143: msdsl
- 144: ieee1394
- 145: if-gsn
- 146: dvbRccMacLayer
- 147: dvbRccDownstream
- 148: dvbRccUpstream
- 149: atmVirtual
- 150: mplsTunnel
- 151: srp
- 152: voiceOverAtm
- 153: voiceOverFrameRelay
- 154: idsl
- 155: compositeLink
- 156: ss7SigLink
- 157: propWirelessP2P
- 158: frForward
- 159: rfc1483
- 160: usb
- 161: ieee8023adLag
- 162: bgppolicyaccounting
- 163: frf16MfrBundle
- 164: h323Gatekeeper
- 165: h323Proxy
- 166: mpls
- 167: mfSigLink
- 168: hdsl2
- 169: shdsl
- 170: ds1FDL
- 171: pos
- 172: dvbAsiIn
- 173: dvbAsiOut
- 174: plc
- 175: nfas
- 176: tr008
- 177: gr303RDT
- 178: gr303IDT
- 179: isup
- 180: propDocsWirelessMaclayer
- 181: propDocsWirelessDownstream
- 182: propDocsWirelessUpstream
- 183: hiperlan2
- 184: propBWAp2Mp
- 185: sonetOverheadChannel
- 186: digitalWrapperOverheadChannel
- 187: aal2
- 188: radioMAC
- 189: atmRadio
- 190: imt
- 191: mvl
- 192: reachDSL
- 193: frDlciEndPt
- 194: atmVciEndPt
- 195: opticalChannel
- 196: opticalTransport
- 197: propAtm
- 198: voiceOverCable
- 199: infiniband
- 200: teLink
- 201: q2931
- 202: virtualTg
- 203: sipTg
- 204: sipSig
- 205: docsCableUpstreamChannel
- 206: econet
- 207: pon155
- 208: pon622
- 209: bridge
- 210: linegroup
- 211: voiceEMFGD
- 212: voiceFGDEANA
- 213: voiceDID
- 214: mpegTransport
- 215: sixToFour
- 216: gtp
- 217: pdnEtherLoop1
- 218: pdnEtherLoop2
- 219: opticalChannelGroup
- 220: homepna
- 221: gfp
- 222: ciscoISLvlan
- 223: actelisMetaLOOP
- 224: fcipLink
- 225: rpr
- 226: qam
- 227: lmp
- 228: cblVectaStar
- 229: docsCableMCmtsDownstream
- 230: adsl2
- 231: macSecControlledIF
- 232: macSecUncontrolledIF
- 233: aviciOpticalEther
- 234: atmbond
- 235: voiceFGDOS
- 236: mocaVersion1
- 237: ieee80216WMAN
- 238: adsl2plus
- 239: dvbRcsMacLayer
- 240: dvbTdm
- 241: dvbRcsTdma
- 242: x86Laps
- 243: wwanPP
- 244: wwanPP2
- 245: voiceEBS
- 246: ifPwType
- 247: ilan
- 248: pip
- 249: aluELP
- 250: gpon
- 251: vdsl2
- 252: capwapDot11Profile
- 253: capwapDot11Bss
- 254: capwapWtpVirtualRadio
- 255: bits
- 256: docsCableUpstreamRfPort
- 257: cableDownstreamRfPort
- 258: vmwareVirtualNic
- 259: ieee802154
- 260: otnOdu
- 261: otnOtu
- 262: ifVfiType
- 263: g9981
- 264: g9982
- 265: g9983
- 266: aluEpon
- 267: aluEponOnu
- 268: aluEponPhysicalUni
- 269: aluEponLogicalLink
- 270: aluGponOnu
- 271: aluGponPhysicalUni
- 272: vmwareNicTeam
- 277: docsOfdmDownstream
- 278: docsOfdmaUpstream
- 279: gfast
- 280: sdci
- 281: xboxWireless
- 282: fastdsl
- 283: docsCableScte55d1FwdOob
- 284: docsCableScte55d1RetOob
- 285: docsCableScte55d2DsOob
- 286: docsCableScte55d2UsOob
- 287: docsCableNdf
- 288: docsCableNdr
- 289: ptm
- 290: ghn
- 291: otnOtsi
- 292: otnOtuc
- 293: otnOduc
- 294: otnOtsig
- 295: microwaveCarrierTermination
- 296: microwaveRadioLinkTerminal
- 297: ieee8021axDrni
- 298: ax25
- 299: ieee19061nanocom
- 300: cpri
- 301: omni
- 302: roe
- 303: p2pOverLan
- - name: ifMtu
- oid: 1.3.6.1.2.1.2.2.1.4
- type: gauge
- help: The size of the largest packet which can be sent/received on the interface,
- specified in octets - 1.3.6.1.2.1.2.2.1.4
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifSpeed
- oid: 1.3.6.1.2.1.2.2.1.5
- type: gauge
- help: An estimate of the interface's current bandwidth in bits per second -
- 1.3.6.1.2.1.2.2.1.5
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifPhysAddress
- oid: 1.3.6.1.2.1.2.2.1.6
- type: PhysAddress48
- help: The interface's address at its protocol sub-layer - 1.3.6.1.2.1.2.2.1.6
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifAdminStatus
- oid: 1.3.6.1.2.1.2.2.1.7
- type: gauge
- help: The desired state of the interface - 1.3.6.1.2.1.2.2.1.7
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- enum_values:
- 1: up
- 2: down
- 3: testing
- - name: ifOperStatus
- oid: 1.3.6.1.2.1.2.2.1.8
- type: gauge
- help: The current operational state of the interface - 1.3.6.1.2.1.2.2.1.8
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- enum_values:
- 1: up
- 2: down
- 3: testing
- 4: unknown
- 5: dormant
- 6: notPresent
- 7: lowerLayerDown
- - name: ifLastChange
- oid: 1.3.6.1.2.1.2.2.1.9
- type: gauge
- help: The value of sysUpTime at the time the interface entered its current operational
- state - 1.3.6.1.2.1.2.2.1.9
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifInOctets
- oid: 1.3.6.1.2.1.2.2.1.10
- type: counter
- help: The total number of octets received on the interface, including framing
- characters - 1.3.6.1.2.1.2.2.1.10
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifInUcastPkts
- oid: 1.3.6.1.2.1.2.2.1.11
- type: counter
- help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
- which were not addressed to a multicast or broadcast address at this sub-layer
- - 1.3.6.1.2.1.2.2.1.11
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifInNUcastPkts
- oid: 1.3.6.1.2.1.2.2.1.12
- type: counter
- help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
- which were addressed to a multicast or broadcast address at this sub-layer
- - 1.3.6.1.2.1.2.2.1.12
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifInDiscards
- oid: 1.3.6.1.2.1.2.2.1.13
- type: counter
- help: The number of inbound packets which were chosen to be discarded even though
- no errors had been detected to prevent their being deliverable to a higher-layer
- protocol - 1.3.6.1.2.1.2.2.1.13
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifInErrors
- oid: 1.3.6.1.2.1.2.2.1.14
- type: counter
- help: For packet-oriented interfaces, the number of inbound packets that contained
- errors preventing them from being deliverable to a higher-layer protocol -
- 1.3.6.1.2.1.2.2.1.14
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifInUnknownProtos
- oid: 1.3.6.1.2.1.2.2.1.15
- type: counter
- help: For packet-oriented interfaces, the number of packets received via the
- interface which were discarded because of an unknown or unsupported protocol
- - 1.3.6.1.2.1.2.2.1.15
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifOutOctets
- oid: 1.3.6.1.2.1.2.2.1.16
- type: counter
- help: The total number of octets transmitted out of the interface, including
- framing characters - 1.3.6.1.2.1.2.2.1.16
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifOutUcastPkts
- oid: 1.3.6.1.2.1.2.2.1.17
- type: counter
- help: The total number of packets that higher-level protocols requested be transmitted,
- and which were not addressed to a multicast or broadcast address at this sub-layer,
- including those that were discarded or not sent - 1.3.6.1.2.1.2.2.1.17
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifOutNUcastPkts
- oid: 1.3.6.1.2.1.2.2.1.18
- type: counter
- help: The total number of packets that higher-level protocols requested be transmitted,
- and which were addressed to a multicast or broadcast address at this sub-layer,
- including those that were discarded or not sent - 1.3.6.1.2.1.2.2.1.18
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifOutDiscards
- oid: 1.3.6.1.2.1.2.2.1.19
- type: counter
- help: The number of outbound packets which were chosen to be discarded even
- though no errors had been detected to prevent their being transmitted - 1.3.6.1.2.1.2.2.1.19
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifOutErrors
- oid: 1.3.6.1.2.1.2.2.1.20
- type: counter
- help: For packet-oriented interfaces, the number of outbound packets that could
- not be transmitted because of errors - 1.3.6.1.2.1.2.2.1.20
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifOutQLen
- oid: 1.3.6.1.2.1.2.2.1.21
- type: gauge
- help: The length of the output packet queue (in packets). - 1.3.6.1.2.1.2.2.1.21
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifSpecific
- oid: 1.3.6.1.2.1.2.2.1.22
- type: OctetString
- help: A reference to MIB definitions specific to the particular media being
- used to realize the interface - 1.3.6.1.2.1.2.2.1.22
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifInMulticastPkts
- oid: 1.3.6.1.2.1.31.1.1.1.2
- type: counter
- help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
- which were addressed to a multicast address at this sub-layer - 1.3.6.1.2.1.31.1.1.1.2
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifInBroadcastPkts
- oid: 1.3.6.1.2.1.31.1.1.1.3
- type: counter
- help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
- which were addressed to a broadcast address at this sub-layer - 1.3.6.1.2.1.31.1.1.1.3
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifOutMulticastPkts
- oid: 1.3.6.1.2.1.31.1.1.1.4
- type: counter
- help: The total number of packets that higher-level protocols requested be transmitted,
- and which were addressed to a multicast address at this sub-layer, including
- those that were discarded or not sent - 1.3.6.1.2.1.31.1.1.1.4
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifOutBroadcastPkts
- oid: 1.3.6.1.2.1.31.1.1.1.5
- type: counter
- help: The total number of packets that higher-level protocols requested be transmitted,
- and which were addressed to a broadcast address at this sub-layer, including
- those that were discarded or not sent - 1.3.6.1.2.1.31.1.1.1.5
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifHCInOctets
- oid: 1.3.6.1.2.1.31.1.1.1.6
- type: counter
- help: The total number of octets received on the interface, including framing
- characters - 1.3.6.1.2.1.31.1.1.1.6
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifHCInUcastPkts
- oid: 1.3.6.1.2.1.31.1.1.1.7
- type: counter
- help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
- which were not addressed to a multicast or broadcast address at this sub-layer
- - 1.3.6.1.2.1.31.1.1.1.7
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifHCInMulticastPkts
- oid: 1.3.6.1.2.1.31.1.1.1.8
- type: counter
- help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
- which were addressed to a multicast address at this sub-layer - 1.3.6.1.2.1.31.1.1.1.8
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifHCInBroadcastPkts
- oid: 1.3.6.1.2.1.31.1.1.1.9
- type: counter
- help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
- which were addressed to a broadcast address at this sub-layer - 1.3.6.1.2.1.31.1.1.1.9
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifHCOutOctets
- oid: 1.3.6.1.2.1.31.1.1.1.10
- type: counter
- help: The total number of octets transmitted out of the interface, including
- framing characters - 1.3.6.1.2.1.31.1.1.1.10
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifHCOutUcastPkts
- oid: 1.3.6.1.2.1.31.1.1.1.11
- type: counter
- help: The total number of packets that higher-level protocols requested be transmitted,
- and which were not addressed to a multicast or broadcast address at this sub-layer,
- including those that were discarded or not sent - 1.3.6.1.2.1.31.1.1.1.11
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifHCOutMulticastPkts
- oid: 1.3.6.1.2.1.31.1.1.1.12
- type: counter
- help: The total number of packets that higher-level protocols requested be transmitted,
- and which were addressed to a multicast address at this sub-layer, including
- those that were discarded or not sent - 1.3.6.1.2.1.31.1.1.1.12
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifHCOutBroadcastPkts
- oid: 1.3.6.1.2.1.31.1.1.1.13
- type: counter
- help: The total number of packets that higher-level protocols requested be transmitted,
- and which were addressed to a broadcast address at this sub-layer, including
- those that were discarded or not sent - 1.3.6.1.2.1.31.1.1.1.13
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifLinkUpDownTrapEnable
- oid: 1.3.6.1.2.1.31.1.1.1.14
- type: gauge
