Guest User

Untitled

a guest
Nov 27th, 2023
131
0
Never
Not a member of Pastebin yet? Sign Up, it unlocks many cool features!
text 209.86 KB | Software | 0 0
  1. # WARNING: This file was auto-generated using snmp_exporter generator, manual changes will be lost.
  2. auths:
  3. public_v1:
  4. community: public
  5. security_level: noAuthNoPriv
  6. auth_protocol: MD5
  7. priv_protocol: DES
  8. version: 1
  9. public_v2:
  10. community: public
  11. security_level: noAuthNoPriv
  12. auth_protocol: MD5
  13. priv_protocol: DES
  14. version: 2
  15. modules:
  16. apcups:
  17. walk:
  18. - 1.3.6.1.4.1.318.1.1.1.12
  19. - 1.3.6.1.4.1.318.1.1.1.2
  20. - 1.3.6.1.4.1.318.1.1.1.3
  21. - 1.3.6.1.4.1.318.1.1.1.4
  22. - 1.3.6.1.4.1.318.1.1.1.7.2
  23. - 1.3.6.1.4.1.318.1.1.10.2.3.2
  24. - 1.3.6.1.4.1.318.1.1.26.10.2.2
  25. - 1.3.6.1.4.1.318.1.1.26.4.3
  26. - 1.3.6.1.4.1.318.1.1.26.6.3
  27. - 1.3.6.1.4.1.318.1.1.26.8.3
  28. get:
  29. - 1.3.6.1.4.1.318.1.1.1.8.1.0
  30. metrics:
  31. - name: upsOutletGroupStatusTableSize
  32. oid: 1.3.6.1.4.1.318.1.1.1.12.1.1
  33. type: gauge
  34. help: The number of outlet groups for the UPS. - 1.3.6.1.4.1.318.1.1.1.12.1.1
  35. - name: upsOutletGroupStatusIndex
  36. oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.1
  37. type: gauge
  38. help: The index to the outlet group entry. - 1.3.6.1.4.1.318.1.1.1.12.1.2.1.1
  39. indexes:
  40. - labelname: upsOutletGroupStatusIndex
  41. type: gauge
  42. lookups:
  43. - labels:
  44. - upsOutletGroupStatusIndex
  45. labelname: upsOutletGroupStatusName
  46. oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.2
  47. type: DisplayString
  48. - labels: []
  49. labelname: upsOutletGroupStatusIndex
  50. - name: upsOutletGroupStatusName
  51. oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.2
  52. type: DisplayString
  53. help: The name of the outlet group - 1.3.6.1.4.1.318.1.1.1.12.1.2.1.2
  54. indexes:
  55. - labelname: upsOutletGroupStatusIndex
  56. type: gauge
  57. lookups:
  58. - labels:
  59. - upsOutletGroupStatusIndex
  60. labelname: upsOutletGroupStatusName
  61. oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.2
  62. type: DisplayString
  63. - labels: []
  64. labelname: upsOutletGroupStatusIndex
  65. - name: upsOutletGroupStatusGroupState
  66. oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.3
  67. type: gauge
  68. help: Getting this variable will return the outlet group state - 1.3.6.1.4.1.318.1.1.1.12.1.2.1.3
  69. indexes:
  70. - labelname: upsOutletGroupStatusIndex
  71. type: gauge
  72. lookups:
  73. - labels:
  74. - upsOutletGroupStatusIndex
  75. labelname: upsOutletGroupStatusName
  76. oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.2
  77. type: DisplayString
  78. - labels: []
  79. labelname: upsOutletGroupStatusIndex
  80. enum_values:
  81. 1: upsOutletGroupStatusOn
  82. 2: upsOutletGroupStatusOff
  83. 3: upsOutletGroupStatusUnknown
  84. - name: upsOutletGroupStatusCommandPending
  85. oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.4
  86. type: gauge
  87. help: Getting this variable will return the command pending state of the outlet
  88. group - 1.3.6.1.4.1.318.1.1.1.12.1.2.1.4
  89. indexes:
  90. - labelname: upsOutletGroupStatusIndex
  91. type: gauge
  92. lookups:
  93. - labels:
  94. - upsOutletGroupStatusIndex
  95. labelname: upsOutletGroupStatusName
  96. oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.2
  97. type: DisplayString
  98. - labels: []
  99. labelname: upsOutletGroupStatusIndex
  100. enum_values:
  101. 1: upsOutletGroupCommandPending
  102. 2: upsOutletGroupNoCommandPending
  103. - name: upsOutletGroupStatusOutletType
  104. oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.5
  105. type: gauge
  106. help: Getting this variable will return the type of outlet group - 1.3.6.1.4.1.318.1.1.1.12.1.2.1.5
  107. indexes:
  108. - labelname: upsOutletGroupStatusIndex
  109. type: gauge
  110. lookups:
  111. - labels:
  112. - upsOutletGroupStatusIndex
  113. labelname: upsOutletGroupStatusName
  114. oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.2
  115. type: DisplayString
  116. - labels: []
  117. labelname: upsOutletGroupStatusIndex
  118. enum_values:
  119. 1: upsSwitchedOutletGroup
  120. 2: upsMainOutletGroup
  121. - name: upsOutletGroupStatusGroupFullState
  122. oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.6
  123. type: DisplayString
  124. help: An ASCII string containing the 32 flags representing the current state(s)
  125. of the outlet group - 1.3.6.1.4.1.318.1.1.1.12.1.2.1.6
  126. indexes:
  127. - labelname: upsOutletGroupStatusIndex
  128. type: gauge
  129. lookups:
  130. - labels:
  131. - upsOutletGroupStatusIndex
  132. labelname: upsOutletGroupStatusName
  133. oid: 1.3.6.1.4.1.318.1.1.1.12.1.2.1.2
  134. type: DisplayString
  135. - labels: []
  136. labelname: upsOutletGroupStatusIndex
  137. - name: upsOutletGroupConfigTableSize
  138. oid: 1.3.6.1.4.1.318.1.1.1.12.2.1
  139. type: gauge
  140. help: The number of outlet groups for the UPS. - 1.3.6.1.4.1.318.1.1.1.12.2.1
  141. - name: upsOutletGroupConfigIndex
  142. oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.1
  143. type: gauge
  144. help: The index to the outlet group entry. - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.1
  145. indexes:
  146. - labelname: upsOutletGroupConfigIndex
  147. type: gauge
  148. - name: upsOutletGroupConfigName
  149. oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.2
  150. type: DisplayString
  151. help: The name of the outlet group. - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.2
  152. indexes:
  153. - labelname: upsOutletGroupConfigIndex
  154. type: gauge
  155. - name: upsOutletGroupConfigPowerOnDelay
  156. oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.3
  157. type: gauge
  158. help: The amount of time (seconds) the outlet group will delay powering on when
  159. the delayed on, reboot, or shutdown command is applied - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.3
  160. indexes:
  161. - labelname: upsOutletGroupConfigIndex
  162. type: gauge
  163. - name: upsOutletGroupConfigPowerOffDelay
  164. oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.4
  165. type: gauge
  166. help: The amount of time (seconds) the outlet group will delay powering off
  167. when the delayed off, reboot, or shutdown command is applied - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.4
  168. indexes:
  169. - labelname: upsOutletGroupConfigIndex
  170. type: gauge
  171. - name: upsOutletGroupConfigRebootDuration
  172. oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.5
  173. type: gauge
  174. help: During a reboot sequence, power is turned off and then back on - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.5
  175. indexes:
  176. - labelname: upsOutletGroupConfigIndex
  177. type: gauge
  178. - name: upsOutletGroupConfigMinReturnRuntime
  179. oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.6
  180. type: gauge
  181. help: In an Outlet Group shutdown sequence, the Outlet Group cycles power off
  182. then on - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.6
  183. indexes:
  184. - labelname: upsOutletGroupConfigIndex
  185. type: gauge
  186. - name: upsOutletGroupConfigOutletType
  187. oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.7
  188. type: gauge
  189. help: Getting this variable will return the type of outlet group - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.7
  190. indexes:
  191. - labelname: upsOutletGroupConfigIndex
  192. type: gauge
  193. enum_values:
  194. 1: upsSwitchedOutletGroup
  195. 2: upsMainOutletGroup
  196. - name: upsOutletGroupConfigLoadShedControlSkipOffDelay
  197. oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.8
  198. type: gauge
  199. help: Configures whether the outlet group's off delay setting (upsOutletGroupConfigPowerOffDelay)
  200. will be used in a load shedding situation, where applicable. - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.8
  201. indexes:
  202. - labelname: upsOutletGroupConfigIndex
  203. type: gauge
  204. enum_values:
  205. 1: upsOutletGroupConfigSkipOffDelay
  206. 2: upsOutletGroupConfigUseOffDelay
  207. - name: upsOutletGroupConfigLoadShedControlAutoRestart
  208. oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.9
  209. type: gauge
  210. help: Configures whether the outlet group will automatically restart after a
  211. load shedding situation, where applicable. - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.9
  212. indexes:
  213. - labelname: upsOutletGroupConfigIndex
  214. type: gauge
  215. enum_values:
  216. 1: upsOutletGroupConfigAutoRestart
  217. 2: upsOutletGroupConfigManualRestart
  218. - name: upsOutletGroupConfigLoadShedControlTimeOnBattery
  219. oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.10
  220. type: gauge
  221. help: Configures whether the outlet group will load shed (turn off) after the
  222. UPS device's time on battery has exceeded the upsOutletGroupConfigLoadShedTimeOnBattery
  223. OID setting - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.10
  224. indexes:
  225. - labelname: upsOutletGroupConfigIndex
  226. type: gauge
  227. enum_values:
  228. 1: upsOutletGroupConfigDisableTimeOnBatteryLoadShed
  229. 2: upsOutletGroupConfigEnableTimeOnBatteryLoadShed
  230. - name: upsOutletGroupConfigLoadShedControlRuntimeRemaining
  231. oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.11
  232. type: gauge
  233. help: Configures whether the outlet group will load shed (turn off) when the
  234. UPS is on battery and the remaining runtime is less than the upsOutletGroupConfigLoadShedRuntimeRemaining
  235. OID setting - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.11
  236. indexes:
  237. - labelname: upsOutletGroupConfigIndex
  238. type: gauge
  239. enum_values:
  240. 1: upsOutletGroupConfigDisableRuntimeRemainingLoadShed
  241. 2: upsOutletGroupConfigEnableRuntimeRemainingLoadShed
  242. - name: upsOutletGroupConfigLoadShedControlInOverload
  243. oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.12
  244. type: gauge
  245. help: Configures whether the outlet group will load shed (turn off) when the
  246. UPS is in an overload condition - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.12
  247. indexes:
  248. - labelname: upsOutletGroupConfigIndex
  249. type: gauge
  250. enum_values:
  251. 1: upsOutletGroupConfigDisableInOverloadLoadShed
  252. 2: upsOutletGroupConfigEnableInOverloadLoadShed
  253. - name: upsOutletGroupConfigLoadShedTimeOnBattery
  254. oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.13
  255. type: gauge
  256. help: When the UPS has been on battery for more time than this value, the outlet
  257. group will turn off if this condition is enabled by the upsOutletGroupConfigLoadShedControlTimeOnBattery
  258. OID - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.13
  259. indexes:
  260. - labelname: upsOutletGroupConfigIndex
  261. type: gauge
  262. - name: upsOutletGroupConfigLoadShedRuntimeRemaining
  263. oid: 1.3.6.1.4.1.318.1.1.1.12.2.2.1.14
  264. type: gauge
  265. help: When the runtime remaining is less than this value, the outlet group will
  266. turn off if this condition is enabled by the upsOutletGroupConfigLoadShedControlRuntimeRemaining
  267. OID - 1.3.6.1.4.1.318.1.1.1.12.2.2.1.14
  268. indexes:
  269. - labelname: upsOutletGroupConfigIndex
  270. type: gauge
  271. - name: upsOutletGroupControlTableSize
  272. oid: 1.3.6.1.4.1.318.1.1.1.12.3.1
  273. type: gauge
  274. help: The number of outlet groups for the UPS. - 1.3.6.1.4.1.318.1.1.1.12.3.1
  275. - name: upsOutletGroupControlIndex
  276. oid: 1.3.6.1.4.1.318.1.1.1.12.3.2.1.1
  277. type: gauge
  278. help: The index to the outlet group entry. - 1.3.6.1.4.1.318.1.1.1.12.3.2.1.1
  279. indexes:
  280. - labelname: upsOutletGroupControlIndex
  281. type: gauge
  282. - name: upsOutletGroupControlName
  283. oid: 1.3.6.1.4.1.318.1.1.1.12.3.2.1.2
  284. type: DisplayString
  285. help: The name of the outlet group - 1.3.6.1.4.1.318.1.1.1.12.3.2.1.2
  286. indexes:
  287. - labelname: upsOutletGroupControlIndex
  288. type: gauge
  289. - name: upsOutletGroupControlCommand
  290. oid: 1.3.6.1.4.1.318.1.1.1.12.3.2.1.3
  291. type: gauge
  292. help: Getting this variable will return the outlet group state - 1.3.6.1.4.1.318.1.1.1.12.3.2.1.3
  293. indexes:
  294. - labelname: upsOutletGroupControlIndex
  295. type: gauge
  296. enum_values:
  297. 1: upsOutletGroupImmediateOn
  298. 2: upsOutletGroupImmediateOff
  299. 3: upsOutletGroupImmediateRebootWithOrWithoutAC
  300. 4: upsOutletGroupDelayedOn
  301. 5: upsOutletGroupDelayedOff
  302. 6: upsOutletGroupDelayedRebootWithOrWithoutAC
  303. 7: upsOutletGroupCancelPendingCommand
  304. 8: upsOutletGroupControlUnknown
  305. 9: upsOutletGroupImmediateRebootShutdown
  306. 10: upsOutletGroupDelayedRebootShutdown
  307. - name: upsOutletGroupControlOutletType
  308. oid: 1.3.6.1.4.1.318.1.1.1.12.3.2.1.4
  309. type: gauge
  310. help: Getting this variable will return the type of outlet group - 1.3.6.1.4.1.318.1.1.1.12.3.2.1.4
  311. indexes:
  312. - labelname: upsOutletGroupControlIndex
  313. type: gauge
  314. enum_values:
  315. 1: upsSwitchedOutletGroup
  316. 2: upsMainOutletGroup
  317. - name: upsBasicBatteryStatus
  318. oid: 1.3.6.1.4.1.318.1.1.1.2.1.1
  319. type: gauge
  320. help: The status of the UPS batteries - 1.3.6.1.4.1.318.1.1.1.2.1.1
  321. enum_values:
  322. 1: unknown
  323. 2: batteryNormal
  324. 3: batteryLow
  325. 4: batteryInFaultCondition
  326. 5: noBatteryPresent
  327. - name: upsBasicBatteryTimeOnBattery
  328. oid: 1.3.6.1.4.1.318.1.1.1.2.1.2
  329. type: gauge
  330. help: The elapsed time since the UPS has switched to battery power. - 1.3.6.1.4.1.318.1.1.1.2.1.2
  331. - name: upsBasicBatteryLastReplaceDate
  332. oid: 1.3.6.1.4.1.318.1.1.1.2.1.3
  333. type: DisplayString
  334. help: The date when the UPS system's batteries were last replaced in mm/dd/yy
  335. (or yyyy) format - 1.3.6.1.4.1.318.1.1.1.2.1.3
  336. - name: upsAdvBatteryCapacity
  337. oid: 1.3.6.1.4.1.318.1.1.1.2.2.1
  338. type: gauge
  339. help: The remaining battery capacity expressed in percent of full capacity -
  340. 1.3.6.1.4.1.318.1.1.1.2.2.1
  341. - name: upsAdvBatteryTemperature
  342. oid: 1.3.6.1.4.1.318.1.1.1.2.2.2
  343. type: gauge
  344. help: The current internal UPS temperature expressed in Celsius - 1.3.6.1.4.1.318.1.1.1.2.2.2
  345. - name: upsAdvBatteryRunTimeRemaining
  346. oid: 1.3.6.1.4.1.318.1.1.1.2.2.3
  347. type: gauge
  348. help: The UPS battery run time remaining before battery exhaustion. - 1.3.6.1.4.1.318.1.1.1.2.2.3
  349. - name: upsAdvBatteryReplaceIndicator
  350. oid: 1.3.6.1.4.1.318.1.1.1.2.2.4
  351. type: gauge
  352. help: Indicates whether the UPS batteries need replacing. - 1.3.6.1.4.1.318.1.1.1.2.2.4
  353. enum_values:
  354. 1: noBatteryNeedsReplacing
  355. 2: batteryNeedsReplacing
  356. - name: upsAdvBatteryNumOfBattPacks
  357. oid: 1.3.6.1.4.1.318.1.1.1.2.2.5
  358. type: gauge
  359. help: The number of external battery packs connected to the UPS - 1.3.6.1.4.1.318.1.1.1.2.2.5
  360. - name: upsAdvBatteryNumOfBadBattPacks
  361. oid: 1.3.6.1.4.1.318.1.1.1.2.2.6
  362. type: gauge
  363. help: The number of external battery packs connected to the UPS that are defective
  364. - 1.3.6.1.4.1.318.1.1.1.2.2.6
  365. - name: upsAdvBatteryNominalVoltage
  366. oid: 1.3.6.1.4.1.318.1.1.1.2.2.7
  367. type: gauge
  368. help: The nominal battery voltage in Volts. - 1.3.6.1.4.1.318.1.1.1.2.2.7
  369. - name: upsAdvBatteryActualVoltage
  370. oid: 1.3.6.1.4.1.318.1.1.1.2.2.8
  371. type: gauge
  372. help: The actual battery bus voltage in Volts - 1.3.6.1.4.1.318.1.1.1.2.2.8
  373. - name: upsAdvBatteryCurrent
  374. oid: 1.3.6.1.4.1.318.1.1.1.2.2.9
  375. type: gauge
  376. help: The battery current in Amps - 1.3.6.1.4.1.318.1.1.1.2.2.9
  377. - name: upsAdvTotalDCCurrent
  378. oid: 1.3.6.1.4.1.318.1.1.1.2.2.10
  379. type: gauge
  380. help: The total DC current in Amps. - 1.3.6.1.4.1.318.1.1.1.2.2.10
  381. - name: upsAdvBatteryFullCapacity
  382. oid: 1.3.6.1.4.1.318.1.1.1.2.2.11
  383. type: gauge
  384. help: The full chargeable capacity of the battery which is expressed in percentage.
  385. - 1.3.6.1.4.1.318.1.1.1.2.2.11
  386. - name: upsAdvBatteryActualVoltageTableIndex
  387. oid: 1.3.6.1.4.1.318.1.1.1.2.2.12.1.1
  388. type: gauge
  389. help: The Battery Frame identifier - 1.3.6.1.4.1.318.1.1.1.2.2.12.1.1
  390. indexes:
  391. - labelname: upsAdvBatteryActualVoltageTableIndex
  392. type: gauge
  393. - name: upsAdvBatteryActualVoltagePolarity
  394. oid: 1.3.6.1.4.1.318.1.1.1.2.2.12.1.2
  395. type: gauge
  396. help: The selected Battery Voltage Polarity - 1.3.6.1.4.1.318.1.1.1.2.2.12.1.2
  397. indexes:
  398. - labelname: upsAdvBatteryActualVoltageTableIndex
  399. type: gauge
  400. enum_values:
  401. 0: positive
  402. 1: negative
  403. - name: upsAdvBatteryFrameActualVoltage
  404. oid: 1.3.6.1.4.1.318.1.1.1.2.2.12.1.3
  405. type: gauge
  406. help: The actual battery bus voltage in Volts. - 1.3.6.1.4.1.318.1.1.1.2.2.12.1.3
  407. indexes:
  408. - labelname: upsAdvBatteryActualVoltageTableIndex
  409. type: gauge
  410. - name: upsAdvTotalDCCurrentTableIndex
  411. oid: 1.3.6.1.4.1.318.1.1.1.2.2.13.1.1
  412. type: gauge
  413. help: The Battery Frame identifier - 1.3.6.1.4.1.318.1.1.1.2.2.13.1.1
  414. indexes:
  415. - labelname: upsAdvTotalDCCurrentTableIndex
  416. type: gauge
  417. - name: upsAdvTotalDCCurrentPolarity
  418. oid: 1.3.6.1.4.1.318.1.1.1.2.2.13.1.2
  419. type: gauge
  420. help: The selected Battery Current Polarity - 1.3.6.1.4.1.318.1.1.1.2.2.13.1.2
  421. indexes:
  422. - labelname: upsAdvTotalDCCurrentTableIndex
  423. type: gauge
  424. enum_values:
  425. 0: positive
  426. 1: negative
  427. - name: upsAdvTotalFrameDCCurrent
  428. oid: 1.3.6.1.4.1.318.1.1.1.2.2.13.1.3
  429. type: gauge
  430. help: The Total DC Current of battery in Amperes. - 1.3.6.1.4.1.318.1.1.1.2.2.13.1.3
  431. indexes:
  432. - labelname: upsAdvTotalDCCurrentTableIndex
  433. type: gauge
  434. - name: upsAdvBatteryCurrentTableIndex
  435. oid: 1.3.6.1.4.1.318.1.1.1.2.2.14.1.1
  436. type: gauge
  437. help: The Battery Frame identifier - 1.3.6.1.4.1.318.1.1.1.2.2.14.1.1
  438. indexes:
  439. - labelname: upsAdvBatteryCurrentTableIndex
  440. type: gauge
  441. - labelname: upsAdvBatteryCurrentIndex
  442. type: gauge
  443. - name: upsAdvBatteryCurrentIndex
  444. oid: 1.3.6.1.4.1.318.1.1.1.2.2.14.1.2
  445. type: gauge
  446. help: The battery frame identifier. - 1.3.6.1.4.1.318.1.1.1.2.2.14.1.2
  447. indexes:
  448. - labelname: upsAdvBatteryCurrentTableIndex
  449. type: gauge
  450. - labelname: upsAdvBatteryCurrentIndex
  451. type: gauge
  452. - name: upsAdvBatteryCurrentPolarity
  453. oid: 1.3.6.1.4.1.318.1.1.1.2.2.14.1.3
  454. type: gauge
  455. help: The selected Battery current polarity - 1.3.6.1.4.1.318.1.1.1.2.2.14.1.3
  456. indexes:
  457. - labelname: upsAdvBatteryCurrentTableIndex
  458. type: gauge
  459. - labelname: upsAdvBatteryCurrentIndex
  460. type: gauge
  461. enum_values:
  462. 0: positive
  463. 1: negative
  464. - name: upsAdvBatteryFrameCurrent
  465. oid: 1.3.6.1.4.1.318.1.1.1.2.2.14.1.4
  466. type: gauge
  467. help: The Battery current measured in Amperes - 1.3.6.1.4.1.318.1.1.1.2.2.14.1.4
  468. indexes:
  469. - labelname: upsAdvBatteryCurrentTableIndex
  470. type: gauge
  471. - labelname: upsAdvBatteryCurrentIndex
  472. type: gauge
  473. - name: upsAdvBatteryEstimatedChargeTime
  474. oid: 1.3.6.1.4.1.318.1.1.1.2.2.15
  475. type: gauge
  476. help: The estimated remaining time required to charge the UPS to a full state
  477. of charge. - 1.3.6.1.4.1.318.1.1.1.2.2.15
  478. - name: upsAdvBatteryPower
  479. oid: 1.3.6.1.4.1.318.1.1.1.2.2.16
  480. type: gauge
  481. help: The measured battery power in kW. - 1.3.6.1.4.1.318.1.1.1.2.2.16
  482. - name: upsAdvBatteryChargerStatus
  483. oid: 1.3.6.1.4.1.318.1.1.1.2.2.17
  484. type: EnumAsStateSet
  485. help: The status of the battery charger - 1.3.6.1.4.1.318.1.1.1.2.2.17
  486. enum_values:
  487. 1: unknown
  488. 2: ok
  489. 3: inFaultCondition
  490. 4: floatCharging
  491. 5: boostCharging
  492. 6: resting
  493. 7: notCharging
  494. 8: equalizationCharging
  495. 9: testInProgress
  496. 10: cyclicFloatCharging
  497. - name: upsAdvBatteryInternalSKU
  498. oid: 1.3.6.1.4.1.318.1.1.1.2.2.19
  499. type: DisplayString
  500. help: The SKU of the internal battery. - 1.3.6.1.4.1.318.1.1.1.2.2.19
  501. - name: upsAdvBatteryExternalSKU
  502. oid: 1.3.6.1.4.1.318.1.1.1.2.2.20
  503. type: DisplayString
  504. help: The SKU of the external battery. - 1.3.6.1.4.1.318.1.1.1.2.2.20
  505. - name: upsAdvBatteryRecommendedReplaceDate
  506. oid: 1.3.6.1.4.1.318.1.1.1.2.2.21
  507. type: DisplayString
  508. help: The recommended replacement date for the battery based on the UPS internal
  509. battery life algorithm. - 1.3.6.1.4.1.318.1.1.1.2.2.21
  510. - name: upsAdvBatteryNominalBackupTime
  511. oid: 1.3.6.1.4.1.318.1.1.1.2.2.22
  512. type: gauge
  513. help: Defines the runtime of the user supplied battery in minutes, when battery
  514. is new. - 1.3.6.1.4.1.318.1.1.1.2.2.22
  515. - name: upsAdvBatteryCondition
  516. oid: 1.3.6.1.4.1.318.1.1.1.2.2.23
  517. type: EnumAsStateSet
  518. help: Health of the battries based on the battery test. - 1.3.6.1.4.1.318.1.1.1.2.2.23
  519. enum_values:
  520. 1: unknown
  521. 2: ok
  522. 3: weak
  523. 4: poor
  524. - name: upsAdvBatteryChargingCurrentRestricted
  525. oid: 1.3.6.1.4.1.318.1.1.1.2.2.24
  526. type: EnumAsStateSet
  527. help: Indicates whether battery charging current is restricted or not - 1.3.6.1.4.1.318.1.1.1.2.2.24
  528. enum_values:
  529. 1: "yes"
  530. 2: "no"
  531. - name: upsAdvBatteryTotalCapacity
  532. oid: 1.3.6.1.4.1.318.1.1.1.2.2.25
  533. type: gauge
  534. help: The actual available battery capacity of the system expressed in ampere
  535. hours (Ah) - 1.3.6.1.4.1.318.1.1.1.2.2.25
  536. - name: upsAdvBatteryFuseStatus
  537. oid: 1.3.6.1.4.1.318.1.1.1.2.2.26
  538. type: gauge
  539. help: If battery system has one common fuse for the battery system, the status
  540. is given by this value - 1.3.6.1.4.1.318.1.1.1.2.2.26
  541. enum_values:
  542. 1: fuseOpen
  543. 2: fuseOk
  544. 3: notPresent
  545. - name: upsAdvBatteryBreakerStatus
  546. oid: 1.3.6.1.4.1.318.1.1.1.2.2.27
  547. type: gauge
  548. help: The value indicates the aggregated status of the battery breakers in the
  549. system - 1.3.6.1.4.1.318.1.1.1.2.2.27
  550. enum_values:
  551. 1: disconnected
  552. 2: closed
  553. 3: notPresent
  554. - name: upsAdvBatteryWiringConfiguration
  555. oid: 1.3.6.1.4.1.318.1.1.1.2.2.28
  556. type: gauge
  557. help: The value indicates the wiring configuration, whether the battery is 2-wire
  558. or 3-wire - 1.3.6.1.4.1.318.1.1.1.2.2.28
  559. enum_values:
  560. 1: twoWire
  561. 2: threeWire
  562. - name: upsHighPrecBatteryCapacity
  563. oid: 1.3.6.1.4.1.318.1.1.1.2.3.1
  564. type: gauge
  565. help: The remaining battery capacity expressed in tenths of percent of full
  566. capacity. - 1.3.6.1.4.1.318.1.1.1.2.3.1
  567. - name: upsHighPrecBatteryTemperature
  568. oid: 1.3.6.1.4.1.318.1.1.1.2.3.2
  569. type: gauge
  570. help: The current internal UPS temperature expressed in tenths of degrees Celsius
  571. - 1.3.6.1.4.1.318.1.1.1.2.3.2
  572. - name: upsHighPrecBatteryNominalVoltage
  573. oid: 1.3.6.1.4.1.318.1.1.1.2.3.3
  574. type: gauge
  575. help: The nominal battery voltage in tenths of Volts. - 1.3.6.1.4.1.318.1.1.1.2.3.3
  576. - name: upsHighPrecBatteryActualVoltage
  577. oid: 1.3.6.1.4.1.318.1.1.1.2.3.4
  578. type: gauge
  579. help: The actual battery bus voltage in tenths of Volts. - 1.3.6.1.4.1.318.1.1.1.2.3.4
  580. - name: upsHighPrecBatteryCurrent
  581. oid: 1.3.6.1.4.1.318.1.1.1.2.3.5
  582. type: gauge
  583. help: The battery current in tenths of Amps - 1.3.6.1.4.1.318.1.1.1.2.3.5
  584. - name: upsHighPrecTotalDCCurrent
  585. oid: 1.3.6.1.4.1.318.1.1.1.2.3.6
  586. type: gauge
  587. help: The total DC current in tenths of Amps. - 1.3.6.1.4.1.318.1.1.1.2.3.6
  588. - name: upsHighPrecBatteryActualVoltageTableIndex
  589. oid: 1.3.6.1.4.1.318.1.1.1.2.3.7.1.1
  590. type: gauge
  591. help: The Battery Frame identifier - 1.3.6.1.4.1.318.1.1.1.2.3.7.1.1
  592. indexes:
  593. - labelname: upsHighPrecBatteryActualVoltageTableIndex
  594. type: gauge
  595. - name: upsHighPrecBatteryActualVoltagePolarity
  596. oid: 1.3.6.1.4.1.318.1.1.1.2.3.7.1.2
  597. type: gauge
  598. help: The selected Battery Voltage polarity - 1.3.6.1.4.1.318.1.1.1.2.3.7.1.2
  599. indexes:
  600. - labelname: upsHighPrecBatteryActualVoltageTableIndex
  601. type: gauge
  602. enum_values:
  603. 0: positive
  604. 1: negative
  605. - name: upsHighPrecBatteryVoltage
  606. oid: 1.3.6.1.4.1.318.1.1.1.2.3.7.1.3
  607. type: gauge
  608. help: The actual battery bus voltage expressed as tenths of Volts - 1.3.6.1.4.1.318.1.1.1.2.3.7.1.3
  609. indexes:
  610. - labelname: upsHighPrecBatteryActualVoltageTableIndex
  611. type: gauge
  612. - name: upsHighPrecTotalDCCurrentTableIndex
  613. oid: 1.3.6.1.4.1.318.1.1.1.2.3.8.1.1
  614. type: gauge
  615. help: The Battery Frame identifier - 1.3.6.1.4.1.318.1.1.1.2.3.8.1.1
  616. indexes:
  617. - labelname: upsHighPrecTotalDCCurrentTableIndex
  618. type: gauge
  619. - name: upsHighPrecTotalDCCurrentPolarity
  620. oid: 1.3.6.1.4.1.318.1.1.1.2.3.8.1.2
  621. type: gauge
  622. help: The selected Battery Current polarity - 1.3.6.1.4.1.318.1.1.1.2.3.8.1.2
  623. indexes:
  624. - labelname: upsHighPrecTotalDCCurrentTableIndex
  625. type: gauge
  626. enum_values:
  627. 0: positive
  628. 1: negative
  629. - name: upsHighPrecTotalDCFrameCurrent
  630. oid: 1.3.6.1.4.1.318.1.1.1.2.3.8.1.3
  631. type: gauge
  632. help: The total DC current in tenths of Amperes. - 1.3.6.1.4.1.318.1.1.1.2.3.8.1.3
  633. indexes:
  634. - labelname: upsHighPrecTotalDCCurrentTableIndex
  635. type: gauge
  636. - name: upsHighPrecBatteryCurrentTableIndex
  637. oid: 1.3.6.1.4.1.318.1.1.1.2.3.9.1.1
  638. type: gauge
  639. help: The Battery frame identifier - 1.3.6.1.4.1.318.1.1.1.2.3.9.1.1
  640. indexes:
  641. - labelname: upsHighPrecBatteryCurrentTableIndex
  642. type: gauge
  643. - labelname: upsHighPrecBatteryCurrentIndex
  644. type: gauge
  645. - name: upsHighPrecBatteryCurrentIndex
  646. oid: 1.3.6.1.4.1.318.1.1.1.2.3.9.1.2
  647. type: gauge
  648. help: The Battery frame identifier - 1.3.6.1.4.1.318.1.1.1.2.3.9.1.2
  649. indexes:
  650. - labelname: upsHighPrecBatteryCurrentTableIndex
  651. type: gauge
  652. - labelname: upsHighPrecBatteryCurrentIndex
  653. type: gauge
  654. - name: upsHighPrecBatteryCurrentPolarity
  655. oid: 1.3.6.1.4.1.318.1.1.1.2.3.9.1.3
  656. type: gauge
  657. help: The selected Battery Current polarity - 1.3.6.1.4.1.318.1.1.1.2.3.9.1.3
  658. indexes:
  659. - labelname: upsHighPrecBatteryCurrentTableIndex
  660. type: gauge
  661. - labelname: upsHighPrecBatteryCurrentIndex
  662. type: gauge
  663. enum_values:
  664. 0: positive
  665. 1: negative
  666. - name: upsHighPrecBatteryFrameCurrent
  667. oid: 1.3.6.1.4.1.318.1.1.1.2.3.9.1.4
  668. type: gauge
  669. help: The Battery current in tenths of Amperes. - 1.3.6.1.4.1.318.1.1.1.2.3.9.1.4
  670. indexes:
  671. - labelname: upsHighPrecBatteryCurrentTableIndex
  672. type: gauge
  673. - labelname: upsHighPrecBatteryCurrentIndex
  674. type: gauge
  675. - name: upsHighPrecBatteryPackTableSize
  676. oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.1
  677. type: gauge
  678. help: The number of entries in the upsHighPrecBatteryPacks. - 1.3.6.1.4.1.318.1.1.1.2.3.10.1
  679. - name: upsHighPrecBatteryPackIndex
  680. oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.1
  681. type: gauge
  682. help: The battery pack identifier. - 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.1
  683. indexes:
  684. - labelname: upsHighPrecBatteryPackIndex
  685. type: gauge
  686. - labelname: upsHighPrecBatteryCartridgeIndex
  687. type: gauge
  688. - name: upsHighPrecBatteryCartridgeIndex
  689. oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.2
  690. type: gauge
  691. help: The battery cartridge identifier. - 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.2
  692. indexes:
  693. - labelname: upsHighPrecBatteryPackIndex
  694. type: gauge
  695. - labelname: upsHighPrecBatteryCartridgeIndex
  696. type: gauge
  697. - name: upsHighPrecBatteryPackFirmwareRevision
  698. oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.3
  699. type: DisplayString
  700. help: The battery pack firmware revision. - 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.3
  701. indexes:
  702. - labelname: upsHighPrecBatteryPackIndex
  703. type: gauge
  704. - labelname: upsHighPrecBatteryCartridgeIndex
  705. type: gauge
  706. - name: upsHighPrecBatteryPackSerialNumber
  707. oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.4
  708. type: DisplayString
  709. help: The battery pack serial number. - 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.4
  710. indexes:
  711. - labelname: upsHighPrecBatteryPackIndex
  712. type: gauge
  713. - labelname: upsHighPrecBatteryCartridgeIndex
  714. type: gauge
  715. - name: upsHighPrecBatteryPackTemperature
  716. oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.5
  717. type: gauge
  718. help: The battery pack temperature measured in 10ths of degree Celcius - 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.5
  719. indexes:
  720. - labelname: upsHighPrecBatteryPackIndex
  721. type: gauge
  722. - labelname: upsHighPrecBatteryCartridgeIndex
  723. type: gauge
  724. - name: upsHighPrecBatteryPackStatus
  725. oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.6
  726. type: OctetString
  727. help: The battery status for the pack only - 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.6
  728. indexes:
  729. - labelname: upsHighPrecBatteryPackIndex
  730. type: gauge
  731. - labelname: upsHighPrecBatteryCartridgeIndex
  732. type: gauge
  733. - name: upsHighPrecBatteryPackCartridgeHealth
  734. oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7
  735. type: OctetString
  736. help: The battery cartridge health - 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7
  737. indexes:
  738. - labelname: upsHighPrecBatteryPackIndex
  739. type: gauge
  740. - labelname: upsHighPrecBatteryCartridgeIndex
  741. type: gauge
  742. - name: upsHighPrecBatteryPackCartridgeReplaceDate
  743. oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8
  744. type: DisplayString
  745. help: The battery cartridge estimated battery replace date. - 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8
  746. indexes:
  747. - labelname: upsHighPrecBatteryPackIndex
  748. type: gauge
  749. - labelname: upsHighPrecBatteryCartridgeIndex
  750. type: gauge
  751. - name: upsHighPrecBatteryPackCartridgeInstallDate
  752. oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.9
  753. type: DisplayString
  754. help: The battery cartridge install date. - 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.9
  755. indexes:
  756. - labelname: upsHighPrecBatteryPackIndex
  757. type: gauge
  758. - labelname: upsHighPrecBatteryCartridgeIndex
  759. type: gauge
  760. - name: upsHighPrecBatteryPackCartridgeStatus
  761. oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.10
  762. type: OctetString
  763. help: The battery cartridge status - 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.10
  764. indexes:
  765. - labelname: upsHighPrecBatteryPackIndex
  766. type: gauge
  767. - labelname: upsHighPrecBatteryCartridgeIndex
  768. type: gauge
  769. - name: upsHighPrecBatteryPackOnlyTableSize
  770. oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.3
  771. type: gauge
  772. help: The number of entries in the upsHighPrecBatteryPacks. - 1.3.6.1.4.1.318.1.1.1.2.3.10.3
  773. - name: upsHighPrecBatteryPackOnlyIndex
  774. oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.1
  775. type: gauge
  776. help: The battery pack identifier. - 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.1
  777. indexes:
  778. - labelname: upsHighPrecBatteryPackOnlyIndex
  779. type: gauge
  780. - name: upsHighPrecBatteryPackOnlyFirmwareRevision
  781. oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.2
  782. type: DisplayString
  783. help: The battery pack firmware revision. - 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.2
  784. indexes:
  785. - labelname: upsHighPrecBatteryPackOnlyIndex
  786. type: gauge
  787. - name: upsHighPrecBatteryPackOnlySerialNumber
  788. oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.3
  789. type: DisplayString
  790. help: The battery pack serial number. - 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.3
  791. indexes:
  792. - labelname: upsHighPrecBatteryPackOnlyIndex
  793. type: gauge
  794. - name: upsHighPrecBatteryPackOnlyTemperature
  795. oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.4
  796. type: gauge
  797. help: The battery pack temperature measured in 10ths of degree Celcius - 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.4
  798. indexes:
  799. - labelname: upsHighPrecBatteryPackOnlyIndex
  800. type: gauge
  801. - name: upsHighPrecBatteryPackOnlyStatus
  802. oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.5
  803. type: OctetString
  804. help: The battery status for the pack only - 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.5
  805. indexes:
  806. - labelname: upsHighPrecBatteryPackOnlyIndex
  807. type: gauge
  808. - name: upsHighPrecBatteryPackOnlyHealth
  809. oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.6
  810. type: OctetString
  811. help: The battery pack health - 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.6
  812. indexes:
  813. - labelname: upsHighPrecBatteryPackOnlyIndex
  814. type: gauge
  815. - name: upsHighPrecBatteryPackOnlyReplaceDate
  816. oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.7
  817. type: DisplayString
  818. help: The battery pack estimated battery replace date. - 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.7
  819. indexes:
  820. - labelname: upsHighPrecBatteryPackOnlyIndex
  821. type: gauge
  822. - name: upsHighPrecBatteryPackOnlyInstallDate
  823. oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.8
  824. type: DisplayString
  825. help: The battery pack install date. - 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.8
  826. indexes:
  827. - labelname: upsHighPrecBatteryPackOnlyIndex
  828. type: gauge
  829. - name: upsHighPrecBatteryPackOnlyManufactureDate
  830. oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.9
  831. type: DisplayString
  832. help: The battery pack manufacture date. - 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.9
  833. indexes:
  834. - labelname: upsHighPrecBatteryPackOnlyIndex
  835. type: gauge
  836. - name: upsHighPrecBatteryPackOnlySKU
  837. oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.10
  838. type: DisplayString
  839. help: The battery pack SKU. - 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.10
  840. indexes:
  841. - labelname: upsHighPrecBatteryPackOnlyIndex
  842. type: gauge
  843. - name: upsHighPrecBatteryHealth
  844. oid: 1.3.6.1.4.1.318.1.1.1.2.3.11
  845. type: OctetString
  846. help: The battery health - 1.3.6.1.4.1.318.1.1.1.2.3.11
  847. - name: upsHighPrecActivePower
  848. oid: 1.3.6.1.4.1.318.1.1.1.2.3.12
  849. type: gauge
  850. help: Active Power of Battery in tenths of kW - 1.3.6.1.4.1.318.1.1.1.2.3.12
  851. - name: upsHighPrecExtdBatteryTemperature
  852. oid: 1.3.6.1.4.1.318.1.1.1.2.3.13
  853. type: gauge
  854. help: The current internal UPS temperature expressed in tenths of degrees Celsius
  855. - 1.3.6.1.4.1.318.1.1.1.2.3.13
  856. - name: upsHighPrecMaximumModuleTemperature
  857. oid: 1.3.6.1.4.1.318.1.1.1.2.3.14
  858. type: gauge
  859. help: The current maximum temperature across all battery modules in tenths of
  860. degrees Celsius - 1.3.6.1.4.1.318.1.1.1.2.3.14
  861. - name: upsHighPrecMinimumModuleTemperature
  862. oid: 1.3.6.1.4.1.318.1.1.1.2.3.15
  863. type: gauge
  864. help: The current minimum temperature across all battery modules in tenths of
  865. degrees Celsius - 1.3.6.1.4.1.318.1.1.1.2.3.15
  866. - name: upsHighPrecMaximumCellVoltage
  867. oid: 1.3.6.1.4.1.318.1.1.1.2.3.16
  868. type: gauge
  869. help: The current maximum cell voltage in mVDC across all batteries. - 1.3.6.1.4.1.318.1.1.1.2.3.16
  870. - name: upsHighPrecMinimumCellVoltage
  871. oid: 1.3.6.1.4.1.318.1.1.1.2.3.17
  872. type: gauge
  873. help: The current minimum cell voltage in mVDC across all batteries. - 1.3.6.1.4.1.318.1.1.1.2.3.17
  874. - name: upsBatteryNumberOfCabinets
  875. oid: 1.3.6.1.4.1.318.1.1.1.2.4
  876. type: gauge
  877. help: The value indicates the number of battery cabinets in total, internal
  878. and external - 1.3.6.1.4.1.318.1.1.1.2.4
  879. - name: upsBatteryCabinetIndex
  880. oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.1
  881. type: gauge
  882. help: The Battery Cabinet identifier - 1.3.6.1.4.1.318.1.1.1.2.5.1.1
  883. indexes:
  884. - labelname: upsBatteryCabinetIndex
  885. type: gauge
  886. - name: upsBatteryCabinetLocalIndex
  887. oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.2
  888. type: gauge
  889. help: The identification number for the actual battery cabinet in the system
  890. - 1.3.6.1.4.1.318.1.1.1.2.5.1.2
  891. indexes:
  892. - labelname: upsBatteryCabinetIndex
  893. type: gauge
  894. - name: upsBatteryCabinetWiringConfiguration
  895. oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.3
  896. type: gauge
  897. help: The value indicates the wiring configuration, whether the battery is 2-wire
  898. or 3-wire - 1.3.6.1.4.1.318.1.1.1.2.5.1.3
  899. indexes:
  900. - labelname: upsBatteryCabinetIndex
  901. type: gauge
  902. enum_values:
  903. 1: twoWire
  904. 2: threeWire
  905. - name: upsBatteryCabinetVoltagePolarity1
  906. oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.4
  907. type: gauge
  908. help: The battery voltage - 1.3.6.1.4.1.318.1.1.1.2.5.1.4
  909. indexes:
  910. - labelname: upsBatteryCabinetIndex
  911. type: gauge
  912. - name: upsBatteryCabinetVoltagePolarity2
  913. oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.5
  914. type: gauge
  915. help: The voltage for the second side/half of the battery in a split battery
  916. system - 1.3.6.1.4.1.318.1.1.1.2.5.1.5
  917. indexes:
  918. - labelname: upsBatteryCabinetIndex
  919. type: gauge
  920. - name: upsBatteryCabinetCurrentPolarity1
  921. oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.6
  922. type: gauge
  923. help: The battery current - 1.3.6.1.4.1.318.1.1.1.2.5.1.6
  924. indexes:
  925. - labelname: upsBatteryCabinetIndex
  926. type: gauge
  927. - name: upsBatteryCabinetCurrentPolarity2
  928. oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.7
  929. type: gauge
  930. help: The current for the second side/half of the battery in a split battery
  931. system - 1.3.6.1.4.1.318.1.1.1.2.5.1.7
  932. indexes:
  933. - labelname: upsBatteryCabinetIndex
  934. type: gauge
  935. - name: upsBatteryCabinetTemperature
  936. oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.8
  937. type: gauge
  938. help: The measured temperature of the battery cabinet in tenths of degrees Celcius
  939. - 1.3.6.1.4.1.318.1.1.1.2.5.1.8
  940. indexes:
  941. - labelname: upsBatteryCabinetIndex
  942. type: gauge
  943. - name: upsBatteryCabinetMaxTemperature
  944. oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.9
  945. type: gauge
  946. help: The highest temperature measured for the battery in the battery cabinet
  947. in tenths of degrees Celcius - 1.3.6.1.4.1.318.1.1.1.2.5.1.9
  948. indexes:
  949. - labelname: upsBatteryCabinetIndex
  950. type: gauge
  951. - name: upsBatteryCabinetMinTemperature
  952. oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.10
  953. type: gauge
  954. help: The lowest temperature measured for the battery in the battery cabinet
  955. in tenths of degrees Celcius - 1.3.6.1.4.1.318.1.1.1.2.5.1.10
  956. indexes:
  957. - labelname: upsBatteryCabinetIndex
  958. type: gauge
  959. - name: upsBatteryCabinetAverageTemperature
  960. oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.11
  961. type: gauge
  962. help: The average temperature for all the battery sensors in the battery cabinet
  963. and for the battery strings, if battery strings are present - 1.3.6.1.4.1.318.1.1.1.2.5.1.11
  964. indexes:
  965. - labelname: upsBatteryCabinetIndex
  966. type: gauge
  967. - name: upsBatteryCabinetFuse
  968. oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.12
  969. type: gauge
  970. help: If the battery cabinet has a common fuse, the status is given by this
  971. value - 1.3.6.1.4.1.318.1.1.1.2.5.1.12
  972. indexes:
  973. - labelname: upsBatteryCabinetIndex
  974. type: gauge
  975. enum_values:
  976. 1: fuseOpen
  977. 2: fuseOk
  978. 3: notPresent
  979. - name: upsBatteryCabinetBreaker
  980. oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.13
  981. type: gauge
  982. help: The value indicates the battery cabinet breaker status - 1.3.6.1.4.1.318.1.1.1.2.5.1.13
  983. indexes:
  984. - labelname: upsBatteryCabinetIndex
  985. type: gauge
  986. enum_values:
  987. 1: noBreaker
  988. 2: unknown
  989. 3: breakerOpen
  990. 4: breakerClosed
  991. - name: upsBatteryCabinetNumberOfStrings
  992. oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.14
  993. type: gauge
  994. help: The number of battery strings in the battery cabinet - 1.3.6.1.4.1.318.1.1.1.2.5.1.14
  995. indexes:
  996. - labelname: upsBatteryCabinetIndex
  997. type: gauge
  998. - name: upsBatteryCabinetNumberOfVerticalPositions
  999. oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.15
  1000. type: gauge
  1001. help: The number of vertical levels or shelves for battery blocks/modules -
  1002. 1.3.6.1.4.1.318.1.1.1.2.5.1.15
  1003. indexes:
  1004. - labelname: upsBatteryCabinetIndex
  1005. type: gauge
  1006. - name: upsBatteryCabinetNumberOfHorizontalPositions
  1007. oid: 1.3.6.1.4.1.318.1.1.1.2.5.1.16
  1008. type: gauge
  1009. help: The number of horizontal positions for battery blocks/modules - 1.3.6.1.4.1.318.1.1.1.2.5.1.16
  1010. indexes:
  1011. - labelname: upsBatteryCabinetIndex
  1012. type: gauge
  1013. - name: upsBatteryCabStringIndex
  1014. oid: 1.3.6.1.4.1.318.1.1.1.2.6.1.1
  1015. type: gauge
  1016. help: The battery cabinet string identifier - 1.3.6.1.4.1.318.1.1.1.2.6.1.1
  1017. indexes:
  1018. - labelname: upsBatteryCabStringIndex
  1019. type: gauge
  1020. - name: upsBatteryCabStringCabReference
  1021. oid: 1.3.6.1.4.1.318.1.1.1.2.6.1.2
  1022. type: gauge
  1023. help: Reference to the global battery cabinet index where the battery string
  1024. is placed. - 1.3.6.1.4.1.318.1.1.1.2.6.1.2
  1025. indexes:
  1026. - labelname: upsBatteryCabStringIndex
  1027. type: gauge
  1028. - name: upsBatteryCabStringLocalIndex
  1029. oid: 1.3.6.1.4.1.318.1.1.1.2.6.1.3
  1030. type: gauge
  1031. help: Local battery string identification index in the actual battery cabinet
  1032. (e.g - 1.3.6.1.4.1.318.1.1.1.2.6.1.3
  1033. indexes:
  1034. - labelname: upsBatteryCabStringIndex
  1035. type: gauge
  1036. - name: upsBatteryCabStringCurrent
  1037. oid: 1.3.6.1.4.1.318.1.1.1.2.6.1.4
  1038. type: gauge
  1039. help: The current in a battery string or battery halfstring, in tenths of Amps.