- help: Indicates whether linkUp/linkDown traps should be generated for this interface
- - 1.3.6.1.2.1.31.1.1.1.14
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- enum_values:
- 1: enabled
- 2: disabled
- - name: ifHighSpeed
- oid: 1.3.6.1.2.1.31.1.1.1.15
- type: gauge
- help: An estimate of the interface's current bandwidth in units of 1,000,000
- bits per second - 1.3.6.1.2.1.31.1.1.1.15
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- - name: ifPromiscuousMode
- oid: 1.3.6.1.2.1.31.1.1.1.16
- type: gauge
- help: This object has a value of false(2) if this interface only accepts packets/frames
- that are addressed to this station - 1.3.6.1.2.1.31.1.1.1.16
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- enum_values:
- 1: "true"
- 2: "false"
- - name: ifConnectorPresent
- oid: 1.3.6.1.2.1.31.1.1.1.17
- type: gauge
- help: This object has the value 'true(1)' if the interface sublayer has a physical
- connector and the value 'false(2)' otherwise. - 1.3.6.1.2.1.31.1.1.1.17
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- enum_values:
- 1: "true"
- 2: "false"
- - name: ifCounterDiscontinuityTime
- oid: 1.3.6.1.2.1.31.1.1.1.19
- type: gauge
- help: The value of sysUpTime on the most recent occasion at which any one or
- more of this interface's counters suffered a discontinuity - 1.3.6.1.2.1.31.1.1.1.19
- indexes:
- - labelname: ifIndex
- type: gauge
- lookups:
- - labels:
- - ifIndex
- labelname: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- - labels:
- - ifIndex
- labelname: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- ip_mib:
- walk:
- - 1.3.6.1.2.1.4.28
- metrics:
- - name: ipv4InterfaceIfIndex
- oid: 1.3.6.1.2.1.4.28.1.1
- type: gauge
- help: The index value that uniquely identifies the interface to which this entry
- is applicable - 1.3.6.1.2.1.4.28.1.1
- indexes:
- - labelname: ipv4InterfaceIfIndex
- type: gauge
- - name: ipv4InterfaceReasmMaxSize
- oid: 1.3.6.1.2.1.4.28.1.2
- type: gauge
- help: The size of the largest IPv4 datagram that this entity can re-assemble
- from incoming IPv4 fragmented datagrams received on this interface. - 1.3.6.1.2.1.4.28.1.2
- indexes:
- - labelname: ipv4InterfaceIfIndex
- type: gauge
- - name: ipv4InterfaceEnableStatus
- oid: 1.3.6.1.2.1.4.28.1.3
- type: gauge
- help: The indication of whether IPv4 is enabled (up) or disabled (down) on this
- interface - 1.3.6.1.2.1.4.28.1.3
- indexes:
- - labelname: ipv4InterfaceIfIndex
- type: gauge
- enum_values:
- 1: up
- 2: down
- - name: ipv4InterfaceRetransmitTime
- oid: 1.3.6.1.2.1.4.28.1.4
- type: gauge
- help: The time between retransmissions of ARP requests to a neighbor when resolving
- the address or when probing the reachability of a neighbor. - 1.3.6.1.2.1.4.28.1.4
- indexes:
- - labelname: ipv4InterfaceIfIndex
- type: gauge
- synology:
- walk:
- - 1.3.6.1.2.1.2
- - 1.3.6.1.2.1.25.2
- - 1.3.6.1.2.1.31.1.1
- - 1.3.6.1.4.1.2021.10.1.2
- - 1.3.6.1.4.1.2021.10.1.5
- - 1.3.6.1.4.1.2021.4
- - 1.3.6.1.4.1.6574.1
- - 1.3.6.1.4.1.6574.101
- - 1.3.6.1.4.1.6574.102
- - 1.3.6.1.4.1.6574.104
- - 1.3.6.1.4.1.6574.2
- - 1.3.6.1.4.1.6574.3
- - 1.3.6.1.4.1.6574.4
- - 1.3.6.1.4.1.6574.5
- - 1.3.6.1.4.1.6574.6
- get:
- - 1.3.6.1.4.1.2021.11.10.0
- - 1.3.6.1.4.1.2021.11.11.0
- - 1.3.6.1.4.1.2021.11.9.0
- metrics:
- - name: ifNumber
- oid: 1.3.6.1.2.1.2.1
- type: gauge
- help: The number of network interfaces (regardless of their current state) present
- on this system. - 1.3.6.1.2.1.2.1
- - name: ifIndex
- oid: 1.3.6.1.2.1.2.2.1.1
- type: gauge
- help: A unique value, greater than zero, for each interface - 1.3.6.1.2.1.2.2.1.1
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifDescr
- oid: 1.3.6.1.2.1.2.2.1.2
- type: DisplayString
- help: A textual string containing information about the interface - 1.3.6.1.2.1.2.2.1.2
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifType
- oid: 1.3.6.1.2.1.2.2.1.3
- type: gauge
- help: The type of interface - 1.3.6.1.2.1.2.2.1.3
- indexes:
- - labelname: ifIndex
- type: gauge
- enum_values:
- 1: other
- 2: regular1822
- 3: hdh1822
- 4: ddnX25
- 5: rfc877x25
- 6: ethernetCsmacd
- 7: iso88023Csmacd
- 8: iso88024TokenBus
- 9: iso88025TokenRing
- 10: iso88026Man
- 11: starLan
- 12: proteon10Mbit
- 13: proteon80Mbit
- 14: hyperchannel
- 15: fddi
- 16: lapb
- 17: sdlc
- 18: ds1
- 19: e1
- 20: basicISDN
- 21: primaryISDN
- 22: propPointToPointSerial
- 23: ppp
- 24: softwareLoopback
- 25: eon
- 26: ethernet3Mbit
- 27: nsip
- 28: slip
- 29: ultra
- 30: ds3
- 31: sip
- 32: frameRelay
- 33: rs232
- 34: para
- 35: arcnet
- 36: arcnetPlus
- 37: atm
- 38: miox25
- 39: sonet
- 40: x25ple
- 41: iso88022llc
- 42: localTalk
- 43: smdsDxi
- 44: frameRelayService
- 45: v35
- 46: hssi
- 47: hippi
- 48: modem
- 49: aal5
- 50: sonetPath
- 51: sonetVT
- 52: smdsIcip
- 53: propVirtual
- 54: propMultiplexor
- 55: ieee80212
- 56: fibreChannel
- 57: hippiInterface
- 58: frameRelayInterconnect
- 59: aflane8023
- 60: aflane8025
- 61: cctEmul
- 62: fastEther
- 63: isdn
- 64: v11
- 65: v36
- 66: g703at64k
- 67: g703at2mb
- 68: qllc
- 69: fastEtherFX
- 70: channel
- 71: ieee80211
- 72: ibm370parChan
- 73: escon
- 74: dlsw
- 75: isdns
- 76: isdnu
- 77: lapd
- 78: ipSwitch
- 79: rsrb
- 80: atmLogical
- 81: ds0
- 82: ds0Bundle
- 83: bsc
- 84: async
- 85: cnr
- 86: iso88025Dtr
- 87: eplrs
- 88: arap
- 89: propCnls
- 90: hostPad
- 91: termPad
- 92: frameRelayMPI
- 93: x213
- 94: adsl
- 95: radsl
- 96: sdsl
- 97: vdsl
- 98: iso88025CRFPInt
- 99: myrinet
- 100: voiceEM
- 101: voiceFXO
- 102: voiceFXS
- 103: voiceEncap
- 104: voiceOverIp
- 105: atmDxi
- 106: atmFuni
- 107: atmIma
- 108: pppMultilinkBundle
- 109: ipOverCdlc
- 110: ipOverClaw
- 111: stackToStack
- 112: virtualIpAddress
- 113: mpc
- 114: ipOverAtm
- 115: iso88025Fiber
- 116: tdlc
- 117: gigabitEthernet
- 118: hdlc
- 119: lapf
- 120: v37
- 121: x25mlp
- 122: x25huntGroup
- 123: transpHdlc
- 124: interleave
- 125: fast
- 126: ip
- 127: docsCableMaclayer
- 128: docsCableDownstream
- 129: docsCableUpstream
- 130: a12MppSwitch
- 131: tunnel
- 132: coffee
- 133: ces
- 134: atmSubInterface
- 135: l2vlan
- 136: l3ipvlan
- 137: l3ipxvlan
- 138: digitalPowerline
- 139: mediaMailOverIp
- 140: dtm
- 141: dcn
- 142: ipForward
- 143: msdsl
- 144: ieee1394
- 145: if-gsn
- 146: dvbRccMacLayer
- 147: dvbRccDownstream
- 148: dvbRccUpstream
- 149: atmVirtual
- 150: mplsTunnel
- 151: srp
- 152: voiceOverAtm
- 153: voiceOverFrameRelay
- 154: idsl
- 155: compositeLink
- 156: ss7SigLink
- 157: propWirelessP2P
- 158: frForward
- 159: rfc1483
- 160: usb
- 161: ieee8023adLag
- 162: bgppolicyaccounting
- 163: frf16MfrBundle
- 164: h323Gatekeeper
- 165: h323Proxy
- 166: mpls
- 167: mfSigLink
- 168: hdsl2
- 169: shdsl
- 170: ds1FDL
- 171: pos
- 172: dvbAsiIn
- 173: dvbAsiOut
- 174: plc
- 175: nfas
- 176: tr008
- 177: gr303RDT
- 178: gr303IDT
- 179: isup
- 180: propDocsWirelessMaclayer
- 181: propDocsWirelessDownstream
- 182: propDocsWirelessUpstream
- 183: hiperlan2
- 184: propBWAp2Mp
- 185: sonetOverheadChannel
- 186: digitalWrapperOverheadChannel
- 187: aal2
- 188: radioMAC
- 189: atmRadio
- 190: imt
- 191: mvl
- 192: reachDSL
- 193: frDlciEndPt
- 194: atmVciEndPt
- 195: opticalChannel
- 196: opticalTransport
- 197: propAtm
- 198: voiceOverCable
- 199: infiniband
- 200: teLink
- 201: q2931
- 202: virtualTg
- 203: sipTg
- 204: sipSig
- 205: docsCableUpstreamChannel
- 206: econet
- 207: pon155
- 208: pon622
- 209: bridge
- 210: linegroup
- 211: voiceEMFGD
- 212: voiceFGDEANA
- 213: voiceDID
- 214: mpegTransport
- 215: sixToFour
- 216: gtp
- 217: pdnEtherLoop1
- 218: pdnEtherLoop2
- 219: opticalChannelGroup
- 220: homepna
- 221: gfp
- 222: ciscoISLvlan
- 223: actelisMetaLOOP
- 224: fcipLink
- 225: rpr
- 226: qam
- 227: lmp
- 228: cblVectaStar
- 229: docsCableMCmtsDownstream
- 230: adsl2
- 231: macSecControlledIF
- 232: macSecUncontrolledIF
- 233: aviciOpticalEther
- 234: atmbond
- 235: voiceFGDOS
- 236: mocaVersion1
- 237: ieee80216WMAN
- 238: adsl2plus
- 239: dvbRcsMacLayer
- 240: dvbTdm
- 241: dvbRcsTdma
- 242: x86Laps
- 243: wwanPP
- 244: wwanPP2
- 245: voiceEBS
- 246: ifPwType
- 247: ilan
- 248: pip
- 249: aluELP
- 250: gpon
- 251: vdsl2
- 252: capwapDot11Profile
- 253: capwapDot11Bss
- 254: capwapWtpVirtualRadio
- 255: bits
- 256: docsCableUpstreamRfPort
- 257: cableDownstreamRfPort
- 258: vmwareVirtualNic
- 259: ieee802154
- 260: otnOdu
- 261: otnOtu
- 262: ifVfiType
- 263: g9981
- 264: g9982
- 265: g9983
- 266: aluEpon
- 267: aluEponOnu
- 268: aluEponPhysicalUni
- 269: aluEponLogicalLink
- 270: aluGponOnu
- 271: aluGponPhysicalUni
- 272: vmwareNicTeam
- 277: docsOfdmDownstream
- 278: docsOfdmaUpstream
- 279: gfast
- 280: sdci
- 281: xboxWireless
- 282: fastdsl
- 283: docsCableScte55d1FwdOob
- 284: docsCableScte55d1RetOob
- 285: docsCableScte55d2DsOob
- 286: docsCableScte55d2UsOob
- 287: docsCableNdf
- 288: docsCableNdr
- 289: ptm
- 290: ghn
- 291: otnOtsi
- 292: otnOtuc
- 293: otnOduc
- 294: otnOtsig
- 295: microwaveCarrierTermination
- 296: microwaveRadioLinkTerminal
- 297: ieee8021axDrni
- 298: ax25
- 299: ieee19061nanocom
- 300: cpri
- 301: omni
- 302: roe
- 303: p2pOverLan
- - name: ifMtu
- oid: 1.3.6.1.2.1.2.2.1.4
- type: gauge
- help: The size of the largest packet which can be sent/received on the interface,
- specified in octets - 1.3.6.1.2.1.2.2.1.4
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifSpeed
- oid: 1.3.6.1.2.1.2.2.1.5
- type: gauge
- help: An estimate of the interface's current bandwidth in bits per second -
- 1.3.6.1.2.1.2.2.1.5
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifPhysAddress
- oid: 1.3.6.1.2.1.2.2.1.6
- type: PhysAddress48
- help: The interface's address at its protocol sub-layer - 1.3.6.1.2.1.2.2.1.6
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifAdminStatus
- oid: 1.3.6.1.2.1.2.2.1.7
- type: gauge
- help: The desired state of the interface - 1.3.6.1.2.1.2.2.1.7
- indexes:
- - labelname: ifIndex
- type: gauge
- enum_values:
- 1: up
- 2: down
- 3: testing
- - name: ifOperStatus
- oid: 1.3.6.1.2.1.2.2.1.8
- type: gauge
- help: The current operational state of the interface - 1.3.6.1.2.1.2.2.1.8
- indexes:
- - labelname: ifIndex
- type: gauge
- enum_values:
- 1: up
- 2: down
- 3: testing
- 4: unknown
- 5: dormant
- 6: notPresent
- 7: lowerLayerDown
- - name: ifLastChange
- oid: 1.3.6.1.2.1.2.2.1.9
- type: gauge
- help: The value of sysUpTime at the time the interface entered its current operational
- state - 1.3.6.1.2.1.2.2.1.9
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifInOctets
- oid: 1.3.6.1.2.1.2.2.1.10
- type: counter
- help: The total number of octets received on the interface, including framing
- characters - 1.3.6.1.2.1.2.2.1.10
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifInUcastPkts
- oid: 1.3.6.1.2.1.2.2.1.11
- type: counter
- help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
- which were not addressed to a multicast or broadcast address at this sub-layer
- - 1.3.6.1.2.1.2.2.1.11
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifInNUcastPkts
- oid: 1.3.6.1.2.1.2.2.1.12
- type: counter
- help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
- which were addressed to a multicast or broadcast address at this sub-layer
- - 1.3.6.1.2.1.2.2.1.12
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifInDiscards
- oid: 1.3.6.1.2.1.2.2.1.13
- type: counter
- help: The number of inbound packets which were chosen to be discarded even though
- no errors had been detected to prevent their being deliverable to a higher-layer
- protocol - 1.3.6.1.2.1.2.2.1.13
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifInErrors
- oid: 1.3.6.1.2.1.2.2.1.14
- type: counter
- help: For packet-oriented interfaces, the number of inbound packets that contained
- errors preventing them from being deliverable to a higher-layer protocol -
- 1.3.6.1.2.1.2.2.1.14
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifInUnknownProtos
- oid: 1.3.6.1.2.1.2.2.1.15
- type: counter
- help: For packet-oriented interfaces, the number of packets received via the
- interface which were discarded because of an unknown or unsupported protocol
- - 1.3.6.1.2.1.2.2.1.15
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifOutOctets
- oid: 1.3.6.1.2.1.2.2.1.16
- type: counter
- help: The total number of octets transmitted out of the interface, including
- framing characters - 1.3.6.1.2.1.2.2.1.16
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifOutUcastPkts
- oid: 1.3.6.1.2.1.2.2.1.17
- type: counter
- help: The total number of packets that higher-level protocols requested be transmitted,
- and which were not addressed to a multicast or broadcast address at this sub-layer,
- including those that were discarded or not sent - 1.3.6.1.2.1.2.2.1.17
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifOutNUcastPkts
- oid: 1.3.6.1.2.1.2.2.1.18
- type: counter
- help: The total number of packets that higher-level protocols requested be transmitted,
- and which were addressed to a multicast or broadcast address at this sub-layer,
- including those that were discarded or not sent - 1.3.6.1.2.1.2.2.1.18
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifOutDiscards
- oid: 1.3.6.1.2.1.2.2.1.19
- type: counter
- help: The number of outbound packets which were chosen to be discarded even
- though no errors had been detected to prevent their being transmitted - 1.3.6.1.2.1.2.2.1.19
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifOutErrors
- oid: 1.3.6.1.2.1.2.2.1.20
- type: counter
- help: For packet-oriented interfaces, the number of outbound packets that could
- not be transmitted because of errors - 1.3.6.1.2.1.2.2.1.20
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifOutQLen
- oid: 1.3.6.1.2.1.2.2.1.21
- type: gauge
- help: The length of the output packet queue (in packets). - 1.3.6.1.2.1.2.2.1.21
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifSpecific
- oid: 1.3.6.1.2.1.2.2.1.22
- type: OctetString
- help: A reference to MIB definitions specific to the particular media being
- used to realize the interface - 1.3.6.1.2.1.2.2.1.22
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: hrMemorySize
- oid: 1.3.6.1.2.1.25.2.2
- type: gauge
- help: The amount of physical read-write main memory, typically RAM, contained
- by the host. - 1.3.6.1.2.1.25.2.2
- - name: hrStorageIndex
- oid: 1.3.6.1.2.1.25.2.3.1.1
- type: gauge
- help: A unique value for each logical storage area contained by the host. -
- 1.3.6.1.2.1.25.2.3.1.1
- indexes:
- - labelname: hrStorageIndex
- type: gauge
- lookups:
- - labels:
- - hrStorageIndex
- labelname: hrStorageDescr
- oid: 1.3.6.1.2.1.25.2.3.1.3
- type: DisplayString
- - labels: []
- labelname: hrStorageIndex
- - name: hrStorageType
- oid: 1.3.6.1.2.1.25.2.3.1.2
- type: OctetString
- help: The type of storage represented by this entry. - 1.3.6.1.2.1.25.2.3.1.2
- indexes:
- - labelname: hrStorageIndex
- type: gauge
- lookups:
- - labels:
- - hrStorageIndex
- labelname: hrStorageDescr
- oid: 1.3.6.1.2.1.25.2.3.1.3
- type: DisplayString
- - labels: []
- labelname: hrStorageIndex
- - name: hrStorageDescr
- oid: 1.3.6.1.2.1.25.2.3.1.3
- type: DisplayString
- help: A description of the type and instance of the storage described by this
- entry. - 1.3.6.1.2.1.25.2.3.1.3
- indexes:
- - labelname: hrStorageIndex
- type: gauge
- lookups:
- - labels:
- - hrStorageIndex
- labelname: hrStorageDescr
- oid: 1.3.6.1.2.1.25.2.3.1.3
- type: DisplayString
- - labels: []
- labelname: hrStorageIndex
- - name: hrStorageAllocationUnits
- oid: 1.3.6.1.2.1.25.2.3.1.4
- type: gauge
- help: The size, in bytes, of the data objects allocated from this pool - 1.3.6.1.2.1.25.2.3.1.4
- indexes:
- - labelname: hrStorageIndex
- type: gauge
- lookups:
- - labels:
- - hrStorageIndex
- labelname: hrStorageDescr
- oid: 1.3.6.1.2.1.25.2.3.1.3
- type: DisplayString
- - labels: []
- labelname: hrStorageIndex
- - name: hrStorageSize
- oid: 1.3.6.1.2.1.25.2.3.1.5
- type: gauge
- help: The size of the storage represented by this entry, in units of hrStorageAllocationUnits
- - 1.3.6.1.2.1.25.2.3.1.5
- indexes:
- - labelname: hrStorageIndex
- type: gauge
- lookups:
- - labels:
- - hrStorageIndex
- labelname: hrStorageDescr
- oid: 1.3.6.1.2.1.25.2.3.1.3
- type: DisplayString
- - labels: []
- labelname: hrStorageIndex
- - name: hrStorageUsed
- oid: 1.3.6.1.2.1.25.2.3.1.6
- type: gauge
- help: The amount of the storage represented by this entry that is allocated,
- in units of hrStorageAllocationUnits. - 1.3.6.1.2.1.25.2.3.1.6
- indexes:
- - labelname: hrStorageIndex
- type: gauge
- lookups:
- - labels:
- - hrStorageIndex
- labelname: hrStorageDescr
- oid: 1.3.6.1.2.1.25.2.3.1.3
- type: DisplayString
- - labels: []
- labelname: hrStorageIndex
- - name: hrStorageAllocationFailures
- oid: 1.3.6.1.2.1.25.2.3.1.7
- type: counter
- help: The number of requests for storage represented by this entry that could
- not be honored due to not enough storage - 1.3.6.1.2.1.25.2.3.1.7
- indexes:
- - labelname: hrStorageIndex
- type: gauge
- lookups:
- - labels:
- - hrStorageIndex
- labelname: hrStorageDescr
- oid: 1.3.6.1.2.1.25.2.3.1.3
- type: DisplayString
- - labels: []
- labelname: hrStorageIndex
- - name: ifName
- oid: 1.3.6.1.2.1.31.1.1.1.1
- type: DisplayString
- help: The textual name of the interface - 1.3.6.1.2.1.31.1.1.1.1
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifInMulticastPkts
- oid: 1.3.6.1.2.1.31.1.1.1.2
- type: counter
- help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
- which were addressed to a multicast address at this sub-layer - 1.3.6.1.2.1.31.1.1.1.2
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifInBroadcastPkts
- oid: 1.3.6.1.2.1.31.1.1.1.3
- type: counter
- help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
- which were addressed to a broadcast address at this sub-layer - 1.3.6.1.2.1.31.1.1.1.3
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifOutMulticastPkts
- oid: 1.3.6.1.2.1.31.1.1.1.4
- type: counter
- help: The total number of packets that higher-level protocols requested be transmitted,
- and which were addressed to a multicast address at this sub-layer, including
- those that were discarded or not sent - 1.3.6.1.2.1.31.1.1.1.4
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifOutBroadcastPkts
- oid: 1.3.6.1.2.1.31.1.1.1.5
- type: counter
- help: The total number of packets that higher-level protocols requested be transmitted,
- and which were addressed to a broadcast address at this sub-layer, including
- those that were discarded or not sent - 1.3.6.1.2.1.31.1.1.1.5
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifHCInOctets
- oid: 1.3.6.1.2.1.31.1.1.1.6
- type: counter
- help: The total number of octets received on the interface, including framing
- characters - 1.3.6.1.2.1.31.1.1.1.6
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifHCInUcastPkts
- oid: 1.3.6.1.2.1.31.1.1.1.7
- type: counter
- help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
- which were not addressed to a multicast or broadcast address at this sub-layer
- - 1.3.6.1.2.1.31.1.1.1.7
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifHCInMulticastPkts
- oid: 1.3.6.1.2.1.31.1.1.1.8
- type: counter
- help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
- which were addressed to a multicast address at this sub-layer - 1.3.6.1.2.1.31.1.1.1.8
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifHCInBroadcastPkts
- oid: 1.3.6.1.2.1.31.1.1.1.9
- type: counter
- help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
- which were addressed to a broadcast address at this sub-layer - 1.3.6.1.2.1.31.1.1.1.9
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifHCOutOctets
- oid: 1.3.6.1.2.1.31.1.1.1.10
- type: counter
- help: The total number of octets transmitted out of the interface, including
- framing characters - 1.3.6.1.2.1.31.1.1.1.10
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifHCOutUcastPkts
- oid: 1.3.6.1.2.1.31.1.1.1.11
- type: counter
- help: The total number of packets that higher-level protocols requested be transmitted,
- and which were not addressed to a multicast or broadcast address at this sub-layer,
- including those that were discarded or not sent - 1.3.6.1.2.1.31.1.1.1.11
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifHCOutMulticastPkts
- oid: 1.3.6.1.2.1.31.1.1.1.12
- type: counter
- help: The total number of packets that higher-level protocols requested be transmitted,
- and which were addressed to a multicast address at this sub-layer, including
- those that were discarded or not sent - 1.3.6.1.2.1.31.1.1.1.12
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifHCOutBroadcastPkts
- oid: 1.3.6.1.2.1.31.1.1.1.13
- type: counter
- help: The total number of packets that higher-level protocols requested be transmitted,
- and which were addressed to a broadcast address at this sub-layer, including
- those that were discarded or not sent - 1.3.6.1.2.1.31.1.1.1.13
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifLinkUpDownTrapEnable
- oid: 1.3.6.1.2.1.31.1.1.1.14
- type: gauge
- help: Indicates whether linkUp/linkDown traps should be generated for this interface
- - 1.3.6.1.2.1.31.1.1.1.14
- indexes:
- - labelname: ifIndex
- type: gauge
- enum_values:
- 1: enabled
- 2: disabled
- - name: ifHighSpeed
- oid: 1.3.6.1.2.1.31.1.1.1.15
- type: gauge
- help: An estimate of the interface's current bandwidth in units of 1,000,000
- bits per second - 1.3.6.1.2.1.31.1.1.1.15
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifPromiscuousMode
- oid: 1.3.6.1.2.1.31.1.1.1.16
- type: gauge
- help: This object has a value of false(2) if this interface only accepts packets/frames
- that are addressed to this station - 1.3.6.1.2.1.31.1.1.1.16
- indexes:
- - labelname: ifIndex
- type: gauge
- enum_values:
- 1: "true"
- 2: "false"
- - name: ifConnectorPresent
- oid: 1.3.6.1.2.1.31.1.1.1.17
- type: gauge
- help: This object has the value 'true(1)' if the interface sublayer has a physical
- connector and the value 'false(2)' otherwise. - 1.3.6.1.2.1.31.1.1.1.17
- indexes:
- - labelname: ifIndex
- type: gauge
- enum_values:
- 1: "true"
- 2: "false"
- - name: ifAlias
- oid: 1.3.6.1.2.1.31.1.1.1.18
- type: DisplayString
- help: This object is an 'alias' name for the interface as specified by a network
- manager, and provides a non-volatile 'handle' for the interface - 1.3.6.1.2.1.31.1.1.1.18
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: ifCounterDiscontinuityTime
- oid: 1.3.6.1.2.1.31.1.1.1.19
- type: gauge
- help: The value of sysUpTime on the most recent occasion at which any one or
- more of this interface's counters suffered a discontinuity - 1.3.6.1.2.1.31.1.1.1.19
- indexes:
- - labelname: ifIndex
- type: gauge
- - name: laNames
- oid: 1.3.6.1.4.1.2021.10.1.2
- type: DisplayString
- help: The list of loadave names we're watching. - 1.3.6.1.4.1.2021.10.1.2
- indexes:
- - labelname: laIndex
- type: gauge
- lookups:
- - labels:
- - laIndex
- labelname: laNames
- oid: 1.3.6.1.4.1.2021.10.1.2
- type: DisplayString
- - labels: []
- labelname: laIndex
- - name: laLoadInt
- oid: 1.3.6.1.4.1.2021.10.1.5
- type: gauge
- help: The 1,5 and 15 minute load averages as an integer - 1.3.6.1.4.1.2021.10.1.5
- indexes:
- - labelname: laIndex
- type: gauge
- lookups:
- - labels:
- - laIndex
- labelname: laNames
- oid: 1.3.6.1.4.1.2021.10.1.2
- type: DisplayString
- - labels: []
- labelname: laIndex
- - name: ssCpuSystem
- oid: 1.3.6.1.4.1.2021.11.10
- type: gauge
- help: The percentage of CPU time spent processing system-level code, calculated
- over the last minute - 1.3.6.1.4.1.2021.11.10
- - name: ssCpuIdle
- oid: 1.3.6.1.4.1.2021.11.11
- type: gauge
- help: The percentage of processor time spent idle, calculated over the last
- minute - 1.3.6.1.4.1.2021.11.11
- - name: ssCpuUser
- oid: 1.3.6.1.4.1.2021.11.9
- type: gauge
- help: The percentage of CPU time spent processing user-level code, calculated
- over the last minute - 1.3.6.1.4.1.2021.11.9
- - name: memIndex
- oid: 1.3.6.1.4.1.2021.4.1
- type: gauge
- help: Bogus Index - 1.3.6.1.4.1.2021.4.1
- - name: memErrorName
- oid: 1.3.6.1.4.1.2021.4.2
- type: DisplayString
- help: Bogus Name - 1.3.6.1.4.1.2021.4.2
- - name: memTotalSwap
- oid: 1.3.6.1.4.1.2021.4.3
- type: gauge
- help: The total amount of swap space configured for this host. - 1.3.6.1.4.1.2021.4.3
- - name: memAvailSwap
- oid: 1.3.6.1.4.1.2021.4.4
- type: gauge
- help: The amount of swap space currently unused or available. - 1.3.6.1.4.1.2021.4.4
- - name: memTotalReal
- oid: 1.3.6.1.4.1.2021.4.5
- type: gauge
- help: The total amount of real/physical memory installed on this host. - 1.3.6.1.4.1.2021.4.5
- - name: memAvailReal
- oid: 1.3.6.1.4.1.2021.4.6
- type: gauge
- help: The amount of real/physical memory currently unused or available. - 1.3.6.1.4.1.2021.4.6
- - name: memTotalSwapTXT
- oid: 1.3.6.1.4.1.2021.4.7
- type: gauge
- help: The total amount of swap space or virtual memory allocated for text pages
- on this host - 1.3.6.1.4.1.2021.4.7
- - name: memAvailSwapTXT
- oid: 1.3.6.1.4.1.2021.4.8
- type: gauge
- help: The amount of swap space or virtual memory currently being used by text
- pages on this host - 1.3.6.1.4.1.2021.4.8
- - name: memTotalRealTXT
- oid: 1.3.6.1.4.1.2021.4.9
- type: gauge
- help: The total amount of real/physical memory allocated for text pages on this
- host - 1.3.6.1.4.1.2021.4.9
- - name: memAvailRealTXT
- oid: 1.3.6.1.4.1.2021.4.10
- type: gauge
- help: The amount of real/physical memory currently being used by text pages
- on this host - 1.3.6.1.4.1.2021.4.10
- - name: memTotalFree
- oid: 1.3.6.1.4.1.2021.4.11
- type: gauge
- help: The total amount of memory free or available for use on this host - 1.3.6.1.4.1.2021.4.11
- - name: memMinimumSwap
- oid: 1.3.6.1.4.1.2021.4.12
- type: gauge
- help: The minimum amount of swap space expected to be kept free or available
- during normal operation of this host - 1.3.6.1.4.1.2021.4.12
- - name: memShared
- oid: 1.3.6.1.4.1.2021.4.13
- type: gauge
- help: The total amount of real or virtual memory currently allocated for use
- as shared memory - 1.3.6.1.4.1.2021.4.13
- - name: memBuffer
- oid: 1.3.6.1.4.1.2021.4.14
- type: gauge
- help: The total amount of real or virtual memory currently allocated for use
- as memory buffers - 1.3.6.1.4.1.2021.4.14
- - name: memCached
- oid: 1.3.6.1.4.1.2021.4.15
- type: gauge
- help: The total amount of real or virtual memory currently allocated for use
- as cached memory - 1.3.6.1.4.1.2021.4.15
- - name: memUsedSwapTXT
- oid: 1.3.6.1.4.1.2021.4.16
- type: gauge
- help: The amount of swap space or virtual memory currently being used by text
- pages on this host - 1.3.6.1.4.1.2021.4.16
- - name: memUsedRealTXT
- oid: 1.3.6.1.4.1.2021.4.17
- type: gauge
- help: The amount of real/physical memory currently being used by text pages
- on this host - 1.3.6.1.4.1.2021.4.17
- - name: memTotalSwapX
- oid: 1.3.6.1.4.1.2021.4.18
- type: counter
- help: The total amount of swap space configured for this host. - 1.3.6.1.4.1.2021.4.18
- - name: memAvailSwapX
- oid: 1.3.6.1.4.1.2021.4.19
- type: counter
- help: The amount of swap space currently unused or available. - 1.3.6.1.4.1.2021.4.19
- - name: memTotalRealX
- oid: 1.3.6.1.4.1.2021.4.20
- type: counter
- help: The total amount of real/physical memory installed on this host. - 1.3.6.1.4.1.2021.4.20
- - name: memAvailRealX
- oid: 1.3.6.1.4.1.2021.4.21
- type: counter
- help: The amount of real/physical memory currently unused or available. - 1.3.6.1.4.1.2021.4.21
- - name: memTotalFreeX
- oid: 1.3.6.1.4.1.2021.4.22
- type: counter
- help: The total amount of memory free or available for use on this host - 1.3.6.1.4.1.2021.4.22
- - name: memMinimumSwapX
- oid: 1.3.6.1.4.1.2021.4.23
- type: counter
- help: The minimum amount of swap space expected to be kept free or available
- during normal operation of this host - 1.3.6.1.4.1.2021.4.23
- - name: memSharedX
- oid: 1.3.6.1.4.1.2021.4.24
- type: counter
- help: The total amount of real or virtual memory currently allocated for use
- as shared memory - 1.3.6.1.4.1.2021.4.24
- - name: memBufferX
- oid: 1.3.6.1.4.1.2021.4.25
- type: counter
- help: The total amount of real or virtual memory currently allocated for use
- as memory buffers - 1.3.6.1.4.1.2021.4.25
- - name: memCachedX
- oid: 1.3.6.1.4.1.2021.4.26
- type: counter
- help: The total amount of real or virtual memory currently allocated for use
- as cached memory - 1.3.6.1.4.1.2021.4.26
- - name: memSwapError
- oid: 1.3.6.1.4.1.2021.4.100
- type: gauge
- help: Indicates whether the amount of available swap space (as reported by 'memAvailSwap(4)'),
- is less than the desired minimum (specified by 'memMinimumSwap(12)'). - 1.3.6.1.4.1.2021.4.100
- enum_values:
- 0: noError
- 1: error
- - name: memSwapErrorMsg
- oid: 1.3.6.1.4.1.2021.4.101
- type: DisplayString
- help: Describes whether the amount of available swap space (as reported by 'memAvailSwap(4)'),
- is less than the desired minimum (specified by 'memMinimumSwap(12)'). - 1.3.6.1.4.1.2021.4.101
- - name: systemStatus
- oid: 1.3.6.1.4.1.6574.1.1
- type: gauge
- help: Synology system status Each meanings of status represented describe below
- - 1.3.6.1.4.1.6574.1.1
- - name: temperature
- oid: 1.3.6.1.4.1.6574.1.2
- type: gauge
- help: Synology system temperature The temperature of Disk Station uses Celsius
- degree. - 1.3.6.1.4.1.6574.1.2
- - name: powerStatus
- oid: 1.3.6.1.4.1.6574.1.3
- type: gauge
- help: Synology power status Each meanings of status represented describe below
- - 1.3.6.1.4.1.6574.1.3
- - name: systemFanStatus
- oid: 1.3.6.1.4.1.6574.1.4.1
- type: gauge
- help: Synology system fan status Each meanings of status represented describe
- below - 1.3.6.1.4.1.6574.1.4.1
- - name: cpuFanStatus
- oid: 1.3.6.1.4.1.6574.1.4.2
- type: gauge
- help: Synology cpu fan status Each meanings of status represented describe below
- - 1.3.6.1.4.1.6574.1.4.2
- - name: modelName
- oid: 1.3.6.1.4.1.6574.1.5.1
- type: DisplayString
- help: The Model name of this NAS - 1.3.6.1.4.1.6574.1.5.1
- - name: serialNumber
- oid: 1.3.6.1.4.1.6574.1.5.2
- type: OctetString
- help: The serial number of this NAS - 1.3.6.1.4.1.6574.1.5.2
- - name: version
- oid: 1.3.6.1.4.1.6574.1.5.3
- type: OctetString
- help: The version of this DSM - 1.3.6.1.4.1.6574.1.5.3
- - name: upgradeAvailable
- oid: 1.3.6.1.4.1.6574.1.5.4
- type: gauge
- help: This oid is for checking whether there is a latest DSM can be upgraded
- - 1.3.6.1.4.1.6574.1.5.4
- - name: controllerNumber
- oid: 1.3.6.1.4.1.6574.1.6
- type: gauge
- help: Synology system controller number Controller A(0) Controller B(1) - 1.3.6.1.4.1.6574.1.6
- - name: storageIOIndex
- oid: 1.3.6.1.4.1.6574.101.1.1.1
- type: gauge
- help: Reference index for each observed device. - 1.3.6.1.4.1.6574.101.1.1.1
- indexes:
- - labelname: storageIOIndex
- type: gauge
- lookups:
- - labels:
- - storageIOIndex
- labelname: storageIODevice
- oid: 1.3.6.1.4.1.6574.101.1.1.2
- type: DisplayString
- - labels: []
- labelname: storageIOIndex
- - name: storageIODevice
- oid: 1.3.6.1.4.1.6574.101.1.1.2
- type: DisplayString
- help: The name of the device we are counting/checking. - 1.3.6.1.4.1.6574.101.1.1.2
- indexes:
- - labelname: storageIOIndex
- type: gauge
- lookups:
- - labels:
- - storageIOIndex
- labelname: storageIODevice
- oid: 1.3.6.1.4.1.6574.101.1.1.2
- type: DisplayString
- - labels: []
- labelname: storageIOIndex
- - name: storageIONRead
- oid: 1.3.6.1.4.1.6574.101.1.1.3
- type: counter
- help: The number of bytes read from this device since boot. - 1.3.6.1.4.1.6574.101.1.1.3
- indexes:
- - labelname: storageIOIndex
- type: gauge
- lookups:
- - labels:
- - storageIOIndex
- labelname: storageIODevice
- oid: 1.3.6.1.4.1.6574.101.1.1.2
- type: DisplayString
- - labels: []
- labelname: storageIOIndex
- - name: storageIONWritten
- oid: 1.3.6.1.4.1.6574.101.1.1.4
- type: counter
- help: The number of bytes written to this device since boot. - 1.3.6.1.4.1.6574.101.1.1.4
- indexes:
- - labelname: storageIOIndex
- type: gauge
- lookups:
- - labels:
- - storageIOIndex
- labelname: storageIODevice
- oid: 1.3.6.1.4.1.6574.101.1.1.2
- type: DisplayString
- - labels: []
- labelname: storageIOIndex
- - name: storageIOReads
- oid: 1.3.6.1.4.1.6574.101.1.1.5
- type: counter
- help: The number of read accesses from this device since boot. - 1.3.6.1.4.1.6574.101.1.1.5
- indexes:
- - labelname: storageIOIndex
- type: gauge
- lookups:
- - labels:
- - storageIOIndex
- labelname: storageIODevice
- oid: 1.3.6.1.4.1.6574.101.1.1.2
- type: DisplayString
- - labels: []
- labelname: storageIOIndex
- - name: storageIOWrites
- oid: 1.3.6.1.4.1.6574.101.1.1.6
- type: counter
- help: The number of write accesses to this device since boot. - 1.3.6.1.4.1.6574.101.1.1.6
- indexes:
- - labelname: storageIOIndex
- type: gauge
- lookups:
- - labels:
- - storageIOIndex
- labelname: storageIODevice
- oid: 1.3.6.1.4.1.6574.101.1.1.2
- type: DisplayString
- - labels: []
- labelname: storageIOIndex
- - name: storageIOLA
- oid: 1.3.6.1.4.1.6574.101.1.1.8
- type: gauge
- help: The load of disk (%) - 1.3.6.1.4.1.6574.101.1.1.8
- indexes:
- - labelname: storageIOIndex
- type: gauge
- lookups:
- - labels:
- - storageIOIndex
- labelname: storageIODevice
- oid: 1.3.6.1.4.1.6574.101.1.1.2
- type: DisplayString
- - labels: []
- labelname: storageIOIndex
- - name: storageIOLA1
- oid: 1.3.6.1.4.1.6574.101.1.1.9
- type: gauge
- help: The 1 minute average load of disk (%) - 1.3.6.1.4.1.6574.101.1.1.9
- indexes:
- - labelname: storageIOIndex
- type: gauge
- lookups:
- - labels:
- - storageIOIndex
- labelname: storageIODevice
- oid: 1.3.6.1.4.1.6574.101.1.1.2
- type: DisplayString
- - labels: []
- labelname: storageIOIndex
- - name: storageIOLA5
- oid: 1.3.6.1.4.1.6574.101.1.1.10
- type: gauge
- help: The 5 minute average load of disk (%) - 1.3.6.1.4.1.6574.101.1.1.10
- indexes:
- - labelname: storageIOIndex
- type: gauge
- lookups:
- - labels:
- - storageIOIndex
- labelname: storageIODevice
- oid: 1.3.6.1.4.1.6574.101.1.1.2
- type: DisplayString
- - labels: []
- labelname: storageIOIndex
- - name: storageIOLA15
- oid: 1.3.6.1.4.1.6574.101.1.1.11
- type: gauge
- help: The 15 minute average load of disk (%) - 1.3.6.1.4.1.6574.101.1.1.11
- indexes:
- - labelname: storageIOIndex
- type: gauge
- lookups:
- - labels:
- - storageIOIndex
- labelname: storageIODevice
- oid: 1.3.6.1.4.1.6574.101.1.1.2
- type: DisplayString
- - labels: []
- labelname: storageIOIndex
- - name: storageIONReadX
- oid: 1.3.6.1.4.1.6574.101.1.1.12
- type: counter
- help: The number of bytes read from this device since boot. - 1.3.6.1.4.1.6574.101.1.1.12
- indexes:
- - labelname: storageIOIndex
- type: gauge
- lookups:
- - labels:
- - storageIOIndex
- labelname: storageIODevice
- oid: 1.3.6.1.4.1.6574.101.1.1.2
- type: DisplayString
- - labels: []
- labelname: storageIOIndex
- - name: storageIONWrittenX
- oid: 1.3.6.1.4.1.6574.101.1.1.13
- type: counter
- help: The number of bytes written to this device since boot. - 1.3.6.1.4.1.6574.101.1.1.13
- indexes:
- - labelname: storageIOIndex
- type: gauge
- lookups:
- - labels:
- - storageIOIndex
- labelname: storageIODevice
- oid: 1.3.6.1.4.1.6574.101.1.1.2
- type: DisplayString
- - labels: []
- labelname: storageIOIndex
- - name: storageIODeviceSerial
- oid: 1.3.6.1.4.1.6574.101.1.1.14
- type: DisplayString
- help: The name of the device we are counting/checking. - 1.3.6.1.4.1.6574.101.1.1.14
- indexes:
- - labelname: storageIOIndex
- type: gauge
- lookups:
- - labels:
- - storageIOIndex
- labelname: storageIODevice
- oid: 1.3.6.1.4.1.6574.101.1.1.2
- type: DisplayString
- - labels: []
- labelname: storageIOIndex
- - name: spaceIOIndex
- oid: 1.3.6.1.4.1.6574.102.1.1.1
- type: gauge
- help: Reference index for each observed device. - 1.3.6.1.4.1.6574.102.1.1.1
- indexes:
- - labelname: spaceIOIndex
- type: gauge
- lookups:
- - labels:
- - spaceIOIndex
- labelname: spaceIODevice
- oid: 1.3.6.1.4.1.6574.102.1.1.2
- type: DisplayString
- - labels: []
- labelname: spaceIOIndex
- - name: spaceIODevice
- oid: 1.3.6.1.4.1.6574.102.1.1.2
- type: DisplayString
- help: The name of the device we are counting/checking. - 1.3.6.1.4.1.6574.102.1.1.2
- indexes:
- - labelname: spaceIOIndex
- type: gauge
- lookups:
- - labels:
- - spaceIOIndex
- labelname: spaceIODevice
- oid: 1.3.6.1.4.1.6574.102.1.1.2
- type: DisplayString
- - labels: []
- labelname: spaceIOIndex
- - name: spaceIONRead
- oid: 1.3.6.1.4.1.6574.102.1.1.3
- type: counter
- help: The number of bytes read from this device since boot. - 1.3.6.1.4.1.6574.102.1.1.3
- indexes:
- - labelname: spaceIOIndex
- type: gauge
- lookups:
- - labels:
- - spaceIOIndex
- labelname: spaceIODevice
- oid: 1.3.6.1.4.1.6574.102.1.1.2
- type: DisplayString
- - labels: []
- labelname: spaceIOIndex
- - name: spaceIONWritten
- oid: 1.3.6.1.4.1.6574.102.1.1.4
- type: counter
- help: The number of bytes written to this device since boot. - 1.3.6.1.4.1.6574.102.1.1.4
- indexes:
- - labelname: spaceIOIndex
- type: gauge
- lookups:
- - labels:
- - spaceIOIndex
- labelname: spaceIODevice
- oid: 1.3.6.1.4.1.6574.102.1.1.2
- type: DisplayString
- - labels: []
- labelname: spaceIOIndex
- - name: spaceIOReads
- oid: 1.3.6.1.4.1.6574.102.1.1.5
- type: counter
- help: The number of read accesses from this device since boot. - 1.3.6.1.4.1.6574.102.1.1.5
- indexes:
- - labelname: spaceIOIndex
- type: gauge
- lookups:
- - labels:
- - spaceIOIndex
- labelname: spaceIODevice
- oid: 1.3.6.1.4.1.6574.102.1.1.2
- type: DisplayString
- - labels: []
- labelname: spaceIOIndex
- - name: spaceIOWrites
- oid: 1.3.6.1.4.1.6574.102.1.1.6
- type: counter
- help: The number of write accesses to this device since boot. - 1.3.6.1.4.1.6574.102.1.1.6
- indexes:
- - labelname: spaceIOIndex
- type: gauge
- lookups:
- - labels:
- - spaceIOIndex
- labelname: spaceIODevice
- oid: 1.3.6.1.4.1.6574.102.1.1.2
- type: DisplayString
- - labels: []
- labelname: spaceIOIndex
- - name: spaceIOLA
- oid: 1.3.6.1.4.1.6574.102.1.1.8
- type: gauge
- help: The load of disk (%) - 1.3.6.1.4.1.6574.102.1.1.8
- indexes:
- - labelname: spaceIOIndex
- type: gauge
- lookups:
- - labels:
- - spaceIOIndex
- labelname: spaceIODevice
- oid: 1.3.6.1.4.1.6574.102.1.1.2
- type: DisplayString
- - labels: []
- labelname: spaceIOIndex
- - name: spaceIOLA1
- oid: 1.3.6.1.4.1.6574.102.1.1.9
- type: gauge
- help: The 1 minute average load of disk (%) - 1.3.6.1.4.1.6574.102.1.1.9
- indexes:
- - labelname: spaceIOIndex
- type: gauge
- lookups:
- - labels:
- - spaceIOIndex
- labelname: spaceIODevice
- oid: 1.3.6.1.4.1.6574.102.1.1.2
- type: DisplayString
- - labels: []
- labelname: spaceIOIndex
- - name: spaceIOLA5
- oid: 1.3.6.1.4.1.6574.102.1.1.10
- type: gauge
- help: The 5 minute average load of disk (%) - 1.3.6.1.4.1.6574.102.1.1.10
- indexes:
- - labelname: spaceIOIndex
- type: gauge
- lookups:
- - labels:
- - spaceIOIndex
- labelname: spaceIODevice
- oid: 1.3.6.1.4.1.6574.102.1.1.2
- type: DisplayString
- - labels: []
- labelname: spaceIOIndex
- - name: spaceIOLA15
- oid: 1.3.6.1.4.1.6574.102.1.1.11
- type: gauge
- help: The 15 minute average load of disk (%) - 1.3.6.1.4.1.6574.102.1.1.11
- indexes:
- - labelname: spaceIOIndex
- type: gauge
- lookups:
- - labels:
- - spaceIOIndex
- labelname: spaceIODevice
- oid: 1.3.6.1.4.1.6574.102.1.1.2
- type: DisplayString
- - labels: []
- labelname: spaceIOIndex
- - name: spaceIONReadX
- oid: 1.3.6.1.4.1.6574.102.1.1.12
- type: counter
- help: The number of bytes read from this device since boot. - 1.3.6.1.4.1.6574.102.1.1.12
- indexes:
- - labelname: spaceIOIndex
- type: gauge
- lookups:
- - labels:
- - spaceIOIndex
- labelname: spaceIODevice
- oid: 1.3.6.1.4.1.6574.102.1.1.2
- type: DisplayString
- - labels: []
- labelname: spaceIOIndex
- - name: spaceIONWrittenX
- oid: 1.3.6.1.4.1.6574.102.1.1.13
- type: counter
- help: The number of bytes written to this device since boot. - 1.3.6.1.4.1.6574.102.1.1.13
- indexes:
- - labelname: spaceIOIndex
- type: gauge
- lookups:
- - labels:
- - spaceIOIndex
- labelname: spaceIODevice
- oid: 1.3.6.1.4.1.6574.102.1.1.2
- type: DisplayString
- - labels: []
- labelname: spaceIOIndex
- - name: spaceUUID
- oid: 1.3.6.1.4.1.6574.102.1.1.14
- type: DisplayString
- help: The uuid of space. - 1.3.6.1.4.1.6574.102.1.1.14
- indexes:
- - labelname: spaceIOIndex
- type: gauge
- lookups:
- - labels:
- - spaceIOIndex
- labelname: spaceIODevice
- oid: 1.3.6.1.4.1.6574.102.1.1.2
- type: DisplayString
- - labels: []
- labelname: spaceIOIndex
- - name: iSCSILUNInfoIndex
- oid: 1.3.6.1.4.1.6574.104.1.1.1
- type: gauge
- help: LUN info index - 1.3.6.1.4.1.6574.104.1.1.1
- indexes:
- - labelname: iSCSILUNInfoIndex
- type: gauge
- - name: iSCSILUNUUID
- oid: 1.3.6.1.4.1.6574.104.1.1.2
- type: OctetString
- help: LUN uuid - 1.3.6.1.4.1.6574.104.1.1.2
- indexes:
- - labelname: iSCSILUNInfoIndex
- type: gauge
- - name: iSCSILUNName
- oid: 1.3.6.1.4.1.6574.104.1.1.3
- type: OctetString
- help: LUN name - 1.3.6.1.4.1.6574.104.1.1.3
- indexes:
- - labelname: iSCSILUNInfoIndex
- type: gauge
- - name: iSCSILUNThroughputReadHigh
- oid: 1.3.6.1.4.1.6574.104.1.1.4
- type: gauge
- help: LUN read throughput over 32 bits part - 1.3.6.1.4.1.6574.104.1.1.4
- indexes:
- - labelname: iSCSILUNInfoIndex
- type: gauge
- - name: iSCSILUNThroughputReadLow
- oid: 1.3.6.1.4.1.6574.104.1.1.5
- type: gauge
- help: LUN read throughput in unsigned 32 bit - 1.3.6.1.4.1.6574.104.1.1.5
- indexes:
- - labelname: iSCSILUNInfoIndex
- type: gauge
- - name: iSCSILUNThroughputWriteHigh
- oid: 1.3.6.1.4.1.6574.104.1.1.6
- type: gauge
- help: LUN write throughput over 32 bits part - 1.3.6.1.4.1.6574.104.1.1.6
- indexes:
- - labelname: iSCSILUNInfoIndex
- type: gauge
- - name: iSCSILUNThroughputWriteLow
- oid: 1.3.6.1.4.1.6574.104.1.1.7
- type: gauge
- help: LUN write throughput in unsigned 32 bit - 1.3.6.1.4.1.6574.104.1.1.7
- indexes:
- - labelname: iSCSILUNInfoIndex
- type: gauge
- - name: iSCSILUNIopsRead
- oid: 1.3.6.1.4.1.6574.104.1.1.8
- type: gauge
- help: LUN read iops - 1.3.6.1.4.1.6574.104.1.1.8
- indexes:
- - labelname: iSCSILUNInfoIndex
- type: gauge
- - name: iSCSILUNIopsWrite
- oid: 1.3.6.1.4.1.6574.104.1.1.9
- type: gauge
- help: LUN write iops - 1.3.6.1.4.1.6574.104.1.1.9
- indexes:
- - labelname: iSCSILUNInfoIndex
- type: gauge
- - name: iSCSILUNDiskLatencyRead
- oid: 1.3.6.1.4.1.6574.104.1.1.10
- type: gauge
- help: LUN disk latency when reading - 1.3.6.1.4.1.6574.104.1.1.10
- indexes:
- - labelname: iSCSILUNInfoIndex
- type: gauge
- - name: iSCSILUNDiskLatencyWrite
- oid: 1.3.6.1.4.1.6574.104.1.1.11
- type: gauge
- help: LUN disk latency when writing - 1.3.6.1.4.1.6574.104.1.1.11
- indexes:
- - labelname: iSCSILUNInfoIndex
- type: gauge
- - name: iSCSILUNNetworkLatencyTx
- oid: 1.3.6.1.4.1.6574.104.1.1.12
- type: gauge
- help: LUN transfer data network latency - 1.3.6.1.4.1.6574.104.1.1.12
- indexes:
- - labelname: iSCSILUNInfoIndex
- type: gauge
- - name: iSCSILUNNetworkLatencyRx
- oid: 1.3.6.1.4.1.6574.104.1.1.13
- type: gauge
- help: LUN receive data network latency - 1.3.6.1.4.1.6574.104.1.1.13
- indexes:
- - labelname: iSCSILUNInfoIndex
- type: gauge
- - name: iSCSILUNIoSizeRead
- oid: 1.3.6.1.4.1.6574.104.1.1.14
- type: gauge
- help: LUN average io size when reading - 1.3.6.1.4.1.6574.104.1.1.14
- indexes:
- - labelname: iSCSILUNInfoIndex
- type: gauge
- - name: iSCSILUNIoSizeWrite
- oid: 1.3.6.1.4.1.6574.104.1.1.15
- type: gauge
- help: LUN average io size when writing - 1.3.6.1.4.1.6574.104.1.1.15
- indexes:
- - labelname: iSCSILUNInfoIndex
- type: gauge
- - name: iSCSILUNQueueDepth
- oid: 1.3.6.1.4.1.6574.104.1.1.16
- type: gauge
- help: Num of iSCSI commands in LUN queue - 1.3.6.1.4.1.6574.104.1.1.16
- indexes:
- - labelname: iSCSILUNInfoIndex
- type: gauge
- - name: iSCSILUNType
- oid: 1.3.6.1.4.1.6574.104.1.1.17
- type: OctetString
- help: LUN type - 1.3.6.1.4.1.6574.104.1.1.17
- indexes:
- - labelname: iSCSILUNInfoIndex
- type: gauge
- - name: iSCSILUNDiskLatencyAvg
- oid: 1.3.6.1.4.1.6574.104.1.1.18
- type: gauge
- help: Average latency of LUN disk - 1.3.6.1.4.1.6574.104.1.1.18
- indexes:
- - labelname: iSCSILUNInfoIndex
- type: gauge
- - name: iSCSILUNThinProvisionVolFreeMBs
- oid: 1.3.6.1.4.1.6574.104.1.1.19
- type: gauge
- help: Free space(MB) of thin provisioning lun's volume - 1.3.6.1.4.1.6574.104.1.1.19
- indexes:
- - labelname: iSCSILUNInfoIndex
- type: gauge
- - name: diskIndex
- oid: 1.3.6.1.4.1.6574.2.1.1.1
- type: gauge
- help: The index of disk table - 1.3.6.1.4.1.6574.2.1.1.1
- indexes:
- - labelname: diskIndex
- type: gauge
- lookups:
- - labels:
- - diskIndex
- labelname: diskID
- oid: 1.3.6.1.4.1.6574.2.1.1.2
- type: OctetString
- - labels: []
- labelname: diskIndex
- - name: diskID
- oid: 1.3.6.1.4.1.6574.2.1.1.2
- type: OctetString
- help: Synology disk ID The ID of disk is assigned by disk Station. - 1.3.6.1.4.1.6574.2.1.1.2
- indexes:
- - labelname: diskIndex
- type: gauge
- lookups:
- - labels:
- - diskIndex
- labelname: diskID
- oid: 1.3.6.1.4.1.6574.2.1.1.2
- type: OctetString
- - labels: []
- labelname: diskIndex
- - name: diskModel
- oid: 1.3.6.1.4.1.6574.2.1.1.3
- type: DisplayString
- help: Synology disk model name The disk model name will be showed here. - 1.3.6.1.4.1.6574.2.1.1.3
- indexes:
- - labelname: diskIndex
- type: gauge
- lookups:
- - labels:
- - diskIndex
- labelname: diskID
- oid: 1.3.6.1.4.1.6574.2.1.1.2
- type: OctetString
- - labels: []
- labelname: diskIndex
- - name: diskType
- oid: 1.3.6.1.4.1.6574.2.1.1.4
- type: DisplayString
- help: Synology disk type The type of disk will be showed here, including SATA,
- SSD and so on. - 1.3.6.1.4.1.6574.2.1.1.4
- indexes:
- - labelname: diskIndex
- type: gauge
- lookups:
- - labels:
- - diskIndex
- labelname: diskID
- oid: 1.3.6.1.4.1.6574.2.1.1.2
- type: OctetString
- - labels: []
- labelname: diskIndex
- - name: diskStatus
- oid: 1.3.6.1.4.1.6574.2.1.1.5
- type: gauge
- help: Synology disk status Each meanings of status represented describe below
- - 1.3.6.1.4.1.6574.2.1.1.5
- indexes:
- - labelname: diskIndex
- type: gauge
- lookups:
- - labels:
- - diskIndex
- labelname: diskID
- oid: 1.3.6.1.4.1.6574.2.1.1.2
- type: OctetString
- - labels: []
- labelname: diskIndex
- - name: diskTemperature
- oid: 1.3.6.1.4.1.6574.2.1.1.6
- type: gauge
- help: Synology disk temperature The temperature of each disk uses Celsius degree.