  1040. - 1.3.6.1.4.1.318.1.1.1.2.6.1.4
  1041. indexes:
  1042. - labelname: upsBatteryCabStringIndex
  1043. type: gauge
  1044. - name: upsBatteryCabStringAverageTemperature
  1045. oid: 1.3.6.1.4.1.318.1.1.1.2.6.1.5
  1046. type: gauge
  1047. help: Temperature of the battery string or the average of the aggregated temperature
  1048. of each battery block/module (in tenths of degrees Celcius). - 1.3.6.1.4.1.318.1.1.1.2.6.1.5
  1049. indexes:
  1050. - labelname: upsBatteryCabStringIndex
  1051. type: gauge
  1052. - name: upsBatteryCabStringMaxTemperature
  1053. oid: 1.3.6.1.4.1.318.1.1.1.2.6.1.6
  1054. type: gauge
  1055. help: The actual highest battery temperature measurement for the battery blocks/modules
  1056. (in tenths of degrees Celcius). - 1.3.6.1.4.1.318.1.1.1.2.6.1.6
  1057. indexes:
  1058. - labelname: upsBatteryCabStringIndex
  1059. type: gauge
  1060. - name: upsBatteryCabStringMinTemperature
  1061. oid: 1.3.6.1.4.1.318.1.1.1.2.6.1.7
  1062. type: gauge
  1063. help: The actual lowest battery temperature measurement for the battery blocks/modules
  1064. (in tenths of degrees Celcius). - 1.3.6.1.4.1.318.1.1.1.2.6.1.7
  1065. indexes:
  1066. - labelname: upsBatteryCabStringIndex
  1067. type: gauge
  1068. - name: upsBatteryCabStringFuseStatus
  1069. oid: 1.3.6.1.4.1.318.1.1.1.2.6.1.8
  1070. type: gauge
  1071. help: If the battery string has a common fuse, the status is given by this value
  1072. - 1.3.6.1.4.1.318.1.1.1.2.6.1.8
  1073. indexes:
  1074. - labelname: upsBatteryCabStringIndex
  1075. type: gauge
  1076. enum_values:
  1077. 1: fuseOpen
  1078. 2: fuseOk
  1079. 3: notPresent
  1080. - name: upsBatteryCabStringNumberOfBlocks
  1081. oid: 1.3.6.1.4.1.318.1.1.1.2.6.1.9
  1082. type: gauge
  1083. help: The number of battery blocks/modules in a battery string - 1.3.6.1.4.1.318.1.1.1.2.6.1.9
  1084. indexes:
  1085. - labelname: upsBatteryCabStringIndex
  1086. type: gauge
  1087. - name: upsBatteryCabBlockIndex
  1088. oid: 1.3.6.1.4.1.318.1.1.1.2.7.1.1
  1089. type: gauge
  1090. help: The battery cabinet block identifier - 1.3.6.1.4.1.318.1.1.1.2.7.1.1
  1091. indexes:
  1092. - labelname: upsBatteryCabBlockIndex
  1093. type: gauge
  1094. - name: upsBatteryCabBlockStringReference
  1095. oid: 1.3.6.1.4.1.318.1.1.1.2.7.1.2
  1096. type: gauge
  1097. help: Reference to the specific global battery string index - 1.3.6.1.4.1.318.1.1.1.2.7.1.2
  1098. indexes:
  1099. - labelname: upsBatteryCabBlockIndex
  1100. type: gauge
  1101. - name: upsBatteryCabBlockLocalIndex
  1102. oid: 1.3.6.1.4.1.318.1.1.1.2.7.1.3
  1103. type: gauge
  1104. help: Local battery block/module identification index in the actual battery
  1105. string (e.g - 1.3.6.1.4.1.318.1.1.1.2.7.1.3
  1106. indexes:
  1107. - labelname: upsBatteryCabBlockIndex
  1108. type: gauge
  1109. - name: upsBatteryCabBlockPresent
  1110. oid: 1.3.6.1.4.1.318.1.1.1.2.7.1.4
  1111. type: gauge
  1112. help: Value indicates if battery block/module is present in the system - 1.3.6.1.4.1.318.1.1.1.2.7.1.4
  1113. indexes:
  1114. - labelname: upsBatteryCabBlockIndex
  1115. type: gauge
  1116. enum_values:
  1117. 1: present
  1118. 2: notPresent
  1119. 3: notAvailable
  1120. - name: upsBatteryCabBlockType
  1121. oid: 1.3.6.1.4.1.318.1.1.1.2.7.1.5
  1122. type: DisplayString
  1123. help: Text string value, showing the vendor and model of the battery in the
  1124. battery block/module - 1.3.6.1.4.1.318.1.1.1.2.7.1.5
  1125. indexes:
  1126. - labelname: upsBatteryCabBlockIndex
  1127. type: gauge
  1128. - name: upsBatteryCabBlockTemperature
  1129. oid: 1.3.6.1.4.1.318.1.1.1.2.7.1.6
  1130. type: gauge
  1131. help: The temperature for the battery block/module in tenths of degrees Celcius
  1132. - 1.3.6.1.4.1.318.1.1.1.2.7.1.6
  1133. indexes:
  1134. - labelname: upsBatteryCabBlockIndex
  1135. type: gauge
  1136. - name: upsBatteryCabBlockFuseStatus
  1137. oid: 1.3.6.1.4.1.318.1.1.1.2.7.1.7
  1138. type: gauge
  1139. help: If the battery module has a fuse, the status is given by this value -
  1140. 1.3.6.1.4.1.318.1.1.1.2.7.1.7
  1141. indexes:
  1142. - labelname: upsBatteryCabBlockIndex
  1143. type: gauge
  1144. enum_values:
  1145. 1: fuseOpen
  1146. 2: fuseOk
  1147. 3: notPresent
  1148. - name: upsBatteryCabBlockVoltage
  1149. oid: 1.3.6.1.4.1.318.1.1.1.2.7.1.8
  1150. type: gauge
  1151. help: The voltage of the battery block/module - 1.3.6.1.4.1.318.1.1.1.2.7.1.8
  1152. indexes:
  1153. - labelname: upsBatteryCabBlockIndex
  1154. type: gauge
  1155. - name: upsBatteryCabBlockNumberOfCells
  1156. oid: 1.3.6.1.4.1.318.1.1.1.2.7.1.9
  1157. type: gauge
  1158. help: The number of cells in the battery block/module - 1.3.6.1.4.1.318.1.1.1.2.7.1.9
  1159. indexes:
  1160. - labelname: upsBatteryCabBlockIndex
  1161. type: gauge
  1162. - name: upsBatteryCabBlockVerticalPosition
  1163. oid: 1.3.6.1.4.1.318.1.1.1.2.7.1.10
  1164. type: gauge
  1165. help: The vertical position of the battery block/module in the actual battery
  1166. cabinet (e.g - 1.3.6.1.4.1.318.1.1.1.2.7.1.10
  1167. indexes:
  1168. - labelname: upsBatteryCabBlockIndex
  1169. type: gauge
  1170. - name: upsBatteryCabBlockHorizontalPosition
  1171. oid: 1.3.6.1.4.1.318.1.1.1.2.7.1.11
  1172. type: gauge
  1173. help: The horizontal position of the battery block/module in the actual battery
  1174. cabinet (e.g - 1.3.6.1.4.1.318.1.1.1.2.7.1.11
  1175. indexes:
  1176. - labelname: upsBatteryCabBlockIndex
  1177. type: gauge
  1178. - name: upsBatteryCabBlockCellIndex
  1179. oid: 1.3.6.1.4.1.318.1.1.1.2.8.1.1
  1180. type: gauge
  1181. help: The battery block cell identifier - 1.3.6.1.4.1.318.1.1.1.2.8.1.1
  1182. indexes:
  1183. - labelname: upsBatteryCabBlockCellIndex
  1184. type: gauge
  1185. - name: upsBatteryCabBlockCellReference
  1186. oid: 1.3.6.1.4.1.318.1.1.1.2.8.1.2
  1187. type: gauge
  1188. help: Reference to the specific global battery block/module index. - 1.3.6.1.4.1.318.1.1.1.2.8.1.2
  1189. indexes:
  1190. - labelname: upsBatteryCabBlockCellIndex
  1191. type: gauge
  1192. - name: upsBatteryCabBlockCellLocalIndex
  1193. oid: 1.3.6.1.4.1.318.1.1.1.2.8.1.3
  1194. type: gauge
  1195. help: Local battery block/module identification index in the actual battery
  1196. block (e.g - 1.3.6.1.4.1.318.1.1.1.2.8.1.3
  1197. indexes:
  1198. - labelname: upsBatteryCabBlockCellIndex
  1199. type: gauge
  1200. - name: upsBatteryCabBlockCellVoltage
  1201. oid: 1.3.6.1.4.1.318.1.1.1.2.8.1.4
  1202. type: gauge
  1203. help: The measured battery cell voltage - 1.3.6.1.4.1.318.1.1.1.2.8.1.4
  1204. indexes:
  1205. - labelname: upsBatteryCabBlockCellIndex
  1206. type: gauge
  1207. - name: upsBatteryCabBlockCellTemperature
  1208. oid: 1.3.6.1.4.1.318.1.1.1.2.8.1.5
  1209. type: gauge
  1210. help: The temperature for the battery cell in tenths of degrees Celcius - 1.3.6.1.4.1.318.1.1.1.2.8.1.5
  1211. indexes:
  1212. - labelname: upsBatteryCabBlockCellIndex
  1213. type: gauge
  1214. - name: upsBasicInputPhase
  1215. oid: 1.3.6.1.4.1.318.1.1.1.3.1.1
  1216. type: gauge
  1217. help: The current AC input phase. - 1.3.6.1.4.1.318.1.1.1.3.1.1
  1218. - name: upsAdvInputLineVoltage
  1219. oid: 1.3.6.1.4.1.318.1.1.1.3.2.1
  1220. type: gauge
  1221. help: The current utility line voltage in VAC. - 1.3.6.1.4.1.318.1.1.1.3.2.1
  1222. - name: upsAdvInputMaxLineVoltage
  1223. oid: 1.3.6.1.4.1.318.1.1.1.3.2.2
  1224. type: gauge
  1225. help: The maximum utility line voltage in VAC over the previous 1 minute period.
  1226. - 1.3.6.1.4.1.318.1.1.1.3.2.2
  1227. - name: upsAdvInputMinLineVoltage
  1228. oid: 1.3.6.1.4.1.318.1.1.1.3.2.3
  1229. type: gauge
  1230. help: The minimum utility line voltage in VAC over the previous 1 minute period.
  1231. - 1.3.6.1.4.1.318.1.1.1.3.2.3
  1232. - name: upsAdvInputFrequency
  1233. oid: 1.3.6.1.4.1.318.1.1.1.3.2.4
  1234. type: gauge
  1235. help: The current input frequency to the UPS system in Hz. - 1.3.6.1.4.1.318.1.1.1.3.2.4
  1236. - name: upsAdvInputLineFailCause
  1237. oid: 1.3.6.1.4.1.318.1.1.1.3.2.5
  1238. type: gauge
  1239. help: The reason for the occurrence of the last transfer to UPS battery power
  1240. - 1.3.6.1.4.1.318.1.1.1.3.2.5
  1241. enum_values:
  1242. 1: noTransfer
  1243. 2: highLineVoltage
  1244. 3: brownout
  1245. 4: blackout
  1246. 5: smallMomentarySag
  1247. 6: deepMomentarySag
  1248. 7: smallMomentarySpike
  1249. 8: largeMomentarySpike
  1250. 9: selfTest
  1251. 10: rateOfVoltageChange
  1252. - name: upsAdvInputNominalFrequency
  1253. oid: 1.3.6.1.4.1.318.1.1.1.3.2.6
  1254. type: gauge
  1255. help: The nominal input frequency of the UPS system in Hz. - 1.3.6.1.4.1.318.1.1.1.3.2.6
  1256. - name: upsAdvInputNominalVoltage
  1257. oid: 1.3.6.1.4.1.318.1.1.1.3.2.7
  1258. type: gauge
  1259. help: The nominal input voltage of the UPS system in VAC. - 1.3.6.1.4.1.318.1.1.1.3.2.7
  1260. - name: upsAdvInputBypassNominalFrequency
  1261. oid: 1.3.6.1.4.1.318.1.1.1.3.2.8
  1262. type: gauge
  1263. help: The nominal bypass input frequency of the UPS system in Hz. - 1.3.6.1.4.1.318.1.1.1.3.2.8
  1264. - name: upsAdvInputBypassNominalVoltage
  1265. oid: 1.3.6.1.4.1.318.1.1.1.3.2.9
  1266. type: gauge
  1267. help: The nominal bypass input voltage of the UPS system in VAC. - 1.3.6.1.4.1.318.1.1.1.3.2.9
  1268. - name: upsAdvInputStatisticsIndex
  1269. oid: 1.3.6.1.4.1.318.1.1.1.3.2.10.1.1
  1270. type: gauge
  1271. help: The input identifier. - 1.3.6.1.4.1.318.1.1.1.3.2.10.1.1
  1272. indexes:
  1273. - labelname: upsAdvInputStatisticsIndex
  1274. type: gauge
  1275. - name: upsAdvInputApparentPower
  1276. oid: 1.3.6.1.4.1.318.1.1.1.3.2.10.1.2
  1277. type: gauge
  1278. help: The input apparent power(sum of all of the three phases) measured in kVA.
  1279. - 1.3.6.1.4.1.318.1.1.1.3.2.10.1.2
  1280. indexes:
  1281. - labelname: upsAdvInputStatisticsIndex
  1282. type: gauge
  1283. - name: upsAdvInputVoltageTHD
  1284. oid: 1.3.6.1.4.1.318.1.1.1.3.2.10.1.3
  1285. type: gauge
  1286. help: The input voltage Total Harmonic Distortion in percent. - 1.3.6.1.4.1.318.1.1.1.3.2.10.1.3
  1287. indexes:
  1288. - labelname: upsAdvInputStatisticsIndex
  1289. type: gauge
  1290. - name: upsAdvInputBypassVoltageTHD
  1291. oid: 1.3.6.1.4.1.318.1.1.1.3.2.10.1.4
  1292. type: gauge
  1293. help: The bypass input voltage Total Harmonic Distortion in percent. - 1.3.6.1.4.1.318.1.1.1.3.2.10.1.4
  1294. indexes:
  1295. - labelname: upsAdvInputStatisticsIndex
  1296. type: gauge
  1297. - name: upsAdvInputPeakCurrent
  1298. oid: 1.3.6.1.4.1.318.1.1.1.3.2.10.1.5
  1299. type: gauge
  1300. help: The input peak current in Amperes. - 1.3.6.1.4.1.318.1.1.1.3.2.10.1.5
  1301. indexes:
  1302. - labelname: upsAdvInputStatisticsIndex
  1303. type: gauge
  1304. - name: upsAdvInputBypassPeakCurrent
  1305. oid: 1.3.6.1.4.1.318.1.1.1.3.2.10.1.6
  1306. type: gauge
  1307. help: The bypass input peak current in Amperes. - 1.3.6.1.4.1.318.1.1.1.3.2.10.1.6
  1308. indexes:
  1309. - labelname: upsAdvInputStatisticsIndex
  1310. type: gauge
  1311. - name: upsAdvInputActivePower
  1312. oid: 1.3.6.1.4.1.318.1.1.1.3.2.10.1.7
  1313. type: gauge
  1314. help: The input active power measured in kW. - 1.3.6.1.4.1.318.1.1.1.3.2.10.1.7
  1315. indexes:
  1316. - labelname: upsAdvInputStatisticsIndex
  1317. type: gauge
  1318. - name: upsAdvInputTotalApparentPower
  1319. oid: 1.3.6.1.4.1.318.1.1.1.3.2.11
  1320. type: gauge
  1321. help: The input total apparent power(sum of all three phases) of the UPS system
  1322. in kVA. - 1.3.6.1.4.1.318.1.1.1.3.2.11
  1323. - name: upsAdvInputTotalActivePower
  1324. oid: 1.3.6.1.4.1.318.1.1.1.3.2.12
  1325. type: gauge
  1326. help: The input total active power(sum of all three phases) of the UPS system
  1327. in kW - 1.3.6.1.4.1.318.1.1.1.3.2.12
  1328. - name: upsAdvInputBypassTotalApparentPower
  1329. oid: 1.3.6.1.4.1.318.1.1.1.3.2.13
  1330. type: gauge
  1331. help: The input bypass total apparent power(sum of all three phases) of the
  1332. UPS system in kVA. - 1.3.6.1.4.1.318.1.1.1.3.2.13
  1333. - name: upsAdvInputBypassTotalActivePower
  1334. oid: 1.3.6.1.4.1.318.1.1.1.3.2.14
  1335. type: gauge
  1336. help: The input bypass total active power(sum of all three phases) of the UPS
  1337. system in kW. - 1.3.6.1.4.1.318.1.1.1.3.2.14
  1338. - name: upsAdvInputEnergyUsage
  1339. oid: 1.3.6.1.4.1.318.1.1.1.3.2.15
  1340. type: gauge
  1341. help: The input energy usage of the UPS in kWh. - 1.3.6.1.4.1.318.1.1.1.3.2.15
  1342. - name: upsAdvInputDCVoltage
  1343. oid: 1.3.6.1.4.1.318.1.1.1.3.2.16
  1344. type: gauge
  1345. help: The DC input voltage in Volts. - 1.3.6.1.4.1.318.1.1.1.3.2.16
  1346. - name: upsAdvInputDCCurrent
  1347. oid: 1.3.6.1.4.1.318.1.1.1.3.2.17
  1348. type: gauge
  1349. help: The DC input current in Amps. - 1.3.6.1.4.1.318.1.1.1.3.2.17
  1350. - name: upsAdvInputNominalDCVoltage
  1351. oid: 1.3.6.1.4.1.318.1.1.1.3.2.18
  1352. type: gauge
  1353. help: The nominal input DC voltage of the inverter in Volts - 1.3.6.1.4.1.318.1.1.1.3.2.18
  1354. - name: upsHighPrecInputLineVoltage
  1355. oid: 1.3.6.1.4.1.318.1.1.1.3.3.1
  1356. type: gauge
  1357. help: The current utility line voltage in tenths of VAC. - 1.3.6.1.4.1.318.1.1.1.3.3.1
  1358. - name: upsHighPrecInputMaxLineVoltage
  1359. oid: 1.3.6.1.4.1.318.1.1.1.3.3.2
  1360. type: gauge
  1361. help: The maximum utility line voltage in tenths of VAC over the previous 1
  1362. minute period. - 1.3.6.1.4.1.318.1.1.1.3.3.2
  1363. - name: upsHighPrecInputMinLineVoltage
  1364. oid: 1.3.6.1.4.1.318.1.1.1.3.3.3
  1365. type: gauge
  1366. help: The minimum utility line voltage in tenths of VAC over the previous 1
  1367. minute period. - 1.3.6.1.4.1.318.1.1.1.3.3.3
  1368. - name: upsHighPrecInputFrequency
  1369. oid: 1.3.6.1.4.1.318.1.1.1.3.3.4
  1370. type: gauge
  1371. help: The current input frequency to the UPS system in tenths of Hz. - 1.3.6.1.4.1.318.1.1.1.3.3.4
  1372. - name: upsHighPrecInputEnergyUsage
  1373. oid: 1.3.6.1.4.1.318.1.1.1.3.3.5
  1374. type: gauge
  1375. help: The input energy usage of the UPS in hundredths of kWh. - 1.3.6.1.4.1.318.1.1.1.3.3.5
  1376. - name: upsHighPrecInputBypassVoltage
  1377. oid: 1.3.6.1.4.1.318.1.1.1.3.3.6
  1378. type: gauge
  1379. help: The current bypass line voltage in tenths of VAC. - 1.3.6.1.4.1.318.1.1.1.3.3.6
  1380. - name: upsHighPrecInputBypassFrequency
  1381. oid: 1.3.6.1.4.1.318.1.1.1.3.3.7
  1382. type: gauge
  1383. help: The current input bypass frequency to the UPS system in tenths of Hz.
  1384. - 1.3.6.1.4.1.318.1.1.1.3.3.7
  1385. - name: upsHighPrecInputDCVoltage
  1386. oid: 1.3.6.1.4.1.318.1.1.1.3.3.8
  1387. type: gauge
  1388. help: The DC input voltage, in tenths, of Volts on the inverter - 1.3.6.1.4.1.318.1.1.1.3.3.8
  1389. - name: upsHighPrecInputDCCurrent
  1390. oid: 1.3.6.1.4.1.318.1.1.1.3.3.9
  1391. type: gauge
  1392. help: The DC input current, in tenths of amperes, of the inverter. - 1.3.6.1.4.1.318.1.1.1.3.3.9
  1393. - name: upsBasicOutputStatus
  1394. oid: 1.3.6.1.4.1.318.1.1.1.4.1.1
  1395. type: gauge
  1396. help: The current state of the UPS - 1.3.6.1.4.1.318.1.1.1.4.1.1
  1397. enum_values:
  1398. 1: unknown
  1399. 2: onLine
  1400. 3: onBattery
  1401. 4: onSmartBoost
  1402. 5: timedSleeping
  1403. 6: softwareBypass
  1404. 7: "off"
  1405. 8: rebooting
  1406. 9: switchedBypass
  1407. 10: hardwareFailureBypass
  1408. 11: sleepingUntilPowerReturn
  1409. 12: onSmartTrim
  1410. 13: ecoMode
  1411. 14: hotStandby
  1412. 15: onBatteryTest
  1413. 16: emergencyStaticBypass
  1414. 17: staticBypassStandby
  1415. 18: powerSavingMode
  1416. 19: spotMode
  1417. 20: eConversion
  1418. 21: chargerSpotmode
  1419. 22: inverterSpotmode
  1420. 23: activeLoad
  1421. 24: batteryDischargeSpotmode
  1422. 25: inverterStandby
  1423. 26: chargerOnly
  1424. 27: distributedEnergyReserve
  1425. 28: selfTest
  1426. - name: upsBasicOutputPhase
  1427. oid: 1.3.6.1.4.1.318.1.1.1.4.1.2
  1428. type: gauge
  1429. help: The actual number of output phases in a UPS - 1.3.6.1.4.1.318.1.1.1.4.1.2
  1430. - name: upsBasicSystemStatus
  1431. oid: 1.3.6.1.4.1.318.1.1.1.4.1.3
  1432. type: gauge
  1433. help: Current state for the whole system (UPS and surrounding breakers) - 1.3.6.1.4.1.318.1.1.1.4.1.3
  1434. enum_values:
  1435. 1: unknown
  1436. 2: onLine
  1437. 3: onBattery
  1438. 4: onSmartBoost
  1439. 5: timedSleeping
  1440. 6: softwareBypass
  1441. 7: "off"
  1442. 8: rebooting
  1443. 9: switchedBypass
  1444. 10: hardwareFailureBypass
  1445. 11: sleepingUntilPowerReturn
  1446. 12: onSmartTrim
  1447. 13: ecoMode
  1448. 14: inverter
  1449. 15: eConversion
  1450. 16: staticBypassStandby
  1451. 17: efficiencyBoosterMode
  1452. - name: upsBasicSystemInternalTemperature
  1453. oid: 1.3.6.1.4.1.318.1.1.1.4.1.4
  1454. type: gauge
  1455. help: The actual internal temperature of the UPS system in Celsius. - 1.3.6.1.4.1.318.1.1.1.4.1.4
  1456. - name: upsBasicSystemInverterStatus
  1457. oid: 1.3.6.1.4.1.318.1.1.1.4.1.5
  1458. type: gauge
  1459. help: The current state of the UPS inverter - 1.3.6.1.4.1.318.1.1.1.4.1.5
  1460. enum_values:
  1461. 1: unknown
  1462. 2: ok
  1463. 3: inFaultCondition
  1464. - name: upsBasicSystemPFCStatus
  1465. oid: 1.3.6.1.4.1.318.1.1.1.4.1.6
  1466. type: gauge
  1467. help: The general status of the power factor correction (AC input stage of the
  1468. UPS) - 1.3.6.1.4.1.318.1.1.1.4.1.6
  1469. enum_values:
  1470. 1: unknown
  1471. 2: ok
  1472. 3: inFaultCondition
  1473. - name: upsBasicOutputACwiringConfiguration
  1474. oid: 1.3.6.1.4.1.318.1.1.1.4.1.7
  1475. type: gauge
  1476. help: Indicates if neutral wire on output side of the UPS is used (load wired
  1477. line to neutral) - 1.3.6.1.4.1.318.1.1.1.4.1.7
  1478. enum_values:
  1479. 1: unknown
  1480. 2: noNeutralWiredonSystem
  1481. 3: neutralUsedforSupplyingLoad
  1482. - name: upsAdvOutputVoltage
  1483. oid: 1.3.6.1.4.1.318.1.1.1.4.2.1
  1484. type: gauge
  1485. help: The output voltage of the UPS system in VAC. - 1.3.6.1.4.1.318.1.1.1.4.2.1
  1486. - name: upsAdvOutputFrequency
  1487. oid: 1.3.6.1.4.1.318.1.1.1.4.2.2
  1488. type: gauge
  1489. help: The current output frequency of the UPS system in Hz. - 1.3.6.1.4.1.318.1.1.1.4.2.2
  1490. - name: upsAdvOutputLoad
  1491. oid: 1.3.6.1.4.1.318.1.1.1.4.2.3
  1492. type: gauge
  1493. help: The current UPS load expressed in percent of rated capacity. - 1.3.6.1.4.1.318.1.1.1.4.2.3
  1494. - name: upsAdvOutputCurrent
  1495. oid: 1.3.6.1.4.1.318.1.1.1.4.2.4
  1496. type: gauge
  1497. help: The current in amperes drawn by the load on the UPS. - 1.3.6.1.4.1.318.1.1.1.4.2.4
  1498. - name: upsAdvOutputRedundancy
  1499. oid: 1.3.6.1.4.1.318.1.1.1.4.2.5
  1500. type: gauge
  1501. help: The number of power modules which can fail or be removed without causing
  1502. the UPS to generate a Minimum Redundancy Lost event. - 1.3.6.1.4.1.318.1.1.1.4.2.5
  1503. - name: upsAdvOutputKVACapacity
  1504. oid: 1.3.6.1.4.1.318.1.1.1.4.2.6
  1505. type: gauge
  1506. help: The maximum load that this UPS can support - 1.3.6.1.4.1.318.1.1.1.4.2.6
  1507. - name: upsAdvOutputNominalFrequency
  1508. oid: 1.3.6.1.4.1.318.1.1.1.4.2.7
  1509. type: gauge
  1510. help: The nominal output frequency of the UPS system in Hz. - 1.3.6.1.4.1.318.1.1.1.4.2.7
  1511. - name: upsAdvOutputActivePower
  1512. oid: 1.3.6.1.4.1.318.1.1.1.4.2.8
  1513. type: gauge
  1514. help: The total output active power of the UPS system in W - 1.3.6.1.4.1.318.1.1.1.4.2.8
  1515. - name: upsAdvOutputApparentPower
  1516. oid: 1.3.6.1.4.1.318.1.1.1.4.2.9
  1517. type: gauge
  1518. help: The total output apparent power of all phases of the UPS system in VA
  1519. - 1.3.6.1.4.1.318.1.1.1.4.2.9
  1520. - name: upsAdvOutputStatisticsIndex
  1521. oid: 1.3.6.1.4.1.318.1.1.1.4.2.10.1.1
  1522. type: gauge
  1523. help: The output identifier. - 1.3.6.1.4.1.318.1.1.1.4.2.10.1.1
  1524. indexes:
  1525. - labelname: upsAdvOutputStatisticsIndex
  1526. type: gauge
  1527. - name: upsAdvOutputPeakCurrent
  1528. oid: 1.3.6.1.4.1.318.1.1.1.4.2.10.1.2
  1529. type: gauge
  1530. help: The output peak current in Amperes. - 1.3.6.1.4.1.318.1.1.1.4.2.10.1.2
  1531. indexes:
  1532. - labelname: upsAdvOutputStatisticsIndex
  1533. type: gauge
  1534. - name: upsAdvOutputCurrentTHD
  1535. oid: 1.3.6.1.4.1.318.1.1.1.4.2.10.1.3
  1536. type: gauge
  1537. help: The output current Total Harmonic Distortion in percent. - 1.3.6.1.4.1.318.1.1.1.4.2.10.1.3
  1538. indexes:
  1539. - labelname: upsAdvOutputStatisticsIndex
  1540. type: gauge
  1541. - name: upsAdvOutputCrestFactor
  1542. oid: 1.3.6.1.4.1.318.1.1.1.4.2.10.1.4
  1543. type: gauge
  1544. help: The output current crest factor expressed in tenths. - 1.3.6.1.4.1.318.1.1.1.4.2.10.1.4
  1545. indexes:
  1546. - labelname: upsAdvOutputStatisticsIndex
  1547. type: gauge
  1548. - name: upsAdvOutputNeutralCurrent
  1549. oid: 1.3.6.1.4.1.318.1.1.1.4.2.11
  1550. type: gauge
  1551. help: The neutral current in amperes. - 1.3.6.1.4.1.318.1.1.1.4.2.11
  1552. - name: upsAdvOutputEnergyUsage
  1553. oid: 1.3.6.1.4.1.318.1.1.1.4.2.12
  1554. type: gauge
  1555. help: The output energy usage of the UPS in kWh. - 1.3.6.1.4.1.318.1.1.1.4.2.12
  1556. - name: upsAdvOutputSourceSynchronization
  1557. oid: 1.3.6.1.4.1.318.1.1.1.4.2.13
  1558. type: gauge
  1559. help: Indicates the synchronization source for the inverter output frequency
  1560. - 1.3.6.1.4.1.318.1.1.1.4.2.13
  1561. - name: upsAdvOutputInverterFrequency
  1562. oid: 1.3.6.1.4.1.318.1.1.1.4.2.14
  1563. type: gauge
  1564. help: Output frequency in Hz measured at the output of inverter. - 1.3.6.1.4.1.318.1.1.1.4.2.14
  1565. - name: upsAdvOutputInverterLoad
  1566. oid: 1.3.6.1.4.1.318.1.1.1.4.2.15
  1567. type: gauge
  1568. help: The total active power at the output of all inverter modules in percent
  1569. of rated system power (% of kW) If not supported, return -1. - 1.3.6.1.4.1.318.1.1.1.4.2.15
  1570. - name: upsAdvOutputPercentPower
  1571. oid: 1.3.6.1.4.1.318.1.1.1.4.2.16
  1572. type: gauge
  1573. help: The relative active power at the output of the inverter system (static
  1574. switch output) in percent of rated system power (% of kW) - 1.3.6.1.4.1.318.1.1.1.4.2.16
  1575. - name: upsAdvOutputInverterActivePower
  1576. oid: 1.3.6.1.4.1.318.1.1.1.4.2.17
  1577. type: gauge
  1578. help: The total active power at the output of all inverter modules in kW - 1.3.6.1.4.1.318.1.1.1.4.2.17
  1579. - name: upsAdvOutputPercentLoad
  1580. oid: 1.3.6.1.4.1.318.1.1.1.4.2.18
  1581. type: gauge
  1582. help: The relative apparent power at the output of the inverter system (static
  1583. switch output) in percent of rated system load (% of kVA) If not supported,
  1584. return -1. - 1.3.6.1.4.1.318.1.1.1.4.2.18
  1585. - name: upsAdvOutputInverterCurrent
  1586. oid: 1.3.6.1.4.1.318.1.1.1.4.2.19
  1587. type: gauge
  1588. help: The current, in amperes, drawn by the load on the inverter. - 1.3.6.1.4.1.318.1.1.1.4.2.19
  1589. - name: upsAdvOutputReactivePower
  1590. oid: 1.3.6.1.4.1.318.1.1.1.4.2.20
  1591. type: gauge
  1592. help: The total output reactive power of all phases of the UPS system in VAR
  1593. - 1.3.6.1.4.1.318.1.1.1.4.2.20
  1594. - name: upsAdvOutputInverterVoltage
  1595. oid: 1.3.6.1.4.1.318.1.1.1.4.2.21
  1596. type: gauge
  1597. help: The output voltage of the inverter in VAC. - 1.3.6.1.4.1.318.1.1.1.4.2.21
  1598. - name: upsAdvOutputUpperAcceptPowerSettingPct
  1599. oid: 1.3.6.1.4.1.318.1.1.1.4.2.22
  1600. type: gauge
  1601. help: Upper acceptable voltage as percent of nominal voltage - 1.3.6.1.4.1.318.1.1.1.4.2.22
  1602. - name: upsHighPrecOutputVoltage
  1603. oid: 1.3.6.1.4.1.318.1.1.1.4.3.1
  1604. type: gauge
  1605. help: The output voltage of the UPS system in tenths of VAC. - 1.3.6.1.4.1.318.1.1.1.4.3.1
  1606. - name: upsHighPrecOutputFrequency
  1607. oid: 1.3.6.1.4.1.318.1.1.1.4.3.2
  1608. type: gauge
  1609. help: The current output frequency of the UPS system in tenths of Hz. - 1.3.6.1.4.1.318.1.1.1.4.3.2
  1610. - name: upsHighPrecOutputLoad
  1611. oid: 1.3.6.1.4.1.318.1.1.1.4.3.3
  1612. type: gauge
  1613. help: The current UPS load expressed in tenths of percent of rated capacity.
  1614. - 1.3.6.1.4.1.318.1.1.1.4.3.3
  1615. - name: upsHighPrecOutputCurrent
  1616. oid: 1.3.6.1.4.1.318.1.1.1.4.3.4
  1617. type: gauge
  1618. help: The current in tenths of amperes drawn by the load on the UPS. - 1.3.6.1.4.1.318.1.1.1.4.3.4
  1619. - name: upsHighPrecOutputEfficiency
  1620. oid: 1.3.6.1.4.1.318.1.1.1.4.3.5
  1621. type: gauge
  1622. help: The positive values represent efficiency of the UPS in tenths of percent
  1623. - 1.3.6.1.4.1.318.1.1.1.4.3.5
  1624. - name: upsHighPrecOutputEnergyUsage
  1625. oid: 1.3.6.1.4.1.318.1.1.1.4.3.6
  1626. type: gauge
  1627. help: The output energy usage of the UPS in hundredths of kWh. - 1.3.6.1.4.1.318.1.1.1.4.3.6
  1628. - name: upsAdvTestDiagnosticSchedule
  1629. oid: 1.3.6.1.4.1.318.1.1.1.7.2.1
  1630. type: gauge
  1631. help: The UPS system's automatic battery test schedule. - 1.3.6.1.4.1.318.1.1.1.7.2.1
  1632. enum_values:
  1633. 1: unknown
  1634. 2: biweekly
  1635. 3: weekly
  1636. 4: atTurnOn
  1637. 5: never
  1638. 6: fourWeeks
  1639. 7: twelveWeeks
  1640. 8: biweeklySinceLastTest
  1641. 9: weeklySinceLastTest
  1642. 10: eightWeeks
  1643. 11: twentysixWeeks
  1644. 12: fiftytwoWeeks
  1645. - name: upsAdvTestDiagnostics
  1646. oid: 1.3.6.1.4.1.318.1.1.1.7.2.2
  1647. type: gauge
  1648. help: Setting this variable to testDiagnostics(2) causes the UPS to perform
  1649. a diagnostic self test - 1.3.6.1.4.1.318.1.1.1.7.2.2
  1650. enum_values:
  1651. 1: noTestDiagnostics
  1652. 2: testDiagnostics
  1653. - name: upsAdvTestDiagnosticsResults
  1654. oid: 1.3.6.1.4.1.318.1.1.1.7.2.3
  1655. type: gauge
  1656. help: The results of the last UPS diagnostics test performed. - 1.3.6.1.4.1.318.1.1.1.7.2.3
  1657. enum_values:
  1658. 1: ok
  1659. 2: failed
  1660. 3: invalidTest
  1661. 4: testInProgress
  1662. - name: upsAdvTestLastDiagnosticsDate
  1663. oid: 1.3.6.1.4.1.318.1.1.1.7.2.4
  1664. type: DisplayString
  1665. help: The date the last UPS diagnostics test was performed in mm/dd/yy format.
  1666. - 1.3.6.1.4.1.318.1.1.1.7.2.4
  1667. - name: upsAdvTestRuntimeCalibration
  1668. oid: 1.3.6.1.4.1.318.1.1.1.7.2.5
  1669. type: gauge
  1670. help: Setting this variable to performCalibration(2) causes the UPS to discharge
  1671. to calibrate the UPS - 1.3.6.1.4.1.318.1.1.1.7.2.5
  1672. enum_values:
  1673. 1: noPerformCalibration
  1674. 2: performCalibration
  1675. 3: cancelCurrentCalibration
  1676. - name: upsAdvTestCalibrationResults
  1677. oid: 1.3.6.1.4.1.318.1.1.1.7.2.6
  1678. type: gauge
  1679. help: The results of the last runtime calibration - 1.3.6.1.4.1.318.1.1.1.7.2.6
  1680. enum_values:
  1681. 1: ok
  1682. 2: invalidCalibration
  1683. 3: calibrationInProgress
  1684. 4: refused
  1685. 5: aborted
  1686. 6: pending
  1687. 7: unknown
  1688. - name: upsAdvTestCalibrationDate
  1689. oid: 1.3.6.1.4.1.318.1.1.1.7.2.7
  1690. type: DisplayString
  1691. help: The date the last UPS runtime calibration was performed in mm/dd/yy format.
  1692. - 1.3.6.1.4.1.318.1.1.1.7.2.7
  1693. - name: upsAdvTestDiagnosticTime
  1694. oid: 1.3.6.1.4.1.318.1.1.1.7.2.8
  1695. type: DisplayString
  1696. help: The time of the day to perform automatic battery test - 1.3.6.1.4.1.318.1.1.1.7.2.8
  1697. - name: upsAdvTestDiagnosticDay
  1698. oid: 1.3.6.1.4.1.318.1.1.1.7.2.9
  1699. type: gauge
  1700. help: The day of the week to perform automatic battery test. - 1.3.6.1.4.1.318.1.1.1.7.2.9
  1701. enum_values:
  1702. 1: monday
  1703. 2: tuesday
  1704. 3: wednesday
  1705. 4: thursday
  1706. 5: friday
  1707. 6: saturday
  1708. 7: sunday
  1709. - name: upsAdvTestBatteryInterval
  1710. oid: 1.3.6.1.4.1.318.1.1.1.7.2.10
  1711. type: DisplayString
  1712. help: The UPS system's automatic battery test period. - 1.3.6.1.4.1.318.1.1.1.7.2.10
  1713. - name: upsAdvTestCalibrationLastSuccessfulDate
  1714. oid: 1.3.6.1.4.1.318.1.1.1.7.2.11
  1715. type: DisplayString
  1716. help: The latest date when the UPS performed a successful runtime calibration
  1717. test - 1.3.6.1.4.1.318.1.1.1.7.2.11
  1718. - name: upsAdvTestBatteryLastSuccessfulDate
  1719. oid: 1.3.6.1.4.1.318.1.1.1.7.2.12
  1720. type: DisplayString
  1721. help: The latest date when the UPS performed a successful battery diagnostic
  1722. test (battery monitoring test) - 1.3.6.1.4.1.318.1.1.1.7.2.12
  1723. - name: upsAdvTestBatteryLastDate
  1724. oid: 1.3.6.1.4.1.318.1.1.1.7.2.13
  1725. type: DisplayString
  1726. help: The latest date when the UPS performed a battery diagnostic test (battery
  1727. monitoring test), regardless of the test result.The format is YYYY-MM-DD -
  1728. 1.3.6.1.4.1.318.1.1.1.7.2.13
  1729. - name: upsAdvTestBatteryProcessStatus
  1730. oid: 1.3.6.1.4.1.318.1.1.1.7.2.14
  1731. type: gauge
  1732. help: The results of the latest battery diagnostic test (battery monitoring
  1733. test) - 1.3.6.1.4.1.318.1.1.1.7.2.14
  1734. enum_values:
  1735. 1: ok
  1736. 2: preconditionNotMeet
  1737. 3: batteryTestInProgress
  1738. 4: refused
  1739. 5: aborted
  1740. 6: pending
  1741. 7: unknown
  1742. 8: noBatteryPresent
  1743. - name: upsAdvTestBatteryConditionStatus
  1744. oid: 1.3.6.1.4.1.318.1.1.1.7.2.15
  1745. type: gauge
  1746. help: Result of the latest successful test 1 = unknown 2 = battery OK 3 = battery
  1747. capacity decreased 4 = battery defect 5 = indicate that no battery is present
  1748. (no battery, battery breaker open,..) to perform the battery diagnostic test
  1749. - 1.3.6.1.4.1.318.1.1.1.7.2.15
  1750. enum_values:
  1751. 1: unknown
  1752. 2: batteryOK
  1753. 3: batteryCapacityDecreased
  1754. 4: batteryDefect
  1755. 5: noBatteryPresent
  1756. - name: upsAdvTestDiagnosticsBatteryInterval
  1757. oid: 1.3.6.1.4.1.318.1.1.1.7.2.16
  1758. type: gauge
  1759. help: The battery test is a diagnostic test (also referred to as battery monitoring
  1760. test) - 1.3.6.1.4.1.318.1.1.1.7.2.16
  1761. enum_values:
  1762. 1: never
  1763. 2: weekly
  1764. 3: biweekly
  1765. 4: every4weeks
  1766. 5: every8weeks
  1767. 6: every12weeks
  1768. 7: every26weeks
  1769. 8: every52weeks
  1770. - name: upsCommStatus
  1771. oid: 1.3.6.1.4.1.318.1.1.1.8.1
  1772. type: gauge
  1773. help: The status of agent's communication with UPS. - 1.3.6.1.4.1.318.1.1.1.8.1
  1774. enum_values:
  1775. 1: ok
  1776. 2: noComm
  1777. - name: iemStatusProbeNumber
  1778. oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.1
  1779. type: gauge
  1780. help: The index of the probe. - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.1
  1781. indexes:
  1782. - labelname: iemStatusProbeNumber
  1783. type: gauge
  1784. - name: iemStatusProbeName
  1785. oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.2
  1786. type: DisplayString
  1787. help: A descriptive name for the probe set by the user. - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.2
  1788. indexes:
  1789. - labelname: iemStatusProbeNumber
  1790. type: gauge
  1791. - name: iemStatusProbeStatus
  1792. oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.3
  1793. type: gauge
  1794. help: The connected status of the probe, either disconnected(1) or connected(2).
  1795. - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.3
  1796. indexes:
  1797. - labelname: iemStatusProbeNumber
  1798. type: gauge
  1799. enum_values:
  1800. 1: disconnected
  1801. 2: connected
  1802. - name: iemStatusProbeCurrentTemp
  1803. oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.4
  1804. type: gauge
  1805. help: The current temperature reading from the probe displayed in the units
  1806. shown in the 'iemStatusProbeTempUnits' OID (Celsius or Fahrenheit). - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.4
  1807. indexes:
  1808. - labelname: iemStatusProbeNumber
  1809. type: gauge
  1810. - name: iemStatusProbeTempUnits
  1811. oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.5
  1812. type: gauge
  1813. help: The temperature scale used to display the temperature thresholds of the
  1814. probe, Celsius(1) or Fahrenheit(2) - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.5
  1815. indexes:
  1816. - labelname: iemStatusProbeNumber
  1817. type: gauge
  1818. enum_values:
  1819. 1: celsius
  1820. 2: fahrenheit
  1821. - name: iemStatusProbeCurrentHumid
  1822. oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.6
  1823. type: gauge
  1824. help: The current humidity reading from the probe in percent relative humidity.
  1825. - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.6
  1826. indexes:
  1827. - labelname: iemStatusProbeNumber
  1828. type: gauge
  1829. - name: iemStatusProbeHighTempViolation
  1830. oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.7
  1831. type: gauge
  1832. help: The high temperature violation status of the probe temperature reading
  1833. - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.7
  1834. indexes:
  1835. - labelname: iemStatusProbeNumber
  1836. type: gauge
  1837. enum_values:
  1838. 1: noViolation
  1839. 2: highTempViolation
  1840. 3: disabled
  1841. - name: iemStatusProbeLowTempViolation
  1842. oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.8
  1843. type: gauge
  1844. help: The high temperature violation status of the probe temperature reading
  1845. - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.8
  1846. indexes:
  1847. - labelname: iemStatusProbeNumber
  1848. type: gauge
  1849. enum_values:
  1850. 1: noViolation
  1851. 2: lowTempViolation
  1852. 3: disabled
  1853. - name: iemStatusProbeHighHumidViolation
  1854. oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.9
  1855. type: gauge
  1856. help: The high humidity violation status of the probe humidity reading - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.9
  1857. indexes:
  1858. - labelname: iemStatusProbeNumber
  1859. type: gauge
  1860. enum_values:
  1861. 1: noViolation
  1862. 2: highHumidViolation
  1863. 3: disabled
  1864. - name: iemStatusProbeLowHumidViolation
  1865. oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.10
  1866. type: gauge
  1867. help: The low humidity violation status of the probe humidity reading - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.10
  1868. indexes:
  1869. - labelname: iemStatusProbeNumber
  1870. type: gauge
  1871. enum_values:
  1872. 1: noViolation
  1873. 2: lowHumidViolation
  1874. 3: disabled
  1875. - name: iemStatusProbeMaxTempViolation
  1876. oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.11
  1877. type: gauge
  1878. help: The max temperature violation status of the probe temperature reading
  1879. - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.11
  1880. indexes:
  1881. - labelname: iemStatusProbeNumber
  1882. type: gauge
  1883. enum_values:
  1884. 1: noViolation
  1885. 2: maxTempViolation
  1886. 3: disabled
  1887. - name: iemStatusProbeMinTempViolation
  1888. oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.12
  1889. type: gauge
  1890. help: The minimum temperature violation status of the probe temperature reading
  1891. - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.12
  1892. indexes:
  1893. - labelname: iemStatusProbeNumber
  1894. type: gauge
  1895. enum_values:
  1896. 1: noViolation
  1897. 2: minTempViolation
  1898. 3: disabled
  1899. - name: iemStatusProbeMaxHumidViolation
  1900. oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.13
  1901. type: gauge
  1902. help: The maximum humidity violation status of the probe humidity reading -
  1903. 1.3.6.1.4.1.318.1.1.10.2.3.2.1.13
  1904. indexes:
  1905. - labelname: iemStatusProbeNumber
  1906. type: gauge
  1907. enum_values:
  1908. 1: noViolation
  1909. 2: maxHumidViolation
  1910. 3: disabled
  1911. - name: iemStatusProbeMinHumidViolation
  1912. oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.14
  1913. type: gauge
  1914. help: The minimum humidity violation status of the probe humidity reading -
  1915. 1.3.6.1.4.1.318.1.1.10.2.3.2.1.14
  1916. indexes:
  1917. - labelname: iemStatusProbeNumber
  1918. type: gauge
  1919. enum_values:
  1920. 1: noViolation
  1921. 2: minHumidViolation
  1922. 3: disabled
  1923. - name: iemStatusProbeLocation
  1924. oid: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.15
  1925. type: DisplayString
  1926. help: A descriptive location for the probe set by the user. - 1.3.6.1.4.1.318.1.1.10.2.3.2.1.15
  1927. indexes:
  1928. - labelname: iemStatusProbeNumber
  1929. type: gauge
  1930. - name: rPDU2SensorTempHumidityStatusIndex
  1931. oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.1
  1932. type: gauge
  1933. help: The index to the temperature-humidity status data table entry - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.1
  1934. indexes:
  1935. - labelname: rPDU2SensorTempHumidityStatusIndex
  1936. type: gauge
  1937. - name: rPDU2SensorTempHumidityStatusModule
  1938. oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.2
  1939. type: gauge
  1940. help: The user-defined Rack PDU numeric ID - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.2
  1941. indexes:
  1942. - labelname: rPDU2SensorTempHumidityStatusIndex
  1943. type: gauge
  1944. - name: rPDU2SensorTempHumidityStatusName
  1945. oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.3
  1946. type: DisplayString
  1947. help: The user-defined temperature-humidity sensor ID string - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.3
  1948. indexes:
  1949. - labelname: rPDU2SensorTempHumidityStatusIndex
  1950. type: gauge
  1951. - name: rPDU2SensorTempHumidityStatusNumber
  1952. oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.4
  1953. type: gauge
  1954. help: The temperature-humidity sensor numeric ID - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.4
  1955. indexes:
  1956. - labelname: rPDU2SensorTempHumidityStatusIndex
  1957. type: gauge
  1958. - name: rPDU2SensorTempHumidityStatusType
  1959. oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.5
  1960. type: gauge
  1961. help: The type of the sensor - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.5
  1962. indexes:
  1963. - labelname: rPDU2SensorTempHumidityStatusIndex
  1964. type: gauge
  1965. enum_values:
  1966. 1: temperatureOnly
  1967. 2: temperatureHumidity
  1968. 3: commsLost
  1969. 4: notInstalled
  1970. - name: rPDU2SensorTempHumidityStatusCommStatus
  1971. oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.6
  1972. type: gauge
  1973. help: The communications status of the sensor - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.6
  1974. indexes:
  1975. - labelname: rPDU2SensorTempHumidityStatusIndex
  1976. type: gauge
  1977. enum_values:
  1978. 1: notInstalled
  1979. 2: commsOK
  1980. 3: commsLost
  1981. - name: rPDU2SensorTempHumidityStatusTempF
  1982. oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.7
  1983. type: gauge
  1984. help: Sensor temperature reading in tenths of degrees Fahrenheit - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.7
  1985. indexes:
  1986. - labelname: rPDU2SensorTempHumidityStatusIndex
  1987. type: gauge
  1988. - name: rPDU2SensorTempHumidityStatusTempC
  1989. oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.8
  1990. type: gauge
  1991. help: Sensor temperature reading in tenths of degrees Celsius - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.8
  1992. indexes:
  1993. - labelname: rPDU2SensorTempHumidityStatusIndex
  1994. type: gauge
  1995. - name: rPDU2SensorTempHumidityStatusTempStatus
  1996. oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.9
  1997. type: gauge
  1998. help: This OID reports the current state of the temperature probe - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.9
  1999. indexes:
  2000. - labelname: rPDU2SensorTempHumidityStatusIndex
  2001. type: gauge
  2002. enum_values:
  2003. 1: notPresent
  2004. 2: belowMin
  2005. 3: belowLow
  2006. 4: normal
  2007. 5: aboveHigh
  2008. 6: aboveMax
  2009. - name: rPDU2SensorTempHumidityStatusRelativeHumidity
  2010. oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.10
  2011. type: gauge
  2012. help: Sensor humidity reading in percent relative humidity - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.10
  2013. indexes:
  2014. - labelname: rPDU2SensorTempHumidityStatusIndex
  2015. type: gauge
  2016. - name: rPDU2SensorTempHumidityStatusHumidityStatus
  2017. oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.11
  2018. type: gauge
  2019. help: This OID reports the current state of the humidity probe - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.11
  2020. indexes:
  2021. - labelname: rPDU2SensorTempHumidityStatusIndex
  2022. type: gauge
  2023. enum_values:
  2024. 1: notPresent
  2025. 2: belowMin
  2026. 3: belowLow
  2027. 4: normal
  2028. 5: aboveHigh
  2029. 6: aboveMax
  2030. - name: rPDU2SensorTempHumidityStatusTempPeakF
  2031. oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.12
  2032. type: gauge
  2033. help: Sensor peak temperature in tenths of degrees Fahrenheit - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.12
  2034. indexes:
  2035. - labelname: rPDU2SensorTempHumidityStatusIndex
  2036. type: gauge
  2037. - name: rPDU2SensorTempHumidityStatusTempPeakC
  2038. oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.13
  2039. type: gauge
  2040. help: Sensor peak temperature in tenths of degrees Celsius - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.13
  2041. indexes:
  2042. - labelname: rPDU2SensorTempHumidityStatusIndex
  2043. type: gauge
  2044. - name: rPDU2SensorTempHumidityStatusTempPeakTimestamp
  2045. oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.14
  2046. type: DisplayString
  2047. help: Indicates the date and time that the peak temperature occurred - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.14
  2048. indexes:
  2049. - labelname: rPDU2SensorTempHumidityStatusIndex
  2050. type: gauge
  2051. - name: rPDU2SensorTempHumidityStatusTempPeakStartTime
  2052. oid: 1.3.6.1.4.1.318.1.1.26.10.2.2.1.15
  2053. type: DisplayString
  2054. help: Indicates the date and time of the last temperature peak reset - 1.3.6.1.4.1.318.1.1.26.10.2.2.1.15
  2055. indexes:
  2056. - labelname: rPDU2SensorTempHumidityStatusIndex
  2057. type: gauge
  2058. - name: rPDU2DeviceStatusIndex
  2059. oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.1
  2060. type: gauge
  2061. help: The index to the Rack PDU status table entry - 1.3.6.1.4.1.318.1.1.26.4.3.1.1
  2062. indexes:
  2063. - labelname: rPDU2DeviceStatusIndex
  2064. type: gauge
  2065. - name: rPDU2DeviceStatusModule
  2066. oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.2
  2067. type: gauge
  2068. help: The user-defined Rack PDU numeric ID - 1.3.6.1.4.1.318.1.1.26.4.3.1.2
  2069. indexes:
  2070. - labelname: rPDU2DeviceStatusIndex
  2071. type: gauge
  2072. - name: rPDU2DeviceStatusName
  2073. oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.3
  2074. type: DisplayString
  2075. help: A user-defined string identifying the Rack PDU - 1.3.6.1.4.1.318.1.1.26.4.3.1.3
  2076. indexes:
  2077. - labelname: rPDU2DeviceStatusIndex
  2078. type: gauge
  2079. - name: rPDU2DeviceStatusLoadState
  2080. oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.4
  2081. type: gauge
  2082. help: Indicates the present load status of the Rack PDU - 1.3.6.1.4.1.318.1.1.26.4.3.1.4
  2083. indexes:
  2084. - labelname: rPDU2DeviceStatusIndex
  2085. type: gauge
  2086. enum_values:
  2087. 1: lowLoad
  2088. 2: normal
  2089. 3: nearOverload
  2090. 4: overload
  2091. 5: notsupported
  2092. - name: rPDU2DeviceStatusPower
  2093. oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.5
  2094. type: gauge
  2095. help: The power consumption of the Rack PDU load in hundredths of kilowatts
  2096. - 1.3.6.1.4.1.318.1.1.26.4.3.1.5
  2097. indexes:
  2098. - labelname: rPDU2DeviceStatusIndex
  2099. type: gauge
  2100. - name: rPDU2DeviceStatusPeakPower
  2101. oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.6
  2102. type: gauge
  2103. help: The peak power consumption of the Rack PDU load in hundredths of kilowatts
  2104. - 1.3.6.1.4.1.318.1.1.26.4.3.1.6
  2105. indexes:
  2106. - labelname: rPDU2DeviceStatusIndex
  2107. type: gauge
  2108. - name: rPDU2DeviceStatusPeakPowerTimestamp
  2109. oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.7
  2110. type: DisplayString
  2111. help: Indicates the date and time that peak power consumption occurred - 1.3.6.1.4.1.318.1.1.26.4.3.1.7
  2112. indexes:
  2113. - labelname: rPDU2DeviceStatusIndex
  2114. type: gauge
  2115. - name: rPDU2DeviceStatusPeakPowerStartTime
  2116. oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.8
  2117. type: DisplayString
  2118. help: Indicates the date and time of the last device peak power reset - 1.3.6.1.4.1.318.1.1.26.4.3.1.8
  2119. indexes:
  2120. - labelname: rPDU2DeviceStatusIndex
  2121. type: gauge
  2122. - name: rPDU2DeviceStatusEnergy
  2123. oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.9
  2124. type: gauge
  2125. help: A user resettable energy meter measuring Rack PDU load energy consumption
  2126. in tenths of kilowatt-hours - 1.3.6.1.4.1.318.1.1.26.4.3.1.9
  2127. indexes:
  2128. - labelname: rPDU2DeviceStatusIndex
  2129. type: gauge
  2130. - name: rPDU2DeviceStatusEnergyStartTime
  2131. oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.10
  2132. type: DisplayString
  2133. help: Indicates the date and time of the last device energy meter reset - 1.3.6.1.4.1.318.1.1.26.4.3.1.10
  2134. indexes:
  2135. - labelname: rPDU2DeviceStatusIndex
  2136. type: gauge
  2137. - name: rPDU2DeviceStatusCommandPending
  2138. oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.11
  2139. type: gauge
  2140. help: Indicates whether or not the device is processing a pending command -
  2141. 1.3.6.1.4.1.318.1.1.26.4.3.1.11
  2142. indexes:
  2143. - labelname: rPDU2DeviceStatusIndex
  2144. type: gauge
  2145. enum_values:
  2146. 1: commandPending
  2147. 2: noCommandPending
  2148. 3: commandPendingUnknown
  2149. - name: rPDU2DeviceStatusPowerSupplyAlarm
  2150. oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.12
  2151. type: gauge
  2152. help: Indicates a power supply alarm is active when value equals alarm (2) -
  2153. 1.3.6.1.4.1.318.1.1.26.4.3.1.12
  2154. indexes:
  2155. - labelname: rPDU2DeviceStatusIndex
  2156. type: gauge
  2157. enum_values:
  2158. 1: normal
  2159. 2: alarm
  2160. - name: rPDU2DeviceStatusPowerSupply1Status
  2161. oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.13
  2162. type: gauge
  2163. help: Indicates whether or not an alarm is active in Power Supply 1 - 1.3.6.1.4.1.318.1.1.26.4.3.1.13
  2164. indexes:
  2165. - labelname: rPDU2DeviceStatusIndex
  2166. type: gauge
  2167. enum_values:
  2168. 1: normal
  2169. 2: alarm
  2170. 3: notInstalled
  2171. - name: rPDU2DeviceStatusPowerSupply2Status
  2172. oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.14
  2173. type: gauge
  2174. help: Indicates whether or not an alarm is active in Power Supply 2 - 1.3.6.1.4.1.318.1.1.26.4.3.1.14
  2175. indexes:
  2176. - labelname: rPDU2DeviceStatusIndex
  2177. type: gauge
  2178. enum_values:
  2179. 1: normal
  2180. 2: alarm
  2181. 3: notInstalled
  2182. - name: rPDU2DeviceStatusOutletsEnergyStartTime
  2183. oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.15
  2184. type: DisplayString
  2185. help: Indicates the date and time of the last outlets energy meter reset - 1.3.6.1.4.1.318.1.1.26.4.3.1.15
  2186. indexes:
  2187. - labelname: rPDU2DeviceStatusIndex
  2188. type: gauge
  2189. - name: rPDU2DeviceStatusApparentPower
  2190. oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.16
  2191. type: gauge
  2192. help: The apparent power consumption of the Rack PDU load in hundredths of kiloVoltAmps
  2193. (kVA) - 1.3.6.1.4.1.318.1.1.26.4.3.1.16
  2194. indexes:
  2195. - labelname: rPDU2DeviceStatusIndex
  2196. type: gauge
  2197. - name: rPDU2DeviceStatusPowerFactor
  2198. oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.17
  2199. type: gauge
  2200. help: The power factor of the Rack PDU load in hundredths - 1.3.6.1.4.1.318.1.1.26.4.3.1.17
  2201. indexes:
  2202. - labelname: rPDU2DeviceStatusIndex
  2203. type: gauge
  2204. - name: rPDU2DeviceStatusNPSType
  2205. oid: 1.3.6.1.4.1.318.1.1.26.4.3.1.18
  2206. type: gauge
  2207. help: 'The device NPS status: notNPS (1) indicates the Rack PDU is not in an
  2208. NPS group - 1.3.6.1.4.1.318.1.1.26.4.3.1.18'
  2209. indexes:
  2210. - labelname: rPDU2DeviceStatusIndex
  2211. type: gauge
  2212. enum_values:
  2213. 1: notNPS
  2214. 2: host
  2215. 3: guest
  2216. - name: rPDU2PhaseStatusIndex
  2217. oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.1
  2218. type: gauge
  2219. help: The index to the Rack PDU phase status table entry - 1.3.6.1.4.1.318.1.1.26.6.3.1.1
  2220. indexes:
  2221. - labelname: rPDU2PhaseStatusIndex
  2222. type: gauge
  2223. - name: rPDU2PhaseStatusModule
  2224. oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.2
  2225. type: gauge
  2226. help: The user-defined Rack PDU numeric ID - 1.3.6.1.4.1.318.1.1.26.6.3.1.2
  2227. indexes:
  2228. - labelname: rPDU2PhaseStatusIndex
  2229. type: gauge
  2230. - name: rPDU2PhaseStatusNumber
  2231. oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.3
  2232. type: gauge
  2233. help: The numeric phase ID - 1.3.6.1.4.1.318.1.1.26.6.3.1.3
  2234. indexes:
  2235. - labelname: rPDU2PhaseStatusIndex
  2236. type: gauge
  2237. - name: rPDU2PhaseStatusLoadState
  2238. oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.4
  2239. type: gauge
  2240. help: Indicates the present load status of the Rack PDU phase being queried
  2241. - 1.3.6.1.4.1.318.1.1.26.6.3.1.4
  2242. indexes:
  2243. - labelname: rPDU2PhaseStatusIndex
  2244. type: gauge
  2245. enum_values:
  2246. 1: lowLoad
  2247. 2: normal
  2248. 3: nearOverload
  2249. 4: overload
  2250. - name: rPDU2PhaseStatusCurrent
  2251. oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.5
  2252. type: gauge
  2253. help: Indicates the current draw, in tenths of Amps, of the load on the Rack
  2254. PDU phase being queried - 1.3.6.1.4.1.318.1.1.26.6.3.1.5
  2255. indexes:
  2256. - labelname: rPDU2PhaseStatusIndex
  2257. type: gauge
  2258. - name: rPDU2PhaseStatusVoltage
  2259. oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.6
  2260. type: gauge
  2261. help: Indicates the Voltage, in Volts, of the Rack PDU phase being queried -
  2262. 1.3.6.1.4.1.318.1.1.26.6.3.1.6
  2263. indexes:
  2264. - labelname: rPDU2PhaseStatusIndex
  2265. type: gauge
  2266. - name: rPDU2PhaseStatusPower
  2267. oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.7
  2268. type: gauge
  2269. help: Indicates the load power, in hundredths of kilowatts (kW), consumed on
  2270. the Rack PDU phase being queried - 1.3.6.1.4.1.318.1.1.26.6.3.1.7
  2271. indexes:
  2272. - labelname: rPDU2PhaseStatusIndex
  2273. type: gauge
  2274. - name: rPDU2PhaseStatusApparentPower
  2275. oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.8
  2276. type: gauge
  2277. help: Indicates the load apparent power, in hundredths of kiloVoltAmps (kVA),
  2278. consumed on the Rack PDU phase being queried - 1.3.6.1.4.1.318.1.1.26.6.3.1.8
  2279. indexes:
  2280. - labelname: rPDU2PhaseStatusIndex
  2281. type: gauge
  2282. - name: rPDU2PhaseStatusPowerFactor
  2283. oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.9
  2284. type: gauge
  2285. help: Indicates the load power factor, in hundredths, of the Rack PDU phase
  2286. being queried - 1.3.6.1.4.1.318.1.1.26.6.3.1.9
  2287. indexes:
  2288. - labelname: rPDU2PhaseStatusIndex
  2289. type: gauge
  2290. - name: rPDU2PhaseStatusPeakCurrent
  2291. oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.10
  2292. type: gauge
  2293. help: The peak current of the Rack PDU phase load in tenths of Amps - 1.3.6.1.4.1.318.1.1.26.6.3.1.10
  2294. indexes:
  2295. - labelname: rPDU2PhaseStatusIndex
  2296. type: gauge
  2297. - name: rPDU2PhaseStatusPeakCurrentTimestamp
  2298. oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.11
  2299. type: DisplayString
  2300. help: Indicates the date and time that the peak current occurred - 1.3.6.1.4.1.318.1.1.26.6.3.1.11
  2301. indexes:
  2302. - labelname: rPDU2PhaseStatusIndex
  2303. type: gauge
  2304. - name: rPDU2PhaseStatusPeakCurrentStartTime
  2305. oid: 1.3.6.1.4.1.318.1.1.26.6.3.1.12
  2306. type: DisplayString
  2307. help: Indicates the date and time of the last phase peak current reset - 1.3.6.1.4.1.318.1.1.26.6.3.1.12
  2308. indexes:
  2309. - labelname: rPDU2PhaseStatusIndex
  2310. type: gauge
  2311. - name: rPDU2BankStatusIndex
  2312. oid: 1.3.6.1.4.1.318.1.1.26.8.3.1.1
  2313. type: gauge
  2314. help: The index to the Rack PDU bank status table entry - 1.3.6.1.4.1.318.1.1.26.8.3.1.1
  2315. indexes:
  2316. - labelname: rPDU2BankStatusIndex
  2317. type: gauge
  2318. - name: rPDU2BankStatusModule
  2319. oid: 1.3.6.1.4.1.318.1.1.26.8.3.1.2
  2320. type: gauge
  2321. help: The user-defined Rack PDU numeric ID - 1.3.6.1.4.1.318.1.1.26.8.3.1.2
  2322. indexes:
  2323. - labelname: rPDU2BankStatusIndex
  2324. type: gauge
  2325. - name: rPDU2BankStatusNumber
  2326. oid: 1.3.6.1.4.1.318.1.1.26.8.3.1.3
  2327. type: gauge
  2328. help: The numeric bank ID - 1.3.6.1.4.1.318.1.1.26.8.3.1.3
  2329. indexes:
  2330. - labelname: rPDU2BankStatusIndex
  2331. type: gauge
  2332. - name: rPDU2BankStatusLoadState
  2333. oid: 1.3.6.1.4.1.318.1.1.26.8.3.1.4
  2334. type: EnumAsStateSet
  2335. help: Indicates the present load status of the Rack PDU bank being queried -
  2336. 1.3.6.1.4.1.318.1.1.26.8.3.1.4
  2337. indexes:
  2338. - labelname: rPDU2BankStatusIndex
  2339. type: gauge
  2340. enum_values:
  2341. 1: lowLoad
  2342. 2: normal
  2343. 3: nearOverload
  2344. 4: overload
  2345. - name: rPDU2BankStatusCurrent
  2346. oid: 1.3.6.1.4.1.318.1.1.26.8.3.1.5
  2347. type: gauge
  2348. help: Indicates the current draw, in tenths of Amps, of the load on the Rack
  2349. PDU bank being queried - 1.3.6.1.4.1.318.1.1.26.8.3.1.5
  2350. indexes:
  2351. - labelname: rPDU2BankStatusIndex
  2352. type: gauge
  2353. - name: rPDU2BankStatusPeakCurrent
  2354. oid: 1.3.6.1.4.1.318.1.1.26.8.3.1.6
  2355. type: gauge
  2356. help: The peak current of the Rack PDU bank load in tenths of Amps - 1.3.6.1.4.1.318.1.1.26.8.3.1.6
  2357. indexes:
  2358. - labelname: rPDU2BankStatusIndex
  2359. type: gauge
  2360. - name: rPDU2BankStatusPeakCurrentTimestamp
  2361. oid: 1.3.6.1.4.1.318.1.1.26.8.3.1.7
  2362. type: DisplayString
  2363. help: Indicates the date and time the bank peak current occurred - 1.3.6.1.4.1.318.1.1.26.8.3.1.7
  2364. indexes:
  2365. - labelname: rPDU2BankStatusIndex
  2366. type: gauge
  2367. - name: rPDU2BankStatusPeakCurrentStartTime
  2368. oid: 1.3.6.1.4.1.318.1.1.26.8.3.1.8
  2369. type: DisplayString
  2370. help: Indicates the date and time of the last bank peak current reset - 1.3.6.1.4.1.318.1.1.26.8.3.1.8
  2371. indexes:
  2372. - labelname: rPDU2BankStatusIndex
  2373. type: gauge
  2374. if_mib:
  2375. walk:
  2376. - 1.3.6.1.2.1.2
  2377. - 1.3.6.1.2.1.31.1.1
  2378. get:
  2379. - 1.3.6.1.2.1.1.3.0
  2380. metrics:
  2381. - name: sysUpTime
  2382. oid: 1.3.6.1.2.1.1.3
  2383. type: gauge
  2384. help: The time (in hundredths of a second) since the network management portion
  2385. of the system was last re-initialized. - 1.3.6.1.2.1.1.3
  2386. - name: ifNumber
  2387. oid: 1.3.6.1.2.1.2.1
  2388. type: gauge
  2389. help: The number of network interfaces (regardless of their current state) present
  2390. on this system. - 1.3.6.1.2.1.2.1
  2391. - name: ifIndex
  2392. oid: 1.3.6.1.2.1.2.2.1.1
  2393. type: gauge
  2394. help: A unique value, greater than zero, for each interface - 1.3.6.1.2.1.2.2.1.1
  2395. indexes:
  2396. - labelname: ifIndex
  2397. type: gauge
  2398. lookups:
  2399. - labels:
  2400. - ifIndex
  2401. labelname: ifAlias
  2402. oid: 1.3.6.1.2.1.31.1.1.1.18
  2403. type: DisplayString
  2404. - labels:
  2405. - ifIndex
  2406. labelname: ifDescr
  2407. oid: 1.3.6.1.2.1.2.2.1.2
  2408. type: DisplayString
  2409. - labels:
  2410. - ifIndex
  2411. labelname: ifName
  2412. oid: 1.3.6.1.2.1.31.1.1.1.1
  2413. type: DisplayString
  2414. - name: ifType
  2415. oid: 1.3.6.1.2.1.2.2.1.3
  2416. type: EnumAsInfo
  2417. help: The type of interface - 1.3.6.1.2.1.2.2.1.3
  2418. indexes:
  2419. - labelname: ifIndex
  2420. type: gauge
  2421. lookups:
  2422. - labels:
  2423. - ifIndex
  2424. labelname: ifAlias
  2425. oid: 1.3.6.1.2.1.31.1.1.1.18
  2426. type: DisplayString
  2427. - labels:
  2428. - ifIndex
  2429. labelname: ifDescr
  2430. oid: 1.3.6.1.2.1.2.2.1.2
  2431. type: DisplayString
  2432. - labels:
  2433. - ifIndex
  2434. labelname: ifName
  2435. oid: 1.3.6.1.2.1.31.1.1.1.1
  2436. type: DisplayString
  2437. enum_values:
  2438. 1: other
  2439. 2: regular1822
  2440. 3: hdh1822
  2441. 4: ddnX25
  2442. 5: rfc877x25
  2443. 6: ethernetCsmacd
  2444. 7: iso88023Csmacd
  2445. 8: iso88024TokenBus
  2446. 9: iso88025TokenRing
  2447. 10: iso88026Man
  2448. 11: starLan
  2449. 12: proteon10Mbit
  2450. 13: proteon80Mbit
  2451. 14: hyperchannel
  2452. 15: fddi
  2453. 16: lapb
  2454. 17: sdlc
  2455. 18: ds1
  2456. 19: e1
  2457. 20: basicISDN
  2458. 21: primaryISDN
  2459. 22: propPointToPointSerial
  2460. 23: ppp
  2461. 24: softwareLoopback
  2462. 25: eon
  2463. 26: ethernet3Mbit
  2464. 27: nsip
  2465. 28: slip
  2466. 29: ultra
  2467. 30: ds3
  2468. 31: sip
  2469. 32: frameRelay
  2470. 33: rs232
  2471. 34: para
  2472. 35: arcnet
  2473. 36: arcnetPlus
  2474. 37: atm
  2475. 38: miox25
  2476. 39: sonet
  2477. 40: x25ple
  2478. 41: iso88022llc
  2479. 42: localTalk
  2480. 43: smdsDxi
  2481. 44: frameRelayService
  2482. 45: v35
  2483. 46: hssi
  2484. 47: hippi
  2485. 48: modem
  2486. 49: aal5
  2487. 50: sonetPath
  2488. 51: sonetVT
  2489. 52: smdsIcip
  2490. 53: propVirtual
  2491. 54: propMultiplexor
  2492. 55: ieee80212
  2493. 56: fibreChannel
  2494. 57: hippiInterface
  2495. 58: frameRelayInterconnect
  2496. 59: aflane8023
  2497. 60: aflane8025
  2498. 61: cctEmul
  2499. 62: fastEther
  2500. 63: isdn
  2501. 64: v11
  2502. 65: v36
  2503. 66: g703at64k
  2504. 67: g703at2mb
  2505. 68: qllc
  2506. 69: fastEtherFX
  2507. 70: channel
  2508. 71: ieee80211
  2509. 72: ibm370parChan
  2510. 73: escon
  2511. 74: dlsw
  2512. 75: isdns
  2513. 76: isdnu
  2514. 77: lapd
  2515. 78: ipSwitch
  2516. 79: rsrb
  2517. 80: atmLogical
  2518. 81: ds0
  2519. 82: ds0Bundle
  2520. 83: bsc
  2521. 84: async
  2522. 85: cnr
  2523. 86: iso88025Dtr
  2524. 87: eplrs
  2525. 88: arap
  2526. 89: propCnls
  2527. 90: hostPad
  2528. 91: termPad
  2529. 92: frameRelayMPI
  2530. 93: x213
  2531. 94: adsl
  2532. 95: radsl
  2533. 96: sdsl
  2534. 97: vdsl
  2535. 98: iso88025CRFPInt
  2536. 99: myrinet
  2537. 100: voiceEM
  2538. 101: voiceFXO
  2539. 102: voiceFXS
  2540. 103: voiceEncap
  2541. 104: voiceOverIp
  2542. 105: atmDxi
  2543. 106: atmFuni
  2544. 107: atmIma
  2545. 108: pppMultilinkBundle
  2546. 109: ipOverCdlc
  2547. 110: ipOverClaw
  2548. 111: stackToStack
  2549. 112: virtualIpAddress
  2550. 113: mpc
  2551. 114: ipOverAtm
  2552. 115: iso88025Fiber
  2553. 116: tdlc
  2554. 117: gigabitEthernet
  2555. 118: hdlc
  2556. 119: lapf
  2557. 120: v37
  2558. 121: x25mlp
  2559. 122: x25huntGroup
  2560. 123: transpHdlc
  2561. 124: interleave
  2562. 125: fast
  2563. 126: ip
  2564. 127: docsCableMaclayer
  2565. 128: docsCableDownstream
  2566. 129: docsCableUpstream
  2567. 130: a12MppSwitch
  2568. 131: tunnel
  2569. 132: coffee
  2570. 133: ces
  2571. 134: atmSubInterface
  2572. 135: l2vlan
  2573. 136: l3ipvlan
  2574. 137: l3ipxvlan
  2575. 138: digitalPowerline
  2576. 139: mediaMailOverIp
  2577. 140: dtm
  2578. 141: dcn
  2579. 142: ipForward
  2580. 143: msdsl
  2581. 144: ieee1394
  2582. 145: if-gsn
  2583. 146: dvbRccMacLayer
  2584. 147: dvbRccDownstream
  2585. 148: dvbRccUpstream
  2586. 149: atmVirtual
  2587. 150: mplsTunnel
  2588. 151: srp
  2589. 152: voiceOverAtm
  2590. 153: voiceOverFrameRelay
  2591. 154: idsl
  2592. 155: compositeLink
  2593. 156: ss7SigLink
  2594. 157: propWirelessP2P
  2595. 158: frForward
  2596. 159: rfc1483
  2597. 160: usb
  2598. 161: ieee8023adLag
  2599. 162: bgppolicyaccounting
  2600. 163: frf16MfrBundle
  2601. 164: h323Gatekeeper
  2602. 165: h323Proxy
  2603. 166: mpls
  2604. 167: mfSigLink
  2605. 168: hdsl2
  2606. 169: shdsl
  2607. 170: ds1FDL
  2608. 171: pos
  2609. 172: dvbAsiIn
  2610. 173: dvbAsiOut
  2611. 174: plc
  2612. 175: nfas
  2613. 176: tr008
  2614. 177: gr303RDT
  2615. 178: gr303IDT
  2616. 179: isup
  2617. 180: propDocsWirelessMaclayer
  2618. 181: propDocsWirelessDownstream
  2619. 182: propDocsWirelessUpstream
  2620. 183: hiperlan2
  2621. 184: propBWAp2Mp
  2622. 185: sonetOverheadChannel
  2623. 186: digitalWrapperOverheadChannel
  2624. 187: aal2
  2625. 188: radioMAC
  2626. 189: atmRadio
  2627. 190: imt
  2628. 191: mvl
  2629. 192: reachDSL
  2630. 193: frDlciEndPt
  2631. 194: atmVciEndPt
  2632. 195: opticalChannel
  2633. 196: opticalTransport
  2634. 197: propAtm
  2635. 198: voiceOverCable
  2636. 199: infiniband
  2637. 200: teLink
  2638. 201: q2931
  2639. 202: virtualTg
  2640. 203: sipTg
  2641. 204: sipSig
  2642. 205: docsCableUpstreamChannel
  2643. 206: econet
  2644. 207: pon155
  2645. 208: pon622
  2646. 209: bridge
  2647. 210: linegroup
  2648. 211: voiceEMFGD
  2649. 212: voiceFGDEANA
  2650. 213: voiceDID
  2651. 214: mpegTransport
  2652. 215: sixToFour
  2653. 216: gtp
  2654. 217: pdnEtherLoop1
  2655. 218: pdnEtherLoop2
  2656. 219: opticalChannelGroup
  2657. 220: homepna
  2658. 221: gfp
  2659. 222: ciscoISLvlan
  2660. 223: actelisMetaLOOP
  2661. 224: fcipLink
  2662. 225: rpr
  2663. 226: qam
  2664. 227: lmp
  2665. 228: cblVectaStar
  2666. 229: docsCableMCmtsDownstream
  2667. 230: adsl2
  2668. 231: macSecControlledIF
  2669. 232: macSecUncontrolledIF
  2670. 233: aviciOpticalEther
  2671. 234: atmbond
  2672. 235: voiceFGDOS
  2673. 236: mocaVersion1
  2674. 237: ieee80216WMAN
  2675. 238: adsl2plus
  2676. 239: dvbRcsMacLayer
  2677. 240: dvbTdm
  2678. 241: dvbRcsTdma
  2679. 242: x86Laps
  2680. 243: wwanPP
  2681. 244: wwanPP2
  2682. 245: voiceEBS
  2683. 246: ifPwType
  2684. 247: ilan
  2685. 248: pip
  2686. 249: aluELP
  2687. 250: gpon
  2688. 251: vdsl2
  2689. 252: capwapDot11Profile
  2690. 253: capwapDot11Bss
  2691. 254: capwapWtpVirtualRadio
  2692. 255: bits
  2693. 256: docsCableUpstreamRfPort
  2694. 257: cableDownstreamRfPort
  2695. 258: vmwareVirtualNic
  2696. 259: ieee802154
  2697. 260: otnOdu
  2698. 261: otnOtu
  2699. 262: ifVfiType
  2700. 263: g9981
  2701. 264: g9982
  2702. 265: g9983
  2703. 266: aluEpon
  2704. 267: aluEponOnu
  2705. 268: aluEponPhysicalUni
  2706. 269: aluEponLogicalLink
  2707. 270: aluGponOnu
  2708. 271: aluGponPhysicalUni
  2709. 272: vmwareNicTeam
  2710. 277: docsOfdmDownstream
  2711. 278: docsOfdmaUpstream
  2712. 279: gfast
  2713. 280: sdci
  2714. 281: xboxWireless
  2715. 282: fastdsl
  2716. 283: docsCableScte55d1FwdOob
  2717. 284: docsCableScte55d1RetOob
  2718. 285: docsCableScte55d2DsOob
  2719. 286: docsCableScte55d2UsOob
  2720. 287: docsCableNdf
  2721. 288: docsCableNdr
  2722. 289: ptm
  2723. 290: ghn
  2724. 291: otnOtsi
  2725. 292: otnOtuc
  2726. 293: otnOduc
  2727. 294: otnOtsig
  2728. 295: microwaveCarrierTermination
  2729. 296: microwaveRadioLinkTerminal
  2730. 297: ieee8021axDrni
  2731. 298: ax25
  2732. 299: ieee19061nanocom
  2733. 300: cpri
  2734. 301: omni
  2735. 302: roe
  2736. 303: p2pOverLan
  2737. - name: ifMtu
  2738. oid: 1.3.6.1.2.1.2.2.1.4
  2739. type: gauge
  2740. help: The size of the largest packet which can be sent/received on the interface,
  2741. specified in octets - 1.3.6.1.2.1.2.2.1.4
  2742. indexes:
  2743. - labelname: ifIndex
  2744. type: gauge
  2745. lookups:
  2746. - labels:
  2747. - ifIndex
  2748. labelname: ifAlias
  2749. oid: 1.3.6.1.2.1.31.1.1.1.18
  2750. type: DisplayString
  2751. - labels:
  2752. - ifIndex
  2753. labelname: ifDescr
  2754. oid: 1.3.6.1.2.1.2.2.1.2
  2755. type: DisplayString
  2756. - labels:
  2757. - ifIndex
  2758. labelname: ifName
  2759. oid: 1.3.6.1.2.1.31.1.1.1.1
  2760. type: DisplayString
  2761. - name: ifSpeed
  2762. oid: 1.3.6.1.2.1.2.2.1.5
  2763. type: gauge
  2764. help: An estimate of the interface's current bandwidth in bits per second -
  2765. 1.3.6.1.2.1.2.2.1.5
  2766. indexes:
  2767. - labelname: ifIndex
  2768. type: gauge
  2769. lookups:
  2770. - labels:
  2771. - ifIndex
  2772. labelname: ifAlias
  2773. oid: 1.3.6.1.2.1.31.1.1.1.18
  2774. type: DisplayString
  2775. - labels:
  2776. - ifIndex
  2777. labelname: ifDescr
  2778. oid: 1.3.6.1.2.1.2.2.1.2
  2779. type: DisplayString
  2780. - labels:
  2781. - ifIndex
  2782. labelname: ifName
  2783. oid: 1.3.6.1.2.1.31.1.1.1.1
  2784. type: DisplayString
  2785. - name: ifPhysAddress
  2786. oid: 1.3.6.1.2.1.2.2.1.6
  2787. type: PhysAddress48
  2788. help: The interface's address at its protocol sub-layer - 1.3.6.1.2.1.2.2.1.6
  2789. indexes:
  2790. - labelname: ifIndex
  2791. type: gauge
  2792. lookups:
  2793. - labels:
  2794. - ifIndex
  2795. labelname: ifAlias
  2796. oid: 1.3.6.1.2.1.31.1.1.1.18
  2797. type: DisplayString
  2798. - labels:
  2799. - ifIndex
  2800. labelname: ifDescr
  2801. oid: 1.3.6.1.2.1.2.2.1.2
  2802. type: DisplayString
  2803. - labels:
  2804. - ifIndex
  2805. labelname: ifName
  2806. oid: 1.3.6.1.2.1.31.1.1.1.1
  2807. type: DisplayString
  2808. - name: ifAdminStatus
  2809. oid: 1.3.6.1.2.1.2.2.1.7
  2810. type: gauge
  2811. help: The desired state of the interface - 1.3.6.1.2.1.2.2.1.7
  2812. indexes:
  2813. - labelname: ifIndex
  2814. type: gauge
  2815. lookups:
  2816. - labels:
  2817. - ifIndex
  2818. labelname: ifAlias
  2819. oid: 1.3.6.1.2.1.31.1.1.1.18
  2820. type: DisplayString
  2821. - labels:
  2822. - ifIndex
  2823. labelname: ifDescr
  2824. oid: 1.3.6.1.2.1.2.2.1.2
  2825. type: DisplayString
  2826. - labels:
  2827. - ifIndex
  2828. labelname: ifName
  2829. oid: 1.3.6.1.2.1.31.1.1.1.1
  2830. type: DisplayString
  2831. enum_values:
  2832. 1: up
  2833. 2: down
  2834. 3: testing
  2835. - name: ifOperStatus
  2836. oid: 1.3.6.1.2.1.2.2.1.8
  2837. type: gauge
  2838. help: The current operational state of the interface - 1.3.6.1.2.1.2.2.1.8
  2839. indexes:
  2840. - labelname: ifIndex
  2841. type: gauge
  2842. lookups:
  2843. - labels:
  2844. - ifIndex
  2845. labelname: ifAlias
  2846. oid: 1.3.6.1.2.1.31.1.1.1.18
  2847. type: DisplayString
  2848. - labels:
  2849. - ifIndex
  2850. labelname: ifDescr
  2851. oid: 1.3.6.1.2.1.2.2.1.2
  2852. type: DisplayString
  2853. - labels:
  2854. - ifIndex
  2855. labelname: ifName
  2856. oid: 1.3.6.1.2.1.31.1.1.1.1
  2857. type: DisplayString
  2858. enum_values:
  2859. 1: up
  2860. 2: down
  2861. 3: testing
  2862. 4: unknown
  2863. 5: dormant
  2864. 6: notPresent
  2865. 7: lowerLayerDown
  2866. - name: ifLastChange
  2867. oid: 1.3.6.1.2.1.2.2.1.9
  2868. type: gauge
  2869. help: The value of sysUpTime at the time the interface entered its current operational
  2870. state - 1.3.6.1.2.1.2.2.1.9
  2871. indexes:
  2872. - labelname: ifIndex
  2873. type: gauge
  2874. lookups:
  2875. - labels:
  2876. - ifIndex
  2877. labelname: ifAlias
  2878. oid: 1.3.6.1.2.1.31.1.1.1.18
  2879. type: DisplayString
  2880. - labels:
  2881. - ifIndex
  2882. labelname: ifDescr
  2883. oid: 1.3.6.1.2.1.2.2.1.2
  2884. type: DisplayString
  2885. - labels:
  2886. - ifIndex
  2887. labelname: ifName
  2888. oid: 1.3.6.1.2.1.31.1.1.1.1
  2889. type: DisplayString
  2890. - name: ifInOctets
  2891. oid: 1.3.6.1.2.1.2.2.1.10
  2892. type: counter
  2893. help: The total number of octets received on the interface, including framing
  2894. characters - 1.3.6.1.2.1.2.2.1.10
  2895. indexes:
  2896. - labelname: ifIndex
  2897. type: gauge
  2898. lookups:
  2899. - labels:
  2900. - ifIndex
  2901. labelname: ifAlias
  2902. oid: 1.3.6.1.2.1.31.1.1.1.18
  2903. type: DisplayString
  2904. - labels:
  2905. - ifIndex
  2906. labelname: ifDescr
  2907. oid: 1.3.6.1.2.1.2.2.1.2
  2908. type: DisplayString
  2909. - labels:
  2910. - ifIndex
  2911. labelname: ifName
  2912. oid: 1.3.6.1.2.1.31.1.1.1.1
  2913. type: DisplayString
  2914. - name: ifInUcastPkts
  2915. oid: 1.3.6.1.2.1.2.2.1.11
  2916. type: counter
  2917. help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
  2918. which were not addressed to a multicast or broadcast address at this sub-layer
  2919. - 1.3.6.1.2.1.2.2.1.11
  2920. indexes:
  2921. - labelname: ifIndex
  2922. type: gauge
  2923. lookups:
  2924. - labels:
  2925. - ifIndex
  2926. labelname: ifAlias
  2927. oid: 1.3.6.1.2.1.31.1.1.1.18
  2928. type: DisplayString
  2929. - labels:
  2930. - ifIndex
  2931. labelname: ifDescr
  2932. oid: 1.3.6.1.2.1.2.2.1.2
  2933. type: DisplayString
  2934. - labels:
  2935. - ifIndex
  2936. labelname: ifName
  2937. oid: 1.3.6.1.2.1.31.1.1.1.1
  2938. type: DisplayString
  2939. - name: ifInNUcastPkts
  2940. oid: 1.3.6.1.2.1.2.2.1.12
  2941. type: counter
  2942. help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
  2943. which were addressed to a multicast or broadcast address at this sub-layer
  2944. - 1.3.6.1.2.1.2.2.1.12
  2945. indexes:
  2946. - labelname: ifIndex
  2947. type: gauge
  2948. lookups:
  2949. - labels:
  2950. - ifIndex
  2951. labelname: ifAlias
  2952. oid: 1.3.6.1.2.1.31.1.1.1.18
  2953. type: DisplayString
  2954. - labels:
  2955. - ifIndex
  2956. labelname: ifDescr
  2957. oid: 1.3.6.1.2.1.2.2.1.2
  2958. type: DisplayString
  2959. - labels:
  2960. - ifIndex
  2961. labelname: ifName
  2962. oid: 1.3.6.1.2.1.31.1.1.1.1
  2963. type: DisplayString
  2964. - name: ifInDiscards
  2965. oid: 1.3.6.1.2.1.2.2.1.13
  2966. type: counter
  2967. help: The number of inbound packets which were chosen to be discarded even though
  2968. no errors had been detected to prevent their being deliverable to a higher-layer
  2969. protocol - 1.3.6.1.2.1.2.2.1.13
  2970. indexes:
  2971. - labelname: ifIndex
  2972. type: gauge
  2973. lookups:
  2974. - labels:
  2975. - ifIndex
  2976. labelname: ifAlias
  2977. oid: 1.3.6.1.2.1.31.1.1.1.18
  2978. type: DisplayString
  2979. - labels:
  2980. - ifIndex
  2981. labelname: ifDescr
  2982. oid: 1.3.6.1.2.1.2.2.1.2
  2983. type: DisplayString
  2984. - labels:
  2985. - ifIndex
  2986. labelname: ifName
  2987. oid: 1.3.6.1.2.1.31.1.1.1.1
  2988. type: DisplayString
  2989. - name: ifInErrors
  2990. oid: 1.3.6.1.2.1.2.2.1.14
  2991. type: counter
  2992. help: For packet-oriented interfaces, the number of inbound packets that contained
  2993. errors preventing them from being deliverable to a higher-layer protocol -
  2994. 1.3.6.1.2.1.2.2.1.14
  2995. indexes:
  2996. - labelname: ifIndex
  2997. type: gauge
  2998. lookups:
  2999. - labels:
  3000. - ifIndex
  3001. labelname: ifAlias
  3002. oid: 1.3.6.1.2.1.31.1.1.1.18
  3003. type: DisplayString
  3004. - labels:
  3005. - ifIndex
  3006. labelname: ifDescr
  3007. oid: 1.3.6.1.2.1.2.2.1.2
  3008. type: DisplayString
  3009. - labels:
  3010. - ifIndex
  3011. labelname: ifName
  3012. oid: 1.3.6.1.2.1.31.1.1.1.1
  3013. type: DisplayString
  3014. - name: ifInUnknownProtos
  3015. oid: 1.3.6.1.2.1.2.2.1.15
  3016. type: counter
  3017. help: For packet-oriented interfaces, the number of packets received via the
  3018. interface which were discarded because of an unknown or unsupported protocol
  3019. - 1.3.6.1.2.1.2.2.1.15
  3020. indexes:
  3021. - labelname: ifIndex
  3022. type: gauge
  3023. lookups:
  3024. - labels:
  3025. - ifIndex
  3026. labelname: ifAlias
  3027. oid: 1.3.6.1.2.1.31.1.1.1.18
  3028. type: DisplayString
  3029. - labels:
  3030. - ifIndex
  3031. labelname: ifDescr
  3032. oid: 1.3.6.1.2.1.2.2.1.2
  3033. type: DisplayString
  3034. - labels:
  3035. - ifIndex
  3036. labelname: ifName
  3037. oid: 1.3.6.1.2.1.31.1.1.1.1
  3038. type: DisplayString
  3039. - name: ifOutOctets
  3040. oid: 1.3.6.1.2.1.2.2.1.16
  3041. type: counter
  3042. help: The total number of octets transmitted out of the interface, including
  3043. framing characters - 1.3.6.1.2.1.2.2.1.16
  3044. indexes:
  3045. - labelname: ifIndex
  3046. type: gauge
  3047. lookups:
  3048. - labels:
  3049. - ifIndex
  3050. labelname: ifAlias
  3051. oid: 1.3.6.1.2.1.31.1.1.1.18
  3052. type: DisplayString
  3053. - labels:
  3054. - ifIndex
  3055. labelname: ifDescr
  3056. oid: 1.3.6.1.2.1.2.2.1.2
  3057. type: DisplayString
  3058. - labels:
  3059. - ifIndex
  3060. labelname: ifName
  3061. oid: 1.3.6.1.2.1.31.1.1.1.1
  3062. type: DisplayString
  3063. - name: ifOutUcastPkts
  3064. oid: 1.3.6.1.2.1.2.2.1.17
  3065. type: counter
  3066. help: The total number of packets that higher-level protocols requested be transmitted,
  3067. and which were not addressed to a multicast or broadcast address at this sub-layer,
  3068. including those that were discarded or not sent - 1.3.6.1.2.1.2.2.1.17
  3069. indexes:
  3070. - labelname: ifIndex
  3071. type: gauge
  3072. lookups:
  3073. - labels:
  3074. - ifIndex
  3075. labelname: ifAlias
  3076. oid: 1.3.6.1.2.1.31.1.1.1.18
  3077. type: DisplayString
  3078. - labels:
  3079. - ifIndex
  3080. labelname: ifDescr
  3081. oid: 1.3.6.1.2.1.2.2.1.2
  3082. type: DisplayString
  3083. - labels:
  3084. - ifIndex
  3085. labelname: ifName
  3086. oid: 1.3.6.1.2.1.31.1.1.1.1
  3087. type: DisplayString
  3088. - name: ifOutNUcastPkts
  3089. oid: 1.3.6.1.2.1.2.2.1.18
  3090. type: counter
  3091. help: The total number of packets that higher-level protocols requested be transmitted,
  3092. and which were addressed to a multicast or broadcast address at this sub-layer,
  3093. including those that were discarded or not sent - 1.3.6.1.2.1.2.2.1.18
  3094. indexes:
  3095. - labelname: ifIndex
  3096. type: gauge
  3097. lookups:
  3098. - labels:
  3099. - ifIndex
  3100. labelname: ifAlias
  3101. oid: 1.3.6.1.2.1.31.1.1.1.18
  3102. type: DisplayString
  3103. - labels:
  3104. - ifIndex
  3105. labelname: ifDescr
  3106. oid: 1.3.6.1.2.1.2.2.1.2
  3107. type: DisplayString
  3108. - labels:
  3109. - ifIndex
  3110. labelname: ifName
  3111. oid: 1.3.6.1.2.1.31.1.1.1.1
  3112. type: DisplayString
  3113. - name: ifOutDiscards
  3114. oid: 1.3.6.1.2.1.2.2.1.19
  3115. type: counter
  3116. help: The number of outbound packets which were chosen to be discarded even
  3117. though no errors had been detected to prevent their being transmitted - 1.3.6.1.2.1.2.2.1.19
  3118. indexes:
  3119. - labelname: ifIndex
  3120. type: gauge
  3121. lookups:
  3122. - labels:
  3123. - ifIndex
  3124. labelname: ifAlias
  3125. oid: 1.3.6.1.2.1.31.1.1.1.18
  3126. type: DisplayString
  3127. - labels:
  3128. - ifIndex
  3129. labelname: ifDescr
  3130. oid: 1.3.6.1.2.1.2.2.1.2
  3131. type: DisplayString
  3132. - labels:
  3133. - ifIndex
  3134. labelname: ifName
  3135. oid: 1.3.6.1.2.1.31.1.1.1.1
  3136. type: DisplayString
  3137. - name: ifOutErrors
  3138. oid: 1.3.6.1.2.1.2.2.1.20
  3139. type: counter
  3140. help: For packet-oriented interfaces, the number of outbound packets that could
  3141. not be transmitted because of errors - 1.3.6.1.2.1.2.2.1.20
  3142. indexes:
  3143. - labelname: ifIndex
  3144. type: gauge
  3145. lookups:
  3146. - labels:
  3147. - ifIndex
  3148. labelname: ifAlias
  3149. oid: 1.3.6.1.2.1.31.1.1.1.18
  3150. type: DisplayString
  3151. - labels:
  3152. - ifIndex
  3153. labelname: ifDescr
  3154. oid: 1.3.6.1.2.1.2.2.1.2
  3155. type: DisplayString
  3156. - labels:
  3157. - ifIndex
  3158. labelname: ifName
  3159. oid: 1.3.6.1.2.1.31.1.1.1.1
  3160. type: DisplayString
  3161. - name: ifOutQLen
  3162. oid: 1.3.6.1.2.1.2.2.1.21
  3163. type: gauge
  3164. help: The length of the output packet queue (in packets). - 1.3.6.1.2.1.2.2.1.21
  3165. indexes:
  3166. - labelname: ifIndex
  3167. type: gauge
  3168. lookups:
  3169. - labels:
  3170. - ifIndex
  3171. labelname: ifAlias
  3172. oid: 1.3.6.1.2.1.31.1.1.1.18
  3173. type: DisplayString
  3174. - labels:
  3175. - ifIndex
  3176. labelname: ifDescr
  3177. oid: 1.3.6.1.2.1.2.2.1.2
  3178. type: DisplayString
  3179. - labels:
  3180. - ifIndex
  3181. labelname: ifName
  3182. oid: 1.3.6.1.2.1.31.1.1.1.1
  3183. type: DisplayString
  3184. - name: ifSpecific
  3185. oid: 1.3.6.1.2.1.2.2.1.22
  3186. type: OctetString
  3187. help: A reference to MIB definitions specific to the particular media being
  3188. used to realize the interface - 1.3.6.1.2.1.2.2.1.22
  3189. indexes:
  3190. - labelname: ifIndex
  3191. type: gauge
  3192. lookups:
  3193. - labels:
  3194. - ifIndex
  3195. labelname: ifAlias
  3196. oid: 1.3.6.1.2.1.31.1.1.1.18
  3197. type: DisplayString
  3198. - labels:
  3199. - ifIndex
  3200. labelname: ifDescr
  3201. oid: 1.3.6.1.2.1.2.2.1.2
  3202. type: DisplayString
  3203. - labels:
  3204. - ifIndex
  3205. labelname: ifName
  3206. oid: 1.3.6.1.2.1.31.1.1.1.1
  3207. type: DisplayString
  3208. - name: ifInMulticastPkts
  3209. oid: 1.3.6.1.2.1.31.1.1.1.2
  3210. type: counter
  3211. help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
  3212. which were addressed to a multicast address at this sub-layer - 1.3.6.1.2.1.31.1.1.1.2
  3213. indexes:
  3214. - labelname: ifIndex
  3215. type: gauge
  3216. lookups:
  3217. - labels:
  3218. - ifIndex
  3219. labelname: ifAlias
  3220. oid: 1.3.6.1.2.1.31.1.1.1.18
  3221. type: DisplayString
  3222. - labels:
  3223. - ifIndex
  3224. labelname: ifDescr
  3225. oid: 1.3.6.1.2.1.2.2.1.2
  3226. type: DisplayString
  3227. - labels:
  3228. - ifIndex
  3229. labelname: ifName
  3230. oid: 1.3.6.1.2.1.31.1.1.1.1
  3231. type: DisplayString
  3232. - name: ifInBroadcastPkts
  3233. oid: 1.3.6.1.2.1.31.1.1.1.3
  3234. type: counter
  3235. help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
  3236. which were addressed to a broadcast address at this sub-layer - 1.3.6.1.2.1.31.1.1.1.3
  3237. indexes:
  3238. - labelname: ifIndex
  3239. type: gauge
  3240. lookups:
  3241. - labels:
  3242. - ifIndex
  3243. labelname: ifAlias
  3244. oid: 1.3.6.1.2.1.31.1.1.1.18
  3245. type: DisplayString
  3246. - labels:
  3247. - ifIndex
  3248. labelname: ifDescr
  3249. oid: 1.3.6.1.2.1.2.2.1.2
  3250. type: DisplayString
  3251. - labels:
  3252. - ifIndex
  3253. labelname: ifName
  3254. oid: 1.3.6.1.2.1.31.1.1.1.1
  3255. type: DisplayString
  3256. - name: ifOutMulticastPkts
  3257. oid: 1.3.6.1.2.1.31.1.1.1.4
  3258. type: counter
  3259. help: The total number of packets that higher-level protocols requested be transmitted,
  3260. and which were addressed to a multicast address at this sub-layer, including
  3261. those that were discarded or not sent - 1.3.6.1.2.1.31.1.1.1.4
  3262. indexes:
  3263. - labelname: ifIndex
  3264. type: gauge
  3265. lookups:
  3266. - labels:
  3267. - ifIndex
  3268. labelname: ifAlias
  3269. oid: 1.3.6.1.2.1.31.1.1.1.18
  3270. type: DisplayString
  3271. - labels:
  3272. - ifIndex
  3273. labelname: ifDescr
  3274. oid: 1.3.6.1.2.1.2.2.1.2
  3275. type: DisplayString
  3276. - labels:
  3277. - ifIndex
  3278. labelname: ifName
  3279. oid: 1.3.6.1.2.1.31.1.1.1.1
  3280. type: DisplayString
  3281. - name: ifOutBroadcastPkts
  3282. oid: 1.3.6.1.2.1.31.1.1.1.5
  3283. type: counter
  3284. help: The total number of packets that higher-level protocols requested be transmitted,
  3285. and which were addressed to a broadcast address at this sub-layer, including
  3286. those that were discarded or not sent - 1.3.6.1.2.1.31.1.1.1.5
  3287. indexes:
  3288. - labelname: ifIndex
  3289. type: gauge
  3290. lookups:
  3291. - labels:
  3292. - ifIndex
  3293. labelname: ifAlias
  3294. oid: 1.3.6.1.2.1.31.1.1.1.18
  3295. type: DisplayString
  3296. - labels:
  3297. - ifIndex
  3298. labelname: ifDescr
  3299. oid: 1.3.6.1.2.1.2.2.1.2
  3300. type: DisplayString
  3301. - labels:
  3302. - ifIndex
  3303. labelname: ifName
  3304. oid: 1.3.6.1.2.1.31.1.1.1.1
  3305. type: DisplayString
  3306. - name: ifHCInOctets
  3307. oid: 1.3.6.1.2.1.31.1.1.1.6
  3308. type: counter
  3309. help: The total number of octets received on the interface, including framing
  3310. characters - 1.3.6.1.2.1.31.1.1.1.6
  3311. indexes:
  3312. - labelname: ifIndex
  3313. type: gauge
  3314. lookups:
  3315. - labels:
  3316. - ifIndex
  3317. labelname: ifAlias
  3318. oid: 1.3.6.1.2.1.31.1.1.1.18
  3319. type: DisplayString
  3320. - labels:
  3321. - ifIndex
  3322. labelname: ifDescr
  3323. oid: 1.3.6.1.2.1.2.2.1.2
  3324. type: DisplayString
  3325. - labels:
  3326. - ifIndex
  3327. labelname: ifName
  3328. oid: 1.3.6.1.2.1.31.1.1.1.1
  3329. type: DisplayString
  3330. - name: ifHCInUcastPkts
  3331. oid: 1.3.6.1.2.1.31.1.1.1.7
  3332. type: counter
  3333. help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
  3334. which were not addressed to a multicast or broadcast address at this sub-layer
  3335. - 1.3.6.1.2.1.31.1.1.1.7
  3336. indexes:
  3337. - labelname: ifIndex
  3338. type: gauge
  3339. lookups:
  3340. - labels:
  3341. - ifIndex
  3342. labelname: ifAlias
  3343. oid: 1.3.6.1.2.1.31.1.1.1.18
  3344. type: DisplayString
  3345. - labels:
  3346. - ifIndex
  3347. labelname: ifDescr
  3348. oid: 1.3.6.1.2.1.2.2.1.2
  3349. type: DisplayString
  3350. - labels:
  3351. - ifIndex
  3352. labelname: ifName
  3353. oid: 1.3.6.1.2.1.31.1.1.1.1
  3354. type: DisplayString
  3355. - name: ifHCInMulticastPkts
  3356. oid: 1.3.6.1.2.1.31.1.1.1.8
  3357. type: counter
  3358. help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
  3359. which were addressed to a multicast address at this sub-layer - 1.3.6.1.2.1.31.1.1.1.8
  3360. indexes:
  3361. - labelname: ifIndex
  3362. type: gauge
  3363. lookups:
  3364. - labels:
  3365. - ifIndex
  3366. labelname: ifAlias
  3367. oid: 1.3.6.1.2.1.31.1.1.1.18
  3368. type: DisplayString
  3369. - labels:
  3370. - ifIndex
  3371. labelname: ifDescr
  3372. oid: 1.3.6.1.2.1.2.2.1.2
  3373. type: DisplayString
  3374. - labels:
  3375. - ifIndex
  3376. labelname: ifName
  3377. oid: 1.3.6.1.2.1.31.1.1.1.1
  3378. type: DisplayString
  3379. - name: ifHCInBroadcastPkts
  3380. oid: 1.3.6.1.2.1.31.1.1.1.9
  3381. type: counter
  3382. help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
  3383. which were addressed to a broadcast address at this sub-layer - 1.3.6.1.2.1.31.1.1.1.9
  3384. indexes:
  3385. - labelname: ifIndex
  3386. type: gauge
  3387. lookups:
  3388. - labels:
  3389. - ifIndex
  3390. labelname: ifAlias
  3391. oid: 1.3.6.1.2.1.31.1.1.1.18
  3392. type: DisplayString
  3393. - labels:
  3394. - ifIndex
  3395. labelname: ifDescr
  3396. oid: 1.3.6.1.2.1.2.2.1.2
  3397. type: DisplayString
  3398. - labels:
  3399. - ifIndex
  3400. labelname: ifName
  3401. oid: 1.3.6.1.2.1.31.1.1.1.1
  3402. type: DisplayString
  3403. - name: ifHCOutOctets
  3404. oid: 1.3.6.1.2.1.31.1.1.1.10
  3405. type: counter
  3406. help: The total number of octets transmitted out of the interface, including
  3407. framing characters - 1.3.6.1.2.1.31.1.1.1.10
  3408. indexes:
  3409. - labelname: ifIndex
  3410. type: gauge
  3411. lookups:
  3412. - labels:
  3413. - ifIndex
  3414. labelname: ifAlias
  3415. oid: 1.3.6.1.2.1.31.1.1.1.18
  3416. type: DisplayString
  3417. - labels:
  3418. - ifIndex
  3419. labelname: ifDescr
  3420. oid: 1.3.6.1.2.1.2.2.1.2
  3421. type: DisplayString
  3422. - labels:
  3423. - ifIndex
  3424. labelname: ifName
  3425. oid: 1.3.6.1.2.1.31.1.1.1.1
  3426. type: DisplayString
  3427. - name: ifHCOutUcastPkts
  3428. oid: 1.3.6.1.2.1.31.1.1.1.11
  3429. type: counter
  3430. help: The total number of packets that higher-level protocols requested be transmitted,
  3431. and which were not addressed to a multicast or broadcast address at this sub-layer,
  3432. including those that were discarded or not sent - 1.3.6.1.2.1.31.1.1.1.11
  3433. indexes:
  3434. - labelname: ifIndex
  3435. type: gauge
  3436. lookups:
  3437. - labels:
  3438. - ifIndex
  3439. labelname: ifAlias
  3440. oid: 1.3.6.1.2.1.31.1.1.1.18
  3441. type: DisplayString
  3442. - labels:
  3443. - ifIndex
  3444. labelname: ifDescr
  3445. oid: 1.3.6.1.2.1.2.2.1.2
  3446. type: DisplayString
  3447. - labels:
  3448. - ifIndex
  3449. labelname: ifName
  3450. oid: 1.3.6.1.2.1.31.1.1.1.1
  3451. type: DisplayString
  3452. - name: ifHCOutMulticastPkts
  3453. oid: 1.3.6.1.2.1.31.1.1.1.12
  3454. type: counter
  3455. help: The total number of packets that higher-level protocols requested be transmitted,
  3456. and which were addressed to a multicast address at this sub-layer, including
  3457. those that were discarded or not sent - 1.3.6.1.2.1.31.1.1.1.12
  3458. indexes:
  3459. - labelname: ifIndex
  3460. type: gauge
  3461. lookups:
  3462. - labels:
  3463. - ifIndex
  3464. labelname: ifAlias
  3465. oid: 1.3.6.1.2.1.31.1.1.1.18
  3466. type: DisplayString
  3467. - labels:
  3468. - ifIndex
  3469. labelname: ifDescr
  3470. oid: 1.3.6.1.2.1.2.2.1.2
  3471. type: DisplayString
  3472. - labels:
  3473. - ifIndex
  3474. labelname: ifName
  3475. oid: 1.3.6.1.2.1.31.1.1.1.1
  3476. type: DisplayString
  3477. - name: ifHCOutBroadcastPkts
  3478. oid: 1.3.6.1.2.1.31.1.1.1.13
  3479. type: counter
  3480. help: The total number of packets that higher-level protocols requested be transmitted,
  3481. and which were addressed to a broadcast address at this sub-layer, including
  3482. those that were discarded or not sent - 1.3.6.1.2.1.31.1.1.1.13
  3483. indexes:
  3484. - labelname: ifIndex
  3485. type: gauge
  3486. lookups:
  3487. - labels:
  3488. - ifIndex
  3489. labelname: ifAlias
  3490. oid: 1.3.6.1.2.1.31.1.1.1.18
  3491. type: DisplayString
  3492. - labels:
  3493. - ifIndex
  3494. labelname: ifDescr
  3495. oid: 1.3.6.1.2.1.2.2.1.2
  3496. type: DisplayString
  3497. - labels:
  3498. - ifIndex
  3499. labelname: ifName
  3500. oid: 1.3.6.1.2.1.31.1.1.1.1
  3501. type: DisplayString
  3502. - name: ifLinkUpDownTrapEnable
  3503. oid: 1.3.6.1.2.1.31.1.1.1.14
  3504. type: gauge
  3505. help: Indicates whether linkUp/linkDown traps should be generated for this interface
  3506. - 1.3.6.1.2.1.31.1.1.1.14
  3507. indexes:
  3508. - labelname: ifIndex
  3509. type: gauge
  3510. lookups:
  3511. - labels:
  3512. - ifIndex
  3513. labelname: ifAlias
  3514. oid: 1.3.6.1.2.1.31.1.1.1.18
  3515. type: DisplayString
  3516. - labels:
  3517. - ifIndex
  3518. labelname: ifDescr
  3519. oid: 1.3.6.1.2.1.2.2.1.2
  3520. type: DisplayString
  3521. - labels:
  3522. - ifIndex
  3523. labelname: ifName
  3524. oid: 1.3.6.1.2.1.31.1.1.1.1
  3525. type: DisplayString
  3526. enum_values:
  3527. 1: enabled
  3528. 2: disabled
  3529. - name: ifHighSpeed
  3530. oid: 1.3.6.1.2.1.31.1.1.1.15
  3531. type: gauge
  3532. help: An estimate of the interface's current bandwidth in units of 1,000,000
  3533. bits per second - 1.3.6.1.2.1.31.1.1.1.15
  3534. indexes:
  3535. - labelname: ifIndex
  3536. type: gauge
  3537. lookups:
  3538. - labels:
  3539. - ifIndex
  3540. labelname: ifAlias
  3541. oid: 1.3.6.1.2.1.31.1.1.1.18
  3542. type: DisplayString
  3543. - labels:
  3544. - ifIndex
  3545. labelname: ifDescr
  3546. oid: 1.3.6.1.2.1.2.2.1.2
  3547. type: DisplayString
  3548. - labels:
  3549. - ifIndex
  3550. labelname: ifName
  3551. oid: 1.3.6.1.2.1.31.1.1.1.1
  3552. type: DisplayString
  3553. - name: ifPromiscuousMode
  3554. oid: 1.3.6.1.2.1.31.1.1.1.16
  3555. type: gauge
  3556. help: This object has a value of false(2) if this interface only accepts packets/frames
  3557. that are addressed to this station - 1.3.6.1.2.1.31.1.1.1.16
  3558. indexes:
  3559. - labelname: ifIndex
  3560. type: gauge
  3561. lookups:
  3562. - labels:
  3563. - ifIndex
  3564. labelname: ifAlias
  3565. oid: 1.3.6.1.2.1.31.1.1.1.18
  3566. type: DisplayString
  3567. - labels:
  3568. - ifIndex
  3569. labelname: ifDescr
  3570. oid: 1.3.6.1.2.1.2.2.1.2
  3571. type: DisplayString
  3572. - labels:
  3573. - ifIndex
  3574. labelname: ifName
  3575. oid: 1.3.6.1.2.1.31.1.1.1.1
  3576. type: DisplayString
  3577. enum_values:
  3578. 1: "true"
  3579. 2: "false"
  3580. - name: ifConnectorPresent
  3581. oid: 1.3.6.1.2.1.31.1.1.1.17
  3582. type: gauge
  3583. help: This object has the value 'true(1)' if the interface sublayer has a physical
  3584. connector and the value 'false(2)' otherwise. - 1.3.6.1.2.1.31.1.1.1.17
  3585. indexes:
  3586. - labelname: ifIndex
  3587. type: gauge
  3588. lookups:
  3589. - labels:
  3590. - ifIndex
  3591. labelname: ifAlias
  3592. oid: 1.3.6.1.2.1.31.1.1.1.18
  3593. type: DisplayString
  3594. - labels:
  3595. - ifIndex
  3596. labelname: ifDescr
  3597. oid: 1.3.6.1.2.1.2.2.1.2
  3598. type: DisplayString
  3599. - labels:
  3600. - ifIndex
  3601. labelname: ifName
  3602. oid: 1.3.6.1.2.1.31.1.1.1.1
  3603. type: DisplayString
  3604. enum_values:
  3605. 1: "true"
  3606. 2: "false"
  3607. - name: ifCounterDiscontinuityTime
  3608. oid: 1.3.6.1.2.1.31.1.1.1.19
  3609. type: gauge
  3610. help: The value of sysUpTime on the most recent occasion at which any one or
  3611. more of this interface's counters suffered a discontinuity - 1.3.6.1.2.1.31.1.1.1.19
  3612. indexes:
  3613. - labelname: ifIndex
  3614. type: gauge
  3615. lookups:
  3616. - labels:
  3617. - ifIndex
  3618. labelname: ifAlias
  3619. oid: 1.3.6.1.2.1.31.1.1.1.18
  3620. type: DisplayString
  3621. - labels:
  3622. - ifIndex
  3623. labelname: ifDescr
  3624. oid: 1.3.6.1.2.1.2.2.1.2
  3625. type: DisplayString
  3626. - labels:
  3627. - ifIndex
  3628. labelname: ifName
  3629. oid: 1.3.6.1.2.1.31.1.1.1.1
  3630. type: DisplayString
  3631. ip_mib:
  3632. walk:
  3633. - 1.3.6.1.2.1.4.28
  3634. metrics:
  3635. - name: ipv4InterfaceIfIndex
  3636. oid: 1.3.6.1.2.1.4.28.1.1
  3637. type: gauge
  3638. help: The index value that uniquely identifies the interface to which this entry
  3639. is applicable - 1.3.6.1.2.1.4.28.1.1
  3640. indexes:
  3641. - labelname: ipv4InterfaceIfIndex
  3642. type: gauge
  3643. - name: ipv4InterfaceReasmMaxSize
  3644. oid: 1.3.6.1.2.1.4.28.1.2
  3645. type: gauge
  3646. help: The size of the largest IPv4 datagram that this entity can re-assemble
  3647. from incoming IPv4 fragmented datagrams received on this interface. - 1.3.6.1.2.1.4.28.1.2
  3648. indexes:
  3649. - labelname: ipv4InterfaceIfIndex
  3650. type: gauge
  3651. - name: ipv4InterfaceEnableStatus
  3652. oid: 1.3.6.1.2.1.4.28.1.3
  3653. type: gauge
  3654. help: The indication of whether IPv4 is enabled (up) or disabled (down) on this
  3655. interface - 1.3.6.1.2.1.4.28.1.3
  3656. indexes:
  3657. - labelname: ipv4InterfaceIfIndex
  3658. type: gauge
  3659. enum_values:
  3660. 1: up
  3661. 2: down
  3662. - name: ipv4InterfaceRetransmitTime
  3663. oid: 1.3.6.1.2.1.4.28.1.4
  3664. type: gauge
  3665. help: The time between retransmissions of ARP requests to a neighbor when resolving
  3666. the address or when probing the reachability of a neighbor. - 1.3.6.1.2.1.4.28.1.4
  3667. indexes:
  3668. - labelname: ipv4InterfaceIfIndex
  3669. type: gauge
  3670. synology:
  3671. walk:
  3672. - 1.3.6.1.2.1.2
  3673. - 1.3.6.1.2.1.25.2
  3674. - 1.3.6.1.2.1.31.1.1
  3675. - 1.3.6.1.4.1.2021.10.1.2
  3676. - 1.3.6.1.4.1.2021.10.1.5
  3677. - 1.3.6.1.4.1.2021.4
  3678. - 1.3.6.1.4.1.6574.1
  3679. - 1.3.6.1.4.1.6574.101
  3680. - 1.3.6.1.4.1.6574.102
  3681. - 1.3.6.1.4.1.6574.104
  3682. - 1.3.6.1.4.1.6574.2
  3683. - 1.3.6.1.4.1.6574.3
  3684. - 1.3.6.1.4.1.6574.4
  3685. - 1.3.6.1.4.1.6574.5
  3686. - 1.3.6.1.4.1.6574.6
  3687. get:
  3688. - 1.3.6.1.4.1.2021.11.10.0
  3689. - 1.3.6.1.4.1.2021.11.11.0
  3690. - 1.3.6.1.4.1.2021.11.9.0
  3691. metrics:
  3692. - name: ifNumber
  3693. oid: 1.3.6.1.2.1.2.1
  3694. type: gauge
  3695. help: The number of network interfaces (regardless of their current state) present
  3696. on this system. - 1.3.6.1.2.1.2.1
  3697. - name: ifIndex
  3698. oid: 1.3.6.1.2.1.2.2.1.1
  3699. type: gauge
  3700. help: A unique value, greater than zero, for each interface - 1.3.6.1.2.1.2.2.1.1
  3701. indexes:
  3702. - labelname: ifIndex
  3703. type: gauge
  3704. - name: ifDescr
  3705. oid: 1.3.6.1.2.1.2.2.1.2
  3706. type: DisplayString
  3707. help: A textual string containing information about the interface - 1.3.6.1.2.1.2.2.1.2
  3708. indexes:
  3709. - labelname: ifIndex
  3710. type: gauge
  3711. - name: ifType
  3712. oid: 1.3.6.1.2.1.2.2.1.3
  3713. type: gauge
  3714. help: The type of interface - 1.3.6.1.2.1.2.2.1.3
  3715. indexes:
  3716. - labelname: ifIndex
  3717. type: gauge
  3718. enum_values:
  3719. 1: other
  3720. 2: regular1822
  3721. 3: hdh1822
  3722. 4: ddnX25
  3723. 5: rfc877x25
  3724. 6: ethernetCsmacd
  3725. 7: iso88023Csmacd
  3726. 8: iso88024TokenBus
  3727. 9: iso88025TokenRing
  3728. 10: iso88026Man
  3729. 11: starLan
  3730. 12: proteon10Mbit
  3731. 13: proteon80Mbit
  3732. 14: hyperchannel
  3733. 15: fddi
  3734. 16: lapb
  3735. 17: sdlc
  3736. 18: ds1
  3737. 19: e1
  3738. 20: basicISDN
  3739. 21: primaryISDN
  3740. 22: propPointToPointSerial
  3741. 23: ppp
  3742. 24: softwareLoopback
  3743. 25: eon
  3744. 26: ethernet3Mbit
  3745. 27: nsip
  3746. 28: slip
  3747. 29: ultra
  3748. 30: ds3
  3749. 31: sip
  3750. 32: frameRelay
  3751. 33: rs232
  3752. 34: para
  3753. 35: arcnet
  3754. 36: arcnetPlus
  3755. 37: atm
  3756. 38: miox25
  3757. 39: sonet
  3758. 40: x25ple
  3759. 41: iso88022llc
  3760. 42: localTalk
  3761. 43: smdsDxi
  3762. 44: frameRelayService
  3763. 45: v35
  3764. 46: hssi
  3765. 47: hippi
  3766. 48: modem
  3767. 49: aal5
  3768. 50: sonetPath
  3769. 51: sonetVT
  3770. 52: smdsIcip
  3771. 53: propVirtual
  3772. 54: propMultiplexor
  3773. 55: ieee80212
  3774. 56: fibreChannel
  3775. 57: hippiInterface
  3776. 58: frameRelayInterconnect
  3777. 59: aflane8023
  3778. 60: aflane8025
  3779. 61: cctEmul
  3780. 62: fastEther
  3781. 63: isdn
  3782. 64: v11
  3783. 65: v36
  3784. 66: g703at64k
  3785. 67: g703at2mb
  3786. 68: qllc
  3787. 69: fastEtherFX
  3788. 70: channel
  3789. 71: ieee80211
  3790. 72: ibm370parChan
  3791. 73: escon
  3792. 74: dlsw
  3793. 75: isdns
  3794. 76: isdnu
  3795. 77: lapd
  3796. 78: ipSwitch
  3797. 79: rsrb
  3798. 80: atmLogical
  3799. 81: ds0
  3800. 82: ds0Bundle
  3801. 83: bsc
  3802. 84: async
  3803. 85: cnr
  3804. 86: iso88025Dtr
  3805. 87: eplrs
  3806. 88: arap
  3807. 89: propCnls
  3808. 90: hostPad
  3809. 91: termPad
  3810. 92: frameRelayMPI
  3811. 93: x213
  3812. 94: adsl
  3813. 95: radsl
  3814. 96: sdsl
  3815. 97: vdsl
  3816. 98: iso88025CRFPInt
  3817. 99: myrinet
  3818. 100: voiceEM
  3819. 101: voiceFXO
  3820. 102: voiceFXS
  3821. 103: voiceEncap
  3822. 104: voiceOverIp
  3823. 105: atmDxi
  3824. 106: atmFuni
  3825. 107: atmIma
  3826. 108: pppMultilinkBundle
  3827. 109: ipOverCdlc
  3828. 110: ipOverClaw
  3829. 111: stackToStack
  3830. 112: virtualIpAddress
  3831. 113: mpc
  3832. 114: ipOverAtm
  3833. 115: iso88025Fiber
  3834. 116: tdlc
  3835. 117: gigabitEthernet
  3836. 118: hdlc
  3837. 119: lapf
  3838. 120: v37
  3839. 121: x25mlp
  3840. 122: x25huntGroup
  3841. 123: transpHdlc
  3842. 124: interleave
  3843. 125: fast
  3844. 126: ip
  3845. 127: docsCableMaclayer
  3846. 128: docsCableDownstream
  3847. 129: docsCableUpstream
  3848. 130: a12MppSwitch
  3849. 131: tunnel
  3850. 132: coffee
  3851. 133: ces
  3852. 134: atmSubInterface
  3853. 135: l2vlan
  3854. 136: l3ipvlan
  3855. 137: l3ipxvlan
  3856. 138: digitalPowerline
  3857. 139: mediaMailOverIp
  3858. 140: dtm
  3859. 141: dcn
  3860. 142: ipForward
  3861. 143: msdsl
  3862. 144: ieee1394
  3863. 145: if-gsn
  3864. 146: dvbRccMacLayer
  3865. 147: dvbRccDownstream
  3866. 148: dvbRccUpstream
  3867. 149: atmVirtual
  3868. 150: mplsTunnel
  3869. 151: srp
  3870. 152: voiceOverAtm
  3871. 153: voiceOverFrameRelay
  3872. 154: idsl
  3873. 155: compositeLink
  3874. 156: ss7SigLink
  3875. 157: propWirelessP2P
  3876. 158: frForward
  3877. 159: rfc1483
  3878. 160: usb
  3879. 161: ieee8023adLag
  3880. 162: bgppolicyaccounting
  3881. 163: frf16MfrBundle
  3882. 164: h323Gatekeeper
  3883. 165: h323Proxy
  3884. 166: mpls
  3885. 167: mfSigLink
  3886. 168: hdsl2
  3887. 169: shdsl
  3888. 170: ds1FDL
  3889. 171: pos
  3890. 172: dvbAsiIn
  3891. 173: dvbAsiOut
  3892. 174: plc
  3893. 175: nfas
  3894. 176: tr008
  3895. 177: gr303RDT
  3896. 178: gr303IDT
  3897. 179: isup
  3898. 180: propDocsWirelessMaclayer
  3899. 181: propDocsWirelessDownstream
  3900. 182: propDocsWirelessUpstream
  3901. 183: hiperlan2
  3902. 184: propBWAp2Mp
  3903. 185: sonetOverheadChannel
  3904. 186: digitalWrapperOverheadChannel
  3905. 187: aal2
  3906. 188: radioMAC
  3907. 189: atmRadio
  3908. 190: imt
  3909. 191: mvl
  3910. 192: reachDSL
  3911. 193: frDlciEndPt
  3912. 194: atmVciEndPt
  3913. 195: opticalChannel
  3914. 196: opticalTransport
  3915. 197: propAtm
  3916. 198: voiceOverCable
  3917. 199: infiniband
  3918. 200: teLink
  3919. 201: q2931
  3920. 202: virtualTg
  3921. 203: sipTg
  3922. 204: sipSig
  3923. 205: docsCableUpstreamChannel
  3924. 206: econet
  3925. 207: pon155
  3926. 208: pon622
  3927. 209: bridge
  3928. 210: linegroup
  3929. 211: voiceEMFGD
  3930. 212: voiceFGDEANA
  3931. 213: voiceDID
  3932. 214: mpegTransport
  3933. 215: sixToFour
  3934. 216: gtp
  3935. 217: pdnEtherLoop1
  3936. 218: pdnEtherLoop2
  3937. 219: opticalChannelGroup
  3938. 220: homepna
  3939. 221: gfp
  3940. 222: ciscoISLvlan
  3941. 223: actelisMetaLOOP
  3942. 224: fcipLink
  3943. 225: rpr
  3944. 226: qam
  3945. 227: lmp
  3946. 228: cblVectaStar
  3947. 229: docsCableMCmtsDownstream
  3948. 230: adsl2
  3949. 231: macSecControlledIF
  3950. 232: macSecUncontrolledIF
  3951. 233: aviciOpticalEther
  3952. 234: atmbond
  3953. 235: voiceFGDOS
  3954. 236: mocaVersion1
  3955. 237: ieee80216WMAN
  3956. 238: adsl2plus
  3957. 239: dvbRcsMacLayer
  3958. 240: dvbTdm
  3959. 241: dvbRcsTdma
  3960. 242: x86Laps
  3961. 243: wwanPP
  3962. 244: wwanPP2
  3963. 245: voiceEBS
  3964. 246: ifPwType
  3965. 247: ilan
  3966. 248: pip
  3967. 249: aluELP
  3968. 250: gpon
  3969. 251: vdsl2
  3970. 252: capwapDot11Profile
  3971. 253: capwapDot11Bss
  3972. 254: capwapWtpVirtualRadio
  3973. 255: bits
  3974. 256: docsCableUpstreamRfPort
  3975. 257: cableDownstreamRfPort
  3976. 258: vmwareVirtualNic
  3977. 259: ieee802154
  3978. 260: otnOdu
  3979. 261: otnOtu
  3980. 262: ifVfiType
  3981. 263: g9981
  3982. 264: g9982
  3983. 265: g9983
  3984. 266: aluEpon
  3985. 267: aluEponOnu
  3986. 268: aluEponPhysicalUni
  3987. 269: aluEponLogicalLink
  3988. 270: aluGponOnu
  3989. 271: aluGponPhysicalUni
  3990. 272: vmwareNicTeam
  3991. 277: docsOfdmDownstream
  3992. 278: docsOfdmaUpstream
  3993. 279: gfast
  3994. 280: sdci
  3995. 281: xboxWireless
  3996. 282: fastdsl
  3997. 283: docsCableScte55d1FwdOob
  3998. 284: docsCableScte55d1RetOob
  3999. 285: docsCableScte55d2DsOob
  4000. 286: docsCableScte55d2UsOob
  4001. 287: docsCableNdf
  4002. 288: docsCableNdr
  4003. 289: ptm
  4004. 290: ghn
  4005. 291: otnOtsi
  4006. 292: otnOtuc
  4007. 293: otnOduc
  4008. 294: otnOtsig
  4009. 295: microwaveCarrierTermination
  4010. 296: microwaveRadioLinkTerminal
  4011. 297: ieee8021axDrni
  4012. 298: ax25
  4013. 299: ieee19061nanocom
  4014. 300: cpri
  4015. 301: omni
  4016. 302: roe
  4017. 303: p2pOverLan
  4018. - name: ifMtu
  4019. oid: 1.3.6.1.2.1.2.2.1.4
  4020. type: gauge
  4021. help: The size of the largest packet which can be sent/received on the interface,
  4022. specified in octets - 1.3.6.1.2.1.2.2.1.4
  4023. indexes:
  4024. - labelname: ifIndex
  4025. type: gauge
  4026. - name: ifSpeed
  4027. oid: 1.3.6.1.2.1.2.2.1.5
  4028. type: gauge
  4029. help: An estimate of the interface's current bandwidth in bits per second -
  4030. 1.3.6.1.2.1.2.2.1.5
  4031. indexes:
  4032. - labelname: ifIndex
  4033. type: gauge
  4034. - name: ifPhysAddress
  4035. oid: 1.3.6.1.2.1.2.2.1.6
  4036. type: PhysAddress48
  4037. help: The interface's address at its protocol sub-layer - 1.3.6.1.2.1.2.2.1.6
  4038. indexes:
  4039. - labelname: ifIndex
  4040. type: gauge
  4041. - name: ifAdminStatus
  4042. oid: 1.3.6.1.2.1.2.2.1.7
  4043. type: gauge
  4044. help: The desired state of the interface - 1.3.6.1.2.1.2.2.1.7
  4045. indexes:
  4046. - labelname: ifIndex
  4047. type: gauge
  4048. enum_values:
  4049. 1: up
  4050. 2: down
  4051. 3: testing
  4052. - name: ifOperStatus
  4053. oid: 1.3.6.1.2.1.2.2.1.8
  4054. type: gauge
  4055. help: The current operational state of the interface - 1.3.6.1.2.1.2.2.1.8
  4056. indexes:
  4057. - labelname: ifIndex
  4058. type: gauge
  4059. enum_values:
  4060. 1: up
  4061. 2: down
  4062. 3: testing
  4063. 4: unknown
  4064. 5: dormant
  4065. 6: notPresent
  4066. 7: lowerLayerDown
  4067. - name: ifLastChange
  4068. oid: 1.3.6.1.2.1.2.2.1.9
  4069. type: gauge
  4070. help: The value of sysUpTime at the time the interface entered its current operational
  4071. state - 1.3.6.1.2.1.2.2.1.9
  4072. indexes:
  4073. - labelname: ifIndex
  4074. type: gauge
  4075. - name: ifInOctets
  4076. oid: 1.3.6.1.2.1.2.2.1.10
  4077. type: counter
  4078. help: The total number of octets received on the interface, including framing
  4079. characters - 1.3.6.1.2.1.2.2.1.10
  4080. indexes:
  4081. - labelname: ifIndex
  4082. type: gauge
  4083. - name: ifInUcastPkts
  4084. oid: 1.3.6.1.2.1.2.2.1.11
  4085. type: counter
  4086. help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
  4087. which were not addressed to a multicast or broadcast address at this sub-layer
  4088. - 1.3.6.1.2.1.2.2.1.11
  4089. indexes:
  4090. - labelname: ifIndex
  4091. type: gauge
  4092. - name: ifInNUcastPkts
  4093. oid: 1.3.6.1.2.1.2.2.1.12
  4094. type: counter
  4095. help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
  4096. which were addressed to a multicast or broadcast address at this sub-layer
  4097. - 1.3.6.1.2.1.2.2.1.12
  4098. indexes:
  4099. - labelname: ifIndex
  4100. type: gauge
  4101. - name: ifInDiscards
  4102. oid: 1.3.6.1.2.1.2.2.1.13
  4103. type: counter
  4104. help: The number of inbound packets which were chosen to be discarded even though
  4105. no errors had been detected to prevent their being deliverable to a higher-layer
  4106. protocol - 1.3.6.1.2.1.2.2.1.13
  4107. indexes:
  4108. - labelname: ifIndex
  4109. type: gauge
  4110. - name: ifInErrors
  4111. oid: 1.3.6.1.2.1.2.2.1.14
  4112. type: counter
  4113. help: For packet-oriented interfaces, the number of inbound packets that contained
  4114. errors preventing them from being deliverable to a higher-layer protocol -
  4115. 1.3.6.1.2.1.2.2.1.14
  4116. indexes:
  4117. - labelname: ifIndex
  4118. type: gauge
  4119. - name: ifInUnknownProtos
  4120. oid: 1.3.6.1.2.1.2.2.1.15
  4121. type: counter
  4122. help: For packet-oriented interfaces, the number of packets received via the
  4123. interface which were discarded because of an unknown or unsupported protocol
  4124. - 1.3.6.1.2.1.2.2.1.15
  4125. indexes:
  4126. - labelname: ifIndex
  4127. type: gauge
  4128. - name: ifOutOctets
  4129. oid: 1.3.6.1.2.1.2.2.1.16
  4130. type: counter
  4131. help: The total number of octets transmitted out of the interface, including
  4132. framing characters - 1.3.6.1.2.1.2.2.1.16
  4133. indexes:
  4134. - labelname: ifIndex
  4135. type: gauge
  4136. - name: ifOutUcastPkts
  4137. oid: 1.3.6.1.2.1.2.2.1.17
  4138. type: counter
  4139. help: The total number of packets that higher-level protocols requested be transmitted,
  4140. and which were not addressed to a multicast or broadcast address at this sub-layer,
  4141. including those that were discarded or not sent - 1.3.6.1.2.1.2.2.1.17
  4142. indexes:
  4143. - labelname: ifIndex
  4144. type: gauge
  4145. - name: ifOutNUcastPkts
  4146. oid: 1.3.6.1.2.1.2.2.1.18
  4147. type: counter
  4148. help: The total number of packets that higher-level protocols requested be transmitted,
  4149. and which were addressed to a multicast or broadcast address at this sub-layer,
  4150. including those that were discarded or not sent - 1.3.6.1.2.1.2.2.1.18
  4151. indexes:
  4152. - labelname: ifIndex
  4153. type: gauge
  4154. - name: ifOutDiscards
  4155. oid: 1.3.6.1.2.1.2.2.1.19
  4156. type: counter