- - 1.3.6.1.4.1.6574.2.1.1.6
- indexes:
- - labelname: diskIndex
- type: gauge
- lookups:
- - labels:
- - diskIndex
- labelname: diskID
- oid: 1.3.6.1.4.1.6574.2.1.1.2
- type: OctetString
- - labels: []
- labelname: diskIndex
- - name: diskRole
- oid: 1.3.6.1.4.1.6574.2.1.1.7
- type: OctetString
- help: Synology disk role The role of the disk in system - 1.3.6.1.4.1.6574.2.1.1.7
- indexes:
- - labelname: diskIndex
- type: gauge
- lookups:
- - labels:
- - diskIndex
- labelname: diskID
- oid: 1.3.6.1.4.1.6574.2.1.1.2
- type: OctetString
- - labels: []
- labelname: diskIndex
- - name: diskRetry
- oid: 1.3.6.1.4.1.6574.2.1.1.8
- type: gauge
- help: Synology disk retry count The count of each disk connection retries. -
- 1.3.6.1.4.1.6574.2.1.1.8
- indexes:
- - labelname: diskIndex
- type: gauge
- lookups:
- - labels:
- - diskIndex
- labelname: diskID
- oid: 1.3.6.1.4.1.6574.2.1.1.2
- type: OctetString
- - labels: []
- labelname: diskIndex
- - name: diskBadSector
- oid: 1.3.6.1.4.1.6574.2.1.1.9
- type: gauge
- help: Synology disk bad sector count The count of each disk I/O bad sector.
- - 1.3.6.1.4.1.6574.2.1.1.9
- indexes:
- - labelname: diskIndex
- type: gauge
- lookups:
- - labels:
- - diskIndex
- labelname: diskID
- oid: 1.3.6.1.4.1.6574.2.1.1.2
- type: OctetString
- - labels: []
- labelname: diskIndex
- - name: diskIdentifyFail
- oid: 1.3.6.1.4.1.6574.2.1.1.10
- type: gauge
- help: Synology disk identify fail count The count of each disk identify fails.
- - 1.3.6.1.4.1.6574.2.1.1.10
- indexes:
- - labelname: diskIndex
- type: gauge
- lookups:
- - labels:
- - diskIndex
- labelname: diskID
- oid: 1.3.6.1.4.1.6574.2.1.1.2
- type: OctetString
- - labels: []
- labelname: diskIndex
- - name: diskRemainLife
- oid: 1.3.6.1.4.1.6574.2.1.1.11
- type: gauge
- help: Synology disk remainLife The estimate remain life of each disk. - 1.3.6.1.4.1.6574.2.1.1.11
- indexes:
- - labelname: diskIndex
- type: gauge
- lookups:
- - labels:
- - diskIndex
- labelname: diskID
- oid: 1.3.6.1.4.1.6574.2.1.1.2
- type: OctetString
- - labels: []
- labelname: diskIndex
- - name: diskName
- oid: 1.3.6.1.4.1.6574.2.1.1.12
- type: OctetString
- help: Synology disk name The name of disk which align to storage manager. -
- 1.3.6.1.4.1.6574.2.1.1.12
- indexes:
- - labelname: diskIndex
- type: gauge
- lookups:
- - labels:
- - diskIndex
- labelname: diskID
- oid: 1.3.6.1.4.1.6574.2.1.1.2
- type: OctetString
- - labels: []
- labelname: diskIndex
- - name: diskHealthStatus
- oid: 1.3.6.1.4.1.6574.2.1.1.13
- type: gauge
- help: Synology disk health status Each meanings of status represented describe
- below - 1.3.6.1.4.1.6574.2.1.1.13
- indexes:
- - labelname: diskIndex
- type: gauge
- lookups:
- - labels:
- - diskIndex
- labelname: diskID
- oid: 1.3.6.1.4.1.6574.2.1.1.2
- type: OctetString
- - labels: []
- labelname: diskIndex
- - name: raidIndex
- oid: 1.3.6.1.4.1.6574.3.1.1.1
- type: gauge
- help: The index of raid table - 1.3.6.1.4.1.6574.3.1.1.1
- indexes:
- - labelname: raidIndex
- type: gauge
- lookups:
- - labels:
- - raidIndex
- labelname: raidName
- oid: 1.3.6.1.4.1.6574.3.1.1.2
- type: DisplayString
- - labels: []
- labelname: raidIndex
- - name: raidName
- oid: 1.3.6.1.4.1.6574.3.1.1.2
- type: DisplayString
- help: Synology raid name The name of each raid will be showed here. - 1.3.6.1.4.1.6574.3.1.1.2
- indexes:
- - labelname: raidIndex
- type: gauge
- lookups:
- - labels:
- - raidIndex
- labelname: raidName
- oid: 1.3.6.1.4.1.6574.3.1.1.2
- type: DisplayString
- - labels: []
- labelname: raidIndex
- - name: raidStatus
- oid: 1.3.6.1.4.1.6574.3.1.1.3
- type: gauge
- help: Synology Raid status Each meanings of status represented describe below
- - 1.3.6.1.4.1.6574.3.1.1.3
- indexes:
- - labelname: raidIndex
- type: gauge
- lookups:
- - labels:
- - raidIndex
- labelname: raidName
- oid: 1.3.6.1.4.1.6574.3.1.1.2
- type: DisplayString
- - labels: []
- labelname: raidIndex
- - name: raidFreeSize
- oid: 1.3.6.1.4.1.6574.3.1.1.4
- type: gauge
- help: Synology raid freesize Free space in bytes. - 1.3.6.1.4.1.6574.3.1.1.4
- indexes:
- - labelname: raidIndex
- type: gauge
- lookups:
- - labels:
- - raidIndex
- labelname: raidName
- oid: 1.3.6.1.4.1.6574.3.1.1.2
- type: DisplayString
- - labels: []
- labelname: raidIndex
- - name: raidTotalSize
- oid: 1.3.6.1.4.1.6574.3.1.1.5
- type: gauge
- help: Synology raid totalsize Total space in bytes. - 1.3.6.1.4.1.6574.3.1.1.5
- indexes:
- - labelname: raidIndex
- type: gauge
- lookups:
- - labels:
- - raidIndex
- labelname: raidName
- oid: 1.3.6.1.4.1.6574.3.1.1.2
- type: DisplayString
- - labels: []
- labelname: raidIndex
- - name: raidHotspareCnt
- oid: 1.3.6.1.4.1.6574.3.1.1.6
- type: gauge
- help: Synology raid hotspare Total hotspare disks count - 1.3.6.1.4.1.6574.3.1.1.6
- indexes:
- - labelname: raidIndex
- type: gauge
- lookups:
- - labels:
- - raidIndex
- labelname: raidName
- oid: 1.3.6.1.4.1.6574.3.1.1.2
- type: DisplayString
- - labels: []
- labelname: raidIndex
- - name: upsDeviceModel
- oid: 1.3.6.1.4.1.6574.4.1.1
- type: DisplayString
- help: Device model - 1.3.6.1.4.1.6574.4.1.1
- - name: upsDeviceManufacturer
- oid: 1.3.6.1.4.1.6574.4.1.2
- type: DisplayString
- help: Device manufacturer - 1.3.6.1.4.1.6574.4.1.2
- - name: upsDeviceSerial
- oid: 1.3.6.1.4.1.6574.4.1.3
- type: DisplayString
- help: Device serial number. - 1.3.6.1.4.1.6574.4.1.3
- - name: upsDeviceType
- oid: 1.3.6.1.4.1.6574.4.1.4
- type: DisplayString
- help: Device type (ups, pdu, scd, psu) - 1.3.6.1.4.1.6574.4.1.4
- - name: upsDeviceDescription
- oid: 1.3.6.1.4.1.6574.4.1.5
- type: DisplayString
- help: Device description. - 1.3.6.1.4.1.6574.4.1.5
- - name: upsDeviceContact
- oid: 1.3.6.1.4.1.6574.4.1.6
- type: DisplayString
- help: Device administrator name. - 1.3.6.1.4.1.6574.4.1.6
- - name: upsDeviceLocation
- oid: 1.3.6.1.4.1.6574.4.1.7
- type: DisplayString
- help: Device physical location. - 1.3.6.1.4.1.6574.4.1.7
- - name: upsDevicePart
- oid: 1.3.6.1.4.1.6574.4.1.8
- type: DisplayString
- help: Device part number. - 1.3.6.1.4.1.6574.4.1.8
- - name: upsDeviceMACAddr
- oid: 1.3.6.1.4.1.6574.4.1.9
- type: DisplayString
- help: Physical network address of the device. - 1.3.6.1.4.1.6574.4.1.9
- - name: upsInfoStatus
- oid: 1.3.6.1.4.1.6574.4.2.1
- type: DisplayString
- help: UPS status. - 1.3.6.1.4.1.6574.4.2.1
- - name: upsInfoAlarm
- oid: 1.3.6.1.4.1.6574.4.2.2
- type: DisplayString
- help: UPS alarms - 1.3.6.1.4.1.6574.4.2.2
- - name: upsInfoTime
- oid: 1.3.6.1.4.1.6574.4.2.3
- type: DisplayString
- help: Internal UPS clock time - 1.3.6.1.4.1.6574.4.2.3
- - name: upsInfoDate
- oid: 1.3.6.1.4.1.6574.4.2.4
- type: DisplayString
- help: Internal UPS clock date - 1.3.6.1.4.1.6574.4.2.4
- - name: upsInfoModel
- oid: 1.3.6.1.4.1.6574.4.2.5
- type: DisplayString
- help: UPS model - 1.3.6.1.4.1.6574.4.2.5
- - name: upsInfoMfrName
- oid: 1.3.6.1.4.1.6574.4.2.6.1
- type: DisplayString
- help: UPS manufacturer - 1.3.6.1.4.1.6574.4.2.6.1
- - name: upsInfoMfrDate
- oid: 1.3.6.1.4.1.6574.4.2.6.2
- type: DisplayString
- help: UPS manufacturing date - 1.3.6.1.4.1.6574.4.2.6.2
- - name: upsInfoSerial
- oid: 1.3.6.1.4.1.6574.4.2.7
- type: DisplayString
- help: UPS serial number - 1.3.6.1.4.1.6574.4.2.7
- - name: upsInfoVendorID
- oid: 1.3.6.1.4.1.6574.4.2.8
- type: DisplayString
- help: Vendor ID for USB devices - 1.3.6.1.4.1.6574.4.2.8
- - name: upsInfoProductID
- oid: 1.3.6.1.4.1.6574.4.2.9
- type: DisplayString
- help: Product ID for USB devices - 1.3.6.1.4.1.6574.4.2.9
- - name: upsInfoFirmwareName
- oid: 1.3.6.1.4.1.6574.4.2.10.1
- type: DisplayString
- help: UPS firmware - 1.3.6.1.4.1.6574.4.2.10.1
- - name: upsInfoFirmwareAux
- oid: 1.3.6.1.4.1.6574.4.2.10.2
- type: DisplayString
- help: Auxiliary device firmware - 1.3.6.1.4.1.6574.4.2.10.2
- - name: upsInfoTemperature
- oid: 1.3.6.1.4.1.6574.4.2.11
- type: Float
- help: UPS temperature (degrees C) - 1.3.6.1.4.1.6574.4.2.11
- - name: upsInfoLoadValue
- oid: 1.3.6.1.4.1.6574.4.2.12.1
- type: Float
- help: Load on UPS (percent) - 1.3.6.1.4.1.6574.4.2.12.1
- - name: upsInfoLoadHigh
- oid: 1.3.6.1.4.1.6574.4.2.12.2
- type: Float
- help: Load when UPS switches to overload condition (OVER) (percent) - 1.3.6.1.4.1.6574.4.2.12.2
- - name: upsInfoID
- oid: 1.3.6.1.4.1.6574.4.2.13
- type: DisplayString
- help: UPS system identifier - 1.3.6.1.4.1.6574.4.2.13
- - name: upsInfoDelayStart
- oid: 1.3.6.1.4.1.6574.4.2.14.1
- type: gauge
- help: Interval to wait before restarting the load (seconds) - 1.3.6.1.4.1.6574.4.2.14.1
- - name: upsInfoDelayReboot
- oid: 1.3.6.1.4.1.6574.4.2.14.2
- type: gauge
- help: Interval to wait before rebooting the UPS (seconds) - 1.3.6.1.4.1.6574.4.2.14.2
- - name: upsInfoDelayShutdown
- oid: 1.3.6.1.4.1.6574.4.2.14.3
- type: gauge
- help: Interval to wait after shutdown with delay command (seconds) - 1.3.6.1.4.1.6574.4.2.14.3
- - name: upsInfoTimerStart
- oid: 1.3.6.1.4.1.6574.4.2.15.1
- type: gauge
- help: Time before the load will be started (seconds) - 1.3.6.1.4.1.6574.4.2.15.1
- - name: upsInfoTimerReboot
- oid: 1.3.6.1.4.1.6574.4.2.15.2
- type: gauge
- help: Time before the load will be rebooted (seconds) - 1.3.6.1.4.1.6574.4.2.15.2
- - name: upsInfoTimerShutdown
- oid: 1.3.6.1.4.1.6574.4.2.15.3
- type: gauge
- help: Time before the load will be shutdown (seconds) - 1.3.6.1.4.1.6574.4.2.15.3
- - name: upsInfoTestInterval
- oid: 1.3.6.1.4.1.6574.4.2.16.1
- type: gauge
- help: Interval between self tests - 1.3.6.1.4.1.6574.4.2.16.1
- - name: upsInfoTestResult
- oid: 1.3.6.1.4.1.6574.4.2.16.2
- type: DisplayString
- help: Results of last self test - 1.3.6.1.4.1.6574.4.2.16.2
- - name: upsInfoDisplayLanguage
- oid: 1.3.6.1.4.1.6574.4.2.17
- type: DisplayString
- help: Language to use on front panel - 1.3.6.1.4.1.6574.4.2.17
- - name: upsInfoContacts
- oid: 1.3.6.1.4.1.6574.4.2.18
- type: DisplayString
- help: UPS external contact sensors - 1.3.6.1.4.1.6574.4.2.18
- - name: upsInfoEffciency
- oid: 1.3.6.1.4.1.6574.4.2.19
- type: gauge
- help: Efficiency of the UPS (ratio of the output current on the input current)
- (percent) - 1.3.6.1.4.1.6574.4.2.19
- - name: upsInfoPowerValue
- oid: 1.3.6.1.4.1.6574.4.2.20.1
- type: Float
- help: Current value of apparent power (Volt-Amps) - 1.3.6.1.4.1.6574.4.2.20.1
- - name: upsInfoPowerNominal
- oid: 1.3.6.1.4.1.6574.4.2.20.2
- type: Float
- help: Nominal value of apparent power (Volt-Amps) - 1.3.6.1.4.1.6574.4.2.20.2
- - name: upsInfoRealPowerValue
- oid: 1.3.6.1.4.1.6574.4.2.21.1
- type: Float
- help: Current value of real power (Watts) - 1.3.6.1.4.1.6574.4.2.21.1
- - name: upsInfoRealPowerNominal
- oid: 1.3.6.1.4.1.6574.4.2.21.2
- type: Float
- help: Nominal value of real power (Watts) - 1.3.6.1.4.1.6574.4.2.21.2
- - name: upsInfoBeeperStatus
- oid: 1.3.6.1.4.1.6574.4.2.22
- type: DisplayString
- help: UPS beeper status (enabled, disabled or muted) - 1.3.6.1.4.1.6574.4.2.22
- - name: upsInfoType
- oid: 1.3.6.1.4.1.6574.4.2.23
- type: DisplayString
- help: UPS type - 1.3.6.1.4.1.6574.4.2.23
- - name: upsInfoWatchdogStatus
- oid: 1.3.6.1.4.1.6574.4.2.24
- type: DisplayString
- help: UPS watchdog status (enabled or disabled) - 1.3.6.1.4.1.6574.4.2.24
- - name: upsInfoStartAuto
- oid: 1.3.6.1.4.1.6574.4.2.25.1
- type: DisplayString
- help: UPS starts when mains is (re)applied - 1.3.6.1.4.1.6574.4.2.25.1
- - name: upsInfoStartBattery
- oid: 1.3.6.1.4.1.6574.4.2.25.2
- type: DisplayString
- help: Allow to start UPS from battery - 1.3.6.1.4.1.6574.4.2.25.2
- - name: upsInfoStartReboot
- oid: 1.3.6.1.4.1.6574.4.2.25.3
- type: DisplayString
- help: UPS coldstarts from battery (enabled or disabled) - 1.3.6.1.4.1.6574.4.2.25.3
- - name: upsBatteryChargeValue
- oid: 1.3.6.1.4.1.6574.4.3.1.1
- type: Float
- help: Battery charge - 1.3.6.1.4.1.6574.4.3.1.1
- - name: upsBatteryChargeLow
- oid: 1.3.6.1.4.1.6574.4.3.1.2
- type: Float
- help: Remaining battery level when UPS switches to LB (percent) - 1.3.6.1.4.1.6574.4.3.1.2
- - name: upsBatteryChargeRestart
- oid: 1.3.6.1.4.1.6574.4.3.1.3
- type: Float
- help: Minimum battery level for UPS restart after power-off - 1.3.6.1.4.1.6574.4.3.1.3
- - name: upsBatteryChargeWarning
- oid: 1.3.6.1.4.1.6574.4.3.1.4
- type: Float
- help: Battery level when UPS switches to Warning state (percent) - 1.3.6.1.4.1.6574.4.3.1.4
- - name: upsBatteryVoltageValue
- oid: 1.3.6.1.4.1.6574.4.3.2.1
- type: Float
- help: The magnitude of the present battery voltage. - 1.3.6.1.4.1.6574.4.3.2.1
- - name: upsBatteryVoltageNominal
- oid: 1.3.6.1.4.1.6574.4.3.2.2
- type: Float
- help: Nominal battery voltage. - 1.3.6.1.4.1.6574.4.3.2.2
- - name: upsBatteryVoltageLow
- oid: 1.3.6.1.4.1.6574.4.3.2.3
- type: Float
- help: Minimum battery voltage, that triggers FSD status . - 1.3.6.1.4.1.6574.4.3.2.3
- - name: upsBatteryVoltageHigh
- oid: 1.3.6.1.4.1.6574.4.3.2.4
- type: Float
- help: Maximum battery voltage (Ie battery.charge = 100). - 1.3.6.1.4.1.6574.4.3.2.4
- - name: upsBatteryCapacity
- oid: 1.3.6.1.4.1.6574.4.3.3
- type: Float
- help: Battery capacity (Ah) - 1.3.6.1.4.1.6574.4.3.3
- - name: upsBatteryCurrent
- oid: 1.3.6.1.4.1.6574.4.3.4
- type: Float
- help: The present battery current. - 1.3.6.1.4.1.6574.4.3.4
- - name: upsBatteryTemperature
- oid: 1.3.6.1.4.1.6574.4.3.5
- type: Float
- help: The ambient temperature at or near the UPS Battery casing. - 1.3.6.1.4.1.6574.4.3.5
- - name: upsBatteryRuntimeValue
- oid: 1.3.6.1.4.1.6574.4.3.6.1
- type: gauge
- help: Battery runtime (seconds) - 1.3.6.1.4.1.6574.4.3.6.1
- - name: upsBatteryRuntimeLow
- oid: 1.3.6.1.4.1.6574.4.3.6.2
- type: gauge
- help: Remaining battery runtime when UPS switches to LB (seconds) - 1.3.6.1.4.1.6574.4.3.6.2
- - name: upsBatteryRuntimeRestart
- oid: 1.3.6.1.4.1.6574.4.3.6.3
- type: gauge
- help: Minimum battery runtime for UPS restart after power-off (seconds) - 1.3.6.1.4.1.6574.4.3.6.3
- - name: upsBatteryAlarmThreshold
- oid: 1.3.6.1.4.1.6574.4.3.7
- type: DisplayString
- help: Battery alarm threshold - 1.3.6.1.4.1.6574.4.3.7
- - name: upsBatteryDate
- oid: 1.3.6.1.4.1.6574.4.3.8
- type: DisplayString
- help: Battery change date - 1.3.6.1.4.1.6574.4.3.8
- - name: upsBatteryMfrDate
- oid: 1.3.6.1.4.1.6574.4.3.9
- type: DisplayString
- help: Battery manufacturing date - 1.3.6.1.4.1.6574.4.3.9
- - name: upsBatteryPacks
- oid: 1.3.6.1.4.1.6574.4.3.10
- type: gauge
- help: Number of battery packs - 1.3.6.1.4.1.6574.4.3.10
- - name: upsBatteryPacksBad
- oid: 1.3.6.1.4.1.6574.4.3.11
- type: gauge
- help: Number of bad battery packs - 1.3.6.1.4.1.6574.4.3.11
- - name: upsBatteryType
- oid: 1.3.6.1.4.1.6574.4.3.12
- type: DisplayString
- help: Battery chemistry - 1.3.6.1.4.1.6574.4.3.12
- - name: upsBatteryProtection
- oid: 1.3.6.1.4.1.6574.4.3.13
- type: DisplayString
- help: Prevent deep discharge of battery - 1.3.6.1.4.1.6574.4.3.13
- - name: upsBatteryEnergySave
- oid: 1.3.6.1.4.1.6574.4.3.14
- type: DisplayString
- help: Switch off when running on battery and no/low load - 1.3.6.1.4.1.6574.4.3.14
- - name: upsInputVoltageValue
- oid: 1.3.6.1.4.1.6574.4.4.1.1
- type: Float
- help: Input voltage - 1.3.6.1.4.1.6574.4.4.1.1
- - name: upsInputVoltageMax
- oid: 1.3.6.1.4.1.6574.4.4.1.2
- type: Float
- help: Maximum incoming voltage seen - 1.3.6.1.4.1.6574.4.4.1.2
- - name: upsInputVoltageMin
- oid: 1.3.6.1.4.1.6574.4.4.1.3
- type: Float
- help: Minimum incoming voltage seen - 1.3.6.1.4.1.6574.4.4.1.3
- - name: upsInputVoltageNominal
- oid: 1.3.6.1.4.1.6574.4.4.1.4
- type: Float
- help: Nominal input voltage - 1.3.6.1.4.1.6574.4.4.1.4
- - name: upsInputVoltageExtend
- oid: 1.3.6.1.4.1.6574.4.4.1.5
- type: DisplayString
- help: Extended input voltage range - 1.3.6.1.4.1.6574.4.4.1.5
- - name: upsInputVoltageFault
- oid: 1.3.6.1.4.1.6574.4.4.1.6
- type: Float
- help: Input voltage Fault - 1.3.6.1.4.1.6574.4.4.1.6
- - name: upsInputTransferReason
- oid: 1.3.6.1.4.1.6574.4.4.2.1
- type: DisplayString
- help: Reason for last transfer to battery - 1.3.6.1.4.1.6574.4.4.2.1
- - name: upsInputTransferLow
- oid: 1.3.6.1.4.1.6574.4.4.2.2
- type: Float
- help: Low voltage transfer point - 1.3.6.1.4.1.6574.4.4.2.2
- - name: upsInputTransferHigh
- oid: 1.3.6.1.4.1.6574.4.4.2.3
- type: Float
- help: High voltage transfer point - 1.3.6.1.4.1.6574.4.4.2.3
- - name: upsInputTransferLowMin
- oid: 1.3.6.1.4.1.6574.4.4.2.4
- type: Float
- help: smallest settable low voltage transfer point - 1.3.6.1.4.1.6574.4.4.2.4
- - name: upsInputTransferLowMax
- oid: 1.3.6.1.4.1.6574.4.4.2.5
- type: Float
- help: greatest settable low voltage transfer point - 1.3.6.1.4.1.6574.4.4.2.5
- - name: upsInputTransferHighMin
- oid: 1.3.6.1.4.1.6574.4.4.2.6
- type: Float
- help: smallest settable high voltage transfer point - 1.3.6.1.4.1.6574.4.4.2.6
- - name: upsInputTransferHighMax
- oid: 1.3.6.1.4.1.6574.4.4.2.7
- type: Float
- help: greatest settable high voltage transfer point - 1.3.6.1.4.1.6574.4.4.2.7
- - name: upsInputTransferBoostLow
- oid: 1.3.6.1.4.1.6574.4.4.2.8
- type: Float
- help: Low voltage boosting transfer point - 1.3.6.1.4.1.6574.4.4.2.8
- - name: upsInputTransferBoostHigh
- oid: 1.3.6.1.4.1.6574.4.4.2.9
- type: Float
- help: High voltage boosting transfer point - 1.3.6.1.4.1.6574.4.4.2.9
- - name: upsInputTransferTrimLow
- oid: 1.3.6.1.4.1.6574.4.4.2.10
- type: Float
- help: Low voltage trimming transfer point - 1.3.6.1.4.1.6574.4.4.2.10
- - name: upsInputTransferTrimHigh
- oid: 1.3.6.1.4.1.6574.4.4.2.11
- type: Float
- help: High voltage trimming transfer point - 1.3.6.1.4.1.6574.4.4.2.11
- - name: upsInputSensitivity
- oid: 1.3.6.1.4.1.6574.4.4.3
- type: DisplayString
- help: Input power sensitivity - 1.3.6.1.4.1.6574.4.4.3
- - name: upsInputQuality
- oid: 1.3.6.1.4.1.6574.4.4.4
- type: DisplayString
- help: Input power quality - 1.3.6.1.4.1.6574.4.4.4
- - name: upsInputCurrentValue
- oid: 1.3.6.1.4.1.6574.4.4.5.1
- type: Float
- help: Input current (A) - 1.3.6.1.4.1.6574.4.4.5.1
- - name: upsInputCurrentNominal
- oid: 1.3.6.1.4.1.6574.4.4.5.2
- type: Float
- help: Nominal input current (A) - 1.3.6.1.4.1.6574.4.4.5.2
- - name: upsInputFrequencyValue
- oid: 1.3.6.1.4.1.6574.4.4.6.1
- type: Float
- help: Input line frequency (Hz) - 1.3.6.1.4.1.6574.4.4.6.1
- - name: upsInputFrequencyNominal
- oid: 1.3.6.1.4.1.6574.4.4.6.2
- type: Float
- help: Nominal input line frequency (Hz) - 1.3.6.1.4.1.6574.4.4.6.2
- - name: upsInputFrequencyLow
- oid: 1.3.6.1.4.1.6574.4.4.6.3
- type: Float
- help: Input line frequency low (Hz) - 1.3.6.1.4.1.6574.4.4.6.3
- - name: upsInputFrequencyHigh
- oid: 1.3.6.1.4.1.6574.4.4.6.4
- type: Float
- help: Input line frequency high (Hz) - 1.3.6.1.4.1.6574.4.4.6.4
- - name: upsInputFrequencyExtend
- oid: 1.3.6.1.4.1.6574.4.4.6.5
- type: DisplayString
- help: Extended input frequency range - 1.3.6.1.4.1.6574.4.4.6.5
- - name: upsOutputVoltageValue
- oid: 1.3.6.1.4.1.6574.4.5.1.1
- type: Float
- help: Output voltage (V) - 1.3.6.1.4.1.6574.4.5.1.1
- - name: upsOutputVoltageNominal
- oid: 1.3.6.1.4.1.6574.4.5.1.2
- type: Float
- help: Nominal output voltage (V) - 1.3.6.1.4.1.6574.4.5.1.2
- - name: upsOutputFrequencyValue
- oid: 1.3.6.1.4.1.6574.4.5.2.1
- type: Float
- help: Output frequency (Hz) - 1.3.6.1.4.1.6574.4.5.2.1
- - name: upsOutputFrequencyNominal
- oid: 1.3.6.1.4.1.6574.4.5.2.2
- type: Float
- help: Nominal output frequency (Hz) - 1.3.6.1.4.1.6574.4.5.2.2
- - name: upsOutputCurrentValue
- oid: 1.3.6.1.4.1.6574.4.5.3.1
- type: Float
- help: Output current (A) - 1.3.6.1.4.1.6574.4.5.3.1
- - name: upsOutputCurrentNominal
- oid: 1.3.6.1.4.1.6574.4.5.3.2
- type: Float
- help: Nominal output current (A) - 1.3.6.1.4.1.6574.4.5.3.2
- - name: upsAmbientTemperatureValue
- oid: 1.3.6.1.4.1.6574.4.6.1.1
- type: Float
- help: Ambient temperature (degrees C) - 1.3.6.1.4.1.6574.4.6.1.1
- - name: upsAmbientTemperatureAlarm
- oid: 1.3.6.1.4.1.6574.4.6.1.2
- type: DisplayString
- help: Temperature alarm (enabled/disabled) - 1.3.6.1.4.1.6574.4.6.1.2
- - name: upsAmbientTemperatureHigh
- oid: 1.3.6.1.4.1.6574.4.6.1.3
- type: Float
- help: Temperature threshold high (degrees C) - 1.3.6.1.4.1.6574.4.6.1.3
- - name: upsAmbientTemperatureLow
- oid: 1.3.6.1.4.1.6574.4.6.1.4
- type: Float
- help: Temperature threshold low (degrees C) - 1.3.6.1.4.1.6574.4.6.1.4
- - name: upsAmbientTemperatureMax
- oid: 1.3.6.1.4.1.6574.4.6.1.5
- type: Float
- help: Maximum temperature seen (degrees C) - 1.3.6.1.4.1.6574.4.6.1.5
- - name: upsAmbientTemperatureMin
- oid: 1.3.6.1.4.1.6574.4.6.1.6
- type: Float
- help: Minimum temperature seen (degrees C) - 1.3.6.1.4.1.6574.4.6.1.6
- - name: upsAmbientHumidityValue
- oid: 1.3.6.1.4.1.6574.4.6.2.1
- type: Float
- help: Ambient relative humidity (percent) - 1.3.6.1.4.1.6574.4.6.2.1
- - name: upsAmbientHumidityAlarm
- oid: 1.3.6.1.4.1.6574.4.6.2.2
- type: DisplayString
- help: Relative humidity alarm (enabled/disabled) - 1.3.6.1.4.1.6574.4.6.2.2
- - name: upsAmbientHumidityHigh
- oid: 1.3.6.1.4.1.6574.4.6.2.3
- type: Float
- help: Relative humidity threshold high (percent) - 1.3.6.1.4.1.6574.4.6.2.3
- - name: upsAmbientHumidityLow
- oid: 1.3.6.1.4.1.6574.4.6.2.4
- type: Float
- help: Relative humidity threshold low (percent) - 1.3.6.1.4.1.6574.4.6.2.4
- - name: upsAmbientHumidityMax
- oid: 1.3.6.1.4.1.6574.4.6.2.5
- type: Float
- help: Maximum relative humidity seen (percent) - 1.3.6.1.4.1.6574.4.6.2.5
- - name: upsAmbientHumidityMin
- oid: 1.3.6.1.4.1.6574.4.6.2.6
- type: Float
- help: Minimum relative humidity seen (percent) - 1.3.6.1.4.1.6574.4.6.2.6
- - name: upsDriverName
- oid: 1.3.6.1.4.1.6574.4.7.1
- type: DisplayString
- help: Driver name - 1.3.6.1.4.1.6574.4.7.1
- - name: upsDriverVersion
- oid: 1.3.6.1.4.1.6574.4.7.2
- type: DisplayString
- help: Driver version (NUT release) - 1.3.6.1.4.1.6574.4.7.2
- - name: upsDriverVersionData
- oid: 1.3.6.1.4.1.6574.4.7.3
- type: DisplayString
- help: Driver version data - 1.3.6.1.4.1.6574.4.7.3
- - name: upsDriverVersionInternal
- oid: 1.3.6.1.4.1.6574.4.7.4
- type: DisplayString
- help: Internal driver version (if tracked separately) - 1.3.6.1.4.1.6574.4.7.4
- - name: upsDriverPollInterval
- oid: 1.3.6.1.4.1.6574.4.7.5
- type: gauge
- help: Poll interval setup in configuration file - 1.3.6.1.4.1.6574.4.7.5
- - name: upsDriverPort
- oid: 1.3.6.1.4.1.6574.4.7.6
- type: DisplayString
- help: Port setup in configuration file - 1.3.6.1.4.1.6574.4.7.6
- - name: upsDriverPollFrequency
- oid: 1.3.6.1.4.1.6574.4.7.7
- type: gauge
- help: Poll frequency - 1.3.6.1.4.1.6574.4.7.7
- - name: upsDriverProductID
- oid: 1.3.6.1.4.1.6574.4.7.8
- type: DisplayString
- help: Product ID - 1.3.6.1.4.1.6574.4.7.8
- - name: upsDriverSnmpVersion
- oid: 1.3.6.1.4.1.6574.4.7.9
- type: DisplayString
- help: Snmp version - 1.3.6.1.4.1.6574.4.7.9
- - name: upsServerInfo
- oid: 1.3.6.1.4.1.6574.4.8.1
- type: DisplayString
- help: Server information - 1.3.6.1.4.1.6574.4.8.1
- - name: upsServerVersion
- oid: 1.3.6.1.4.1.6574.4.8.2
- type: DisplayString
- help: Server version - 1.3.6.1.4.1.6574.4.8.2
- - name: diskSMARTInfoIndex
- oid: 1.3.6.1.4.1.6574.5.1.1.1
- type: gauge
- help: SMART info index - 1.3.6.1.4.1.6574.5.1.1.1
- indexes:
- - labelname: diskSMARTInfoIndex
- type: gauge
- - name: diskSMARTInfoDevName
- oid: 1.3.6.1.4.1.6574.5.1.1.2
- type: DisplayString
- help: SMART info device name - 1.3.6.1.4.1.6574.5.1.1.2
- indexes:
- - labelname: diskSMARTInfoIndex
- type: gauge
- - name: diskSMARTAttrName
- oid: 1.3.6.1.4.1.6574.5.1.1.3
- type: DisplayString
- help: SMART attribute name - 1.3.6.1.4.1.6574.5.1.1.3
- indexes:
- - labelname: diskSMARTInfoIndex
- type: gauge
- - name: diskSMARTAttrId
- oid: 1.3.6.1.4.1.6574.5.1.1.4
- type: gauge
- help: SMART attribute ID - 1.3.6.1.4.1.6574.5.1.1.4
- indexes:
- - labelname: diskSMARTInfoIndex
- type: gauge
- - name: diskSMARTAttrCurrent
- oid: 1.3.6.1.4.1.6574.5.1.1.5
- type: gauge
- help: SMART attribute current value - 1.3.6.1.4.1.6574.5.1.1.5
- indexes:
- - labelname: diskSMARTInfoIndex
- type: gauge
- - name: diskSMARTAttrWorst
- oid: 1.3.6.1.4.1.6574.5.1.1.6
- type: gauge
- help: SMART attribute worst value - 1.3.6.1.4.1.6574.5.1.1.6
- indexes:
- - labelname: diskSMARTInfoIndex
- type: gauge
- - name: diskSMARTAttrThreshold
- oid: 1.3.6.1.4.1.6574.5.1.1.7
- type: gauge
- help: SMART attribute threshold value - 1.3.6.1.4.1.6574.5.1.1.7
- indexes:
- - labelname: diskSMARTInfoIndex
- type: gauge
- - name: diskSMARTAttrRaw
- oid: 1.3.6.1.4.1.6574.5.1.1.8
- type: gauge
- help: SMART attribute raw value - 1.3.6.1.4.1.6574.5.1.1.8
- indexes:
- - labelname: diskSMARTInfoIndex
- type: gauge
- - name: diskSMARTAttrStatus
- oid: 1.3.6.1.4.1.6574.5.1.1.9
- type: DisplayString
- help: SMART attribute status - 1.3.6.1.4.1.6574.5.1.1.9
- indexes:
- - labelname: diskSMARTInfoIndex
- type: gauge
- - name: serviceInfoIndex
- oid: 1.3.6.1.4.1.6574.6.1.1.1
- type: gauge
- help: Service info index - 1.3.6.1.4.1.6574.6.1.1.1
- indexes:
- - labelname: serviceInfoIndex
- type: gauge
- lookups:
- - labels:
- - serviceInfoIndex
- labelname: serviceName
- oid: 1.3.6.1.4.1.6574.6.1.1.2
- type: DisplayString
- - labels: []
- labelname: serviceInfoIndex
- - name: serviceName
- oid: 1.3.6.1.4.1.6574.6.1.1.2
- type: DisplayString
- help: Service name - 1.3.6.1.4.1.6574.6.1.1.2
- indexes:
- - labelname: serviceInfoIndex
- type: gauge
- lookups:
- - labels:
- - serviceInfoIndex
- labelname: serviceName
- oid: 1.3.6.1.4.1.6574.6.1.1.2
- type: DisplayString
- - labels: []
- labelname: serviceInfoIndex
- - name: serviceUsers
- oid: 1.3.6.1.4.1.6574.6.1.1.3
- type: gauge
- help: Number of users using this service - 1.3.6.1.4.1.6574.6.1.1.3
- indexes:
- - labelname: serviceInfoIndex
- type: gauge
- lookups:
- - labels:
- - serviceInfoIndex
- labelname: serviceName
- oid: 1.3.6.1.4.1.6574.6.1.1.2
- type: DisplayString
- - labels: []
- labelname: serviceInfoIndex
Advertisement