  4157. help: The number of outbound packets which were chosen to be discarded even
  4158. though no errors had been detected to prevent their being transmitted - 1.3.6.1.2.1.2.2.1.19
  4159. indexes:
  4160. - labelname: ifIndex
  4161. type: gauge
  4162. - name: ifOutErrors
  4163. oid: 1.3.6.1.2.1.2.2.1.20
  4164. type: counter
  4165. help: For packet-oriented interfaces, the number of outbound packets that could
  4166. not be transmitted because of errors - 1.3.6.1.2.1.2.2.1.20
  4167. indexes:
  4168. - labelname: ifIndex
  4169. type: gauge
  4170. - name: ifOutQLen
  4171. oid: 1.3.6.1.2.1.2.2.1.21
  4172. type: gauge
  4173. help: The length of the output packet queue (in packets). - 1.3.6.1.2.1.2.2.1.21
  4174. indexes:
  4175. - labelname: ifIndex
  4176. type: gauge
  4177. - name: ifSpecific
  4178. oid: 1.3.6.1.2.1.2.2.1.22
  4179. type: OctetString
  4180. help: A reference to MIB definitions specific to the particular media being
  4181. used to realize the interface - 1.3.6.1.2.1.2.2.1.22
  4182. indexes:
  4183. - labelname: ifIndex
  4184. type: gauge
  4185. - name: hrMemorySize
  4186. oid: 1.3.6.1.2.1.25.2.2
  4187. type: gauge
  4188. help: The amount of physical read-write main memory, typically RAM, contained
  4189. by the host. - 1.3.6.1.2.1.25.2.2
  4190. - name: hrStorageIndex
  4191. oid: 1.3.6.1.2.1.25.2.3.1.1
  4192. type: gauge
  4193. help: A unique value for each logical storage area contained by the host. -
  4194. 1.3.6.1.2.1.25.2.3.1.1
  4195. indexes:
  4196. - labelname: hrStorageIndex
  4197. type: gauge
  4198. lookups:
  4199. - labels:
  4200. - hrStorageIndex
  4201. labelname: hrStorageDescr
  4202. oid: 1.3.6.1.2.1.25.2.3.1.3
  4203. type: DisplayString
  4204. - labels: []
  4205. labelname: hrStorageIndex
  4206. - name: hrStorageType
  4207. oid: 1.3.6.1.2.1.25.2.3.1.2
  4208. type: OctetString
  4209. help: The type of storage represented by this entry. - 1.3.6.1.2.1.25.2.3.1.2
  4210. indexes:
  4211. - labelname: hrStorageIndex
  4212. type: gauge
  4213. lookups:
  4214. - labels:
  4215. - hrStorageIndex
  4216. labelname: hrStorageDescr
  4217. oid: 1.3.6.1.2.1.25.2.3.1.3
  4218. type: DisplayString
  4219. - labels: []
  4220. labelname: hrStorageIndex
  4221. - name: hrStorageDescr
  4222. oid: 1.3.6.1.2.1.25.2.3.1.3
  4223. type: DisplayString
  4224. help: A description of the type and instance of the storage described by this
  4225. entry. - 1.3.6.1.2.1.25.2.3.1.3
  4226. indexes:
  4227. - labelname: hrStorageIndex
  4228. type: gauge
  4229. lookups:
  4230. - labels:
  4231. - hrStorageIndex
  4232. labelname: hrStorageDescr
  4233. oid: 1.3.6.1.2.1.25.2.3.1.3
  4234. type: DisplayString
  4235. - labels: []
  4236. labelname: hrStorageIndex
  4237. - name: hrStorageAllocationUnits
  4238. oid: 1.3.6.1.2.1.25.2.3.1.4
  4239. type: gauge
  4240. help: The size, in bytes, of the data objects allocated from this pool - 1.3.6.1.2.1.25.2.3.1.4
  4241. indexes:
  4242. - labelname: hrStorageIndex
  4243. type: gauge
  4244. lookups:
  4245. - labels:
  4246. - hrStorageIndex
  4247. labelname: hrStorageDescr
  4248. oid: 1.3.6.1.2.1.25.2.3.1.3
  4249. type: DisplayString
  4250. - labels: []
  4251. labelname: hrStorageIndex
  4252. - name: hrStorageSize
  4253. oid: 1.3.6.1.2.1.25.2.3.1.5
  4254. type: gauge
  4255. help: The size of the storage represented by this entry, in units of hrStorageAllocationUnits
  4256. - 1.3.6.1.2.1.25.2.3.1.5
  4257. indexes:
  4258. - labelname: hrStorageIndex
  4259. type: gauge
  4260. lookups:
  4261. - labels:
  4262. - hrStorageIndex
  4263. labelname: hrStorageDescr
  4264. oid: 1.3.6.1.2.1.25.2.3.1.3
  4265. type: DisplayString
  4266. - labels: []
  4267. labelname: hrStorageIndex
  4268. - name: hrStorageUsed
  4269. oid: 1.3.6.1.2.1.25.2.3.1.6
  4270. type: gauge
  4271. help: The amount of the storage represented by this entry that is allocated,
  4272. in units of hrStorageAllocationUnits. - 1.3.6.1.2.1.25.2.3.1.6
  4273. indexes:
  4274. - labelname: hrStorageIndex
  4275. type: gauge
  4276. lookups:
  4277. - labels:
  4278. - hrStorageIndex
  4279. labelname: hrStorageDescr
  4280. oid: 1.3.6.1.2.1.25.2.3.1.3
  4281. type: DisplayString
  4282. - labels: []
  4283. labelname: hrStorageIndex
  4284. - name: hrStorageAllocationFailures
  4285. oid: 1.3.6.1.2.1.25.2.3.1.7
  4286. type: counter
  4287. help: The number of requests for storage represented by this entry that could
  4288. not be honored due to not enough storage - 1.3.6.1.2.1.25.2.3.1.7
  4289. indexes:
  4290. - labelname: hrStorageIndex
  4291. type: gauge
  4292. lookups:
  4293. - labels:
  4294. - hrStorageIndex
  4295. labelname: hrStorageDescr
  4296. oid: 1.3.6.1.2.1.25.2.3.1.3
  4297. type: DisplayString
  4298. - labels: []
  4299. labelname: hrStorageIndex
  4300. - name: ifName
  4301. oid: 1.3.6.1.2.1.31.1.1.1.1
  4302. type: DisplayString
  4303. help: The textual name of the interface - 1.3.6.1.2.1.31.1.1.1.1
  4304. indexes:
  4305. - labelname: ifIndex
  4306. type: gauge
  4307. - name: ifInMulticastPkts
  4308. oid: 1.3.6.1.2.1.31.1.1.1.2
  4309. type: counter
  4310. help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
  4311. which were addressed to a multicast address at this sub-layer - 1.3.6.1.2.1.31.1.1.1.2
  4312. indexes:
  4313. - labelname: ifIndex
  4314. type: gauge
  4315. - name: ifInBroadcastPkts
  4316. oid: 1.3.6.1.2.1.31.1.1.1.3
  4317. type: counter
  4318. help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
  4319. which were addressed to a broadcast address at this sub-layer - 1.3.6.1.2.1.31.1.1.1.3
  4320. indexes:
  4321. - labelname: ifIndex
  4322. type: gauge
  4323. - name: ifOutMulticastPkts
  4324. oid: 1.3.6.1.2.1.31.1.1.1.4
  4325. type: counter
  4326. help: The total number of packets that higher-level protocols requested be transmitted,
  4327. and which were addressed to a multicast address at this sub-layer, including
  4328. those that were discarded or not sent - 1.3.6.1.2.1.31.1.1.1.4
  4329. indexes:
  4330. - labelname: ifIndex
  4331. type: gauge
  4332. - name: ifOutBroadcastPkts
  4333. oid: 1.3.6.1.2.1.31.1.1.1.5
  4334. type: counter
  4335. help: The total number of packets that higher-level protocols requested be transmitted,
  4336. and which were addressed to a broadcast address at this sub-layer, including
  4337. those that were discarded or not sent - 1.3.6.1.2.1.31.1.1.1.5
  4338. indexes:
  4339. - labelname: ifIndex
  4340. type: gauge
  4341. - name: ifHCInOctets
  4342. oid: 1.3.6.1.2.1.31.1.1.1.6
  4343. type: counter
  4344. help: The total number of octets received on the interface, including framing
  4345. characters - 1.3.6.1.2.1.31.1.1.1.6
  4346. indexes:
  4347. - labelname: ifIndex
  4348. type: gauge
  4349. - name: ifHCInUcastPkts
  4350. oid: 1.3.6.1.2.1.31.1.1.1.7
  4351. type: counter
  4352. help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
  4353. which were not addressed to a multicast or broadcast address at this sub-layer
  4354. - 1.3.6.1.2.1.31.1.1.1.7
  4355. indexes:
  4356. - labelname: ifIndex
  4357. type: gauge
  4358. - name: ifHCInMulticastPkts
  4359. oid: 1.3.6.1.2.1.31.1.1.1.8
  4360. type: counter
  4361. help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
  4362. which were addressed to a multicast address at this sub-layer - 1.3.6.1.2.1.31.1.1.1.8
  4363. indexes:
  4364. - labelname: ifIndex
  4365. type: gauge
  4366. - name: ifHCInBroadcastPkts
  4367. oid: 1.3.6.1.2.1.31.1.1.1.9
  4368. type: counter
  4369. help: The number of packets, delivered by this sub-layer to a higher (sub-)layer,
  4370. which were addressed to a broadcast address at this sub-layer - 1.3.6.1.2.1.31.1.1.1.9
  4371. indexes:
  4372. - labelname: ifIndex
  4373. type: gauge
  4374. - name: ifHCOutOctets
  4375. oid: 1.3.6.1.2.1.31.1.1.1.10
  4376. type: counter
  4377. help: The total number of octets transmitted out of the interface, including
  4378. framing characters - 1.3.6.1.2.1.31.1.1.1.10
  4379. indexes:
  4380. - labelname: ifIndex
  4381. type: gauge
  4382. - name: ifHCOutUcastPkts
  4383. oid: 1.3.6.1.2.1.31.1.1.1.11
  4384. type: counter
  4385. help: The total number of packets that higher-level protocols requested be transmitted,
  4386. and which were not addressed to a multicast or broadcast address at this sub-layer,
  4387. including those that were discarded or not sent - 1.3.6.1.2.1.31.1.1.1.11
  4388. indexes:
  4389. - labelname: ifIndex
  4390. type: gauge
  4391. - name: ifHCOutMulticastPkts
  4392. oid: 1.3.6.1.2.1.31.1.1.1.12
  4393. type: counter
  4394. help: The total number of packets that higher-level protocols requested be transmitted,
  4395. and which were addressed to a multicast address at this sub-layer, including
  4396. those that were discarded or not sent - 1.3.6.1.2.1.31.1.1.1.12
  4397. indexes:
  4398. - labelname: ifIndex
  4399. type: gauge
  4400. - name: ifHCOutBroadcastPkts
  4401. oid: 1.3.6.1.2.1.31.1.1.1.13
  4402. type: counter
  4403. help: The total number of packets that higher-level protocols requested be transmitted,
  4404. and which were addressed to a broadcast address at this sub-layer, including
  4405. those that were discarded or not sent - 1.3.6.1.2.1.31.1.1.1.13
  4406. indexes:
  4407. - labelname: ifIndex
  4408. type: gauge
  4409. - name: ifLinkUpDownTrapEnable
  4410. oid: 1.3.6.1.2.1.31.1.1.1.14
  4411. type: gauge
  4412. help: Indicates whether linkUp/linkDown traps should be generated for this interface
  4413. - 1.3.6.1.2.1.31.1.1.1.14
  4414. indexes:
  4415. - labelname: ifIndex
  4416. type: gauge
  4417. enum_values:
  4418. 1: enabled
  4419. 2: disabled
  4420. - name: ifHighSpeed
  4421. oid: 1.3.6.1.2.1.31.1.1.1.15
  4422. type: gauge
  4423. help: An estimate of the interface's current bandwidth in units of 1,000,000
  4424. bits per second - 1.3.6.1.2.1.31.1.1.1.15
  4425. indexes:
  4426. - labelname: ifIndex
  4427. type: gauge
  4428. - name: ifPromiscuousMode
  4429. oid: 1.3.6.1.2.1.31.1.1.1.16
  4430. type: gauge
  4431. help: This object has a value of false(2) if this interface only accepts packets/frames
  4432. that are addressed to this station - 1.3.6.1.2.1.31.1.1.1.16
  4433. indexes:
  4434. - labelname: ifIndex
  4435. type: gauge
  4436. enum_values:
  4437. 1: "true"
  4438. 2: "false"
  4439. - name: ifConnectorPresent
  4440. oid: 1.3.6.1.2.1.31.1.1.1.17
  4441. type: gauge
  4442. help: This object has the value 'true(1)' if the interface sublayer has a physical
  4443. connector and the value 'false(2)' otherwise. - 1.3.6.1.2.1.31.1.1.1.17
  4444. indexes:
  4445. - labelname: ifIndex
  4446. type: gauge
  4447. enum_values:
  4448. 1: "true"
  4449. 2: "false"
  4450. - name: ifAlias
  4451. oid: 1.3.6.1.2.1.31.1.1.1.18
  4452. type: DisplayString
  4453. help: This object is an 'alias' name for the interface as specified by a network
  4454. manager, and provides a non-volatile 'handle' for the interface - 1.3.6.1.2.1.31.1.1.1.18
  4455. indexes:
  4456. - labelname: ifIndex
  4457. type: gauge
  4458. - name: ifCounterDiscontinuityTime
  4459. oid: 1.3.6.1.2.1.31.1.1.1.19
  4460. type: gauge
  4461. help: The value of sysUpTime on the most recent occasion at which any one or
  4462. more of this interface's counters suffered a discontinuity - 1.3.6.1.2.1.31.1.1.1.19
  4463. indexes:
  4464. - labelname: ifIndex
  4465. type: gauge
  4466. - name: laNames
  4467. oid: 1.3.6.1.4.1.2021.10.1.2
  4468. type: DisplayString
  4469. help: The list of loadave names we're watching. - 1.3.6.1.4.1.2021.10.1.2
  4470. indexes:
  4471. - labelname: laIndex
  4472. type: gauge
  4473. lookups:
  4474. - labels:
  4475. - laIndex
  4476. labelname: laNames
  4477. oid: 1.3.6.1.4.1.2021.10.1.2
  4478. type: DisplayString
  4479. - labels: []
  4480. labelname: laIndex
  4481. - name: laLoadInt
  4482. oid: 1.3.6.1.4.1.2021.10.1.5
  4483. type: gauge
  4484. help: The 1,5 and 15 minute load averages as an integer - 1.3.6.1.4.1.2021.10.1.5
  4485. indexes:
  4486. - labelname: laIndex
  4487. type: gauge
  4488. lookups:
  4489. - labels:
  4490. - laIndex
  4491. labelname: laNames
  4492. oid: 1.3.6.1.4.1.2021.10.1.2
  4493. type: DisplayString
  4494. - labels: []
  4495. labelname: laIndex
  4496. - name: ssCpuSystem
  4497. oid: 1.3.6.1.4.1.2021.11.10
  4498. type: gauge
  4499. help: The percentage of CPU time spent processing system-level code, calculated
  4500. over the last minute - 1.3.6.1.4.1.2021.11.10
  4501. - name: ssCpuIdle
  4502. oid: 1.3.6.1.4.1.2021.11.11
  4503. type: gauge
  4504. help: The percentage of processor time spent idle, calculated over the last
  4505. minute - 1.3.6.1.4.1.2021.11.11
  4506. - name: ssCpuUser
  4507. oid: 1.3.6.1.4.1.2021.11.9
  4508. type: gauge
  4509. help: The percentage of CPU time spent processing user-level code, calculated
  4510. over the last minute - 1.3.6.1.4.1.2021.11.9
  4511. - name: memIndex
  4512. oid: 1.3.6.1.4.1.2021.4.1
  4513. type: gauge
  4514. help: Bogus Index - 1.3.6.1.4.1.2021.4.1
  4515. - name: memErrorName
  4516. oid: 1.3.6.1.4.1.2021.4.2
  4517. type: DisplayString
  4518. help: Bogus Name - 1.3.6.1.4.1.2021.4.2
  4519. - name: memTotalSwap
  4520. oid: 1.3.6.1.4.1.2021.4.3
  4521. type: gauge
  4522. help: The total amount of swap space configured for this host. - 1.3.6.1.4.1.2021.4.3
  4523. - name: memAvailSwap
  4524. oid: 1.3.6.1.4.1.2021.4.4
  4525. type: gauge
  4526. help: The amount of swap space currently unused or available. - 1.3.6.1.4.1.2021.4.4
  4527. - name: memTotalReal
  4528. oid: 1.3.6.1.4.1.2021.4.5
  4529. type: gauge
  4530. help: The total amount of real/physical memory installed on this host. - 1.3.6.1.4.1.2021.4.5
  4531. - name: memAvailReal
  4532. oid: 1.3.6.1.4.1.2021.4.6
  4533. type: gauge
  4534. help: The amount of real/physical memory currently unused or available. - 1.3.6.1.4.1.2021.4.6
  4535. - name: memTotalSwapTXT
  4536. oid: 1.3.6.1.4.1.2021.4.7
  4537. type: gauge
  4538. help: The total amount of swap space or virtual memory allocated for text pages
  4539. on this host - 1.3.6.1.4.1.2021.4.7
  4540. - name: memAvailSwapTXT
  4541. oid: 1.3.6.1.4.1.2021.4.8
  4542. type: gauge
  4543. help: The amount of swap space or virtual memory currently being used by text
  4544. pages on this host - 1.3.6.1.4.1.2021.4.8
  4545. - name: memTotalRealTXT
  4546. oid: 1.3.6.1.4.1.2021.4.9
  4547. type: gauge
  4548. help: The total amount of real/physical memory allocated for text pages on this
  4549. host - 1.3.6.1.4.1.2021.4.9
  4550. - name: memAvailRealTXT
  4551. oid: 1.3.6.1.4.1.2021.4.10
  4552. type: gauge
  4553. help: The amount of real/physical memory currently being used by text pages
  4554. on this host - 1.3.6.1.4.1.2021.4.10
  4555. - name: memTotalFree
  4556. oid: 1.3.6.1.4.1.2021.4.11
  4557. type: gauge
  4558. help: The total amount of memory free or available for use on this host - 1.3.6.1.4.1.2021.4.11
  4559. - name: memMinimumSwap
  4560. oid: 1.3.6.1.4.1.2021.4.12
  4561. type: gauge
  4562. help: The minimum amount of swap space expected to be kept free or available
  4563. during normal operation of this host - 1.3.6.1.4.1.2021.4.12
  4564. - name: memShared
  4565. oid: 1.3.6.1.4.1.2021.4.13
  4566. type: gauge
  4567. help: The total amount of real or virtual memory currently allocated for use
  4568. as shared memory - 1.3.6.1.4.1.2021.4.13
  4569. - name: memBuffer
  4570. oid: 1.3.6.1.4.1.2021.4.14
  4571. type: gauge
  4572. help: The total amount of real or virtual memory currently allocated for use
  4573. as memory buffers - 1.3.6.1.4.1.2021.4.14
  4574. - name: memCached
  4575. oid: 1.3.6.1.4.1.2021.4.15
  4576. type: gauge
  4577. help: The total amount of real or virtual memory currently allocated for use
  4578. as cached memory - 1.3.6.1.4.1.2021.4.15
  4579. - name: memUsedSwapTXT
  4580. oid: 1.3.6.1.4.1.2021.4.16
  4581. type: gauge
  4582. help: The amount of swap space or virtual memory currently being used by text
  4583. pages on this host - 1.3.6.1.4.1.2021.4.16
  4584. - name: memUsedRealTXT
  4585. oid: 1.3.6.1.4.1.2021.4.17
  4586. type: gauge
  4587. help: The amount of real/physical memory currently being used by text pages
  4588. on this host - 1.3.6.1.4.1.2021.4.17
  4589. - name: memTotalSwapX
  4590. oid: 1.3.6.1.4.1.2021.4.18
  4591. type: counter
  4592. help: The total amount of swap space configured for this host. - 1.3.6.1.4.1.2021.4.18
  4593. - name: memAvailSwapX
  4594. oid: 1.3.6.1.4.1.2021.4.19
  4595. type: counter
  4596. help: The amount of swap space currently unused or available. - 1.3.6.1.4.1.2021.4.19
  4597. - name: memTotalRealX
  4598. oid: 1.3.6.1.4.1.2021.4.20
  4599. type: counter
  4600. help: The total amount of real/physical memory installed on this host. - 1.3.6.1.4.1.2021.4.20
  4601. - name: memAvailRealX
  4602. oid: 1.3.6.1.4.1.2021.4.21
  4603. type: counter
  4604. help: The amount of real/physical memory currently unused or available. - 1.3.6.1.4.1.2021.4.21
  4605. - name: memTotalFreeX
  4606. oid: 1.3.6.1.4.1.2021.4.22
  4607. type: counter
  4608. help: The total amount of memory free or available for use on this host - 1.3.6.1.4.1.2021.4.22
  4609. - name: memMinimumSwapX
  4610. oid: 1.3.6.1.4.1.2021.4.23
  4611. type: counter
  4612. help: The minimum amount of swap space expected to be kept free or available
  4613. during normal operation of this host - 1.3.6.1.4.1.2021.4.23
  4614. - name: memSharedX
  4615. oid: 1.3.6.1.4.1.2021.4.24
  4616. type: counter
  4617. help: The total amount of real or virtual memory currently allocated for use
  4618. as shared memory - 1.3.6.1.4.1.2021.4.24
  4619. - name: memBufferX
  4620. oid: 1.3.6.1.4.1.2021.4.25
  4621. type: counter
  4622. help: The total amount of real or virtual memory currently allocated for use
  4623. as memory buffers - 1.3.6.1.4.1.2021.4.25
  4624. - name: memCachedX
  4625. oid: 1.3.6.1.4.1.2021.4.26
  4626. type: counter
  4627. help: The total amount of real or virtual memory currently allocated for use
  4628. as cached memory - 1.3.6.1.4.1.2021.4.26
  4629. - name: memSwapError
  4630. oid: 1.3.6.1.4.1.2021.4.100
  4631. type: gauge
  4632. help: Indicates whether the amount of available swap space (as reported by 'memAvailSwap(4)'),
  4633. is less than the desired minimum (specified by 'memMinimumSwap(12)'). - 1.3.6.1.4.1.2021.4.100
  4634. enum_values:
  4635. 0: noError
  4636. 1: error
  4637. - name: memSwapErrorMsg
  4638. oid: 1.3.6.1.4.1.2021.4.101
  4639. type: DisplayString
  4640. help: Describes whether the amount of available swap space (as reported by 'memAvailSwap(4)'),
  4641. is less than the desired minimum (specified by 'memMinimumSwap(12)'). - 1.3.6.1.4.1.2021.4.101
  4642. - name: systemStatus
  4643. oid: 1.3.6.1.4.1.6574.1.1
  4644. type: gauge
  4645. help: Synology system status Each meanings of status represented describe below
  4646. - 1.3.6.1.4.1.6574.1.1
  4647. - name: temperature
  4648. oid: 1.3.6.1.4.1.6574.1.2
  4649. type: gauge
  4650. help: Synology system temperature The temperature of Disk Station uses Celsius
  4651. degree. - 1.3.6.1.4.1.6574.1.2
  4652. - name: powerStatus
  4653. oid: 1.3.6.1.4.1.6574.1.3
  4654. type: gauge
  4655. help: Synology power status Each meanings of status represented describe below
  4656. - 1.3.6.1.4.1.6574.1.3
  4657. - name: systemFanStatus
  4658. oid: 1.3.6.1.4.1.6574.1.4.1
  4659. type: gauge
  4660. help: Synology system fan status Each meanings of status represented describe
  4661. below - 1.3.6.1.4.1.6574.1.4.1
  4662. - name: cpuFanStatus
  4663. oid: 1.3.6.1.4.1.6574.1.4.2
  4664. type: gauge
  4665. help: Synology cpu fan status Each meanings of status represented describe below
  4666. - 1.3.6.1.4.1.6574.1.4.2
  4667. - name: modelName
  4668. oid: 1.3.6.1.4.1.6574.1.5.1
  4669. type: DisplayString
  4670. help: The Model name of this NAS - 1.3.6.1.4.1.6574.1.5.1
  4671. - name: serialNumber
  4672. oid: 1.3.6.1.4.1.6574.1.5.2
  4673. type: OctetString
  4674. help: The serial number of this NAS - 1.3.6.1.4.1.6574.1.5.2
  4675. - name: version
  4676. oid: 1.3.6.1.4.1.6574.1.5.3
  4677. type: OctetString
  4678. help: The version of this DSM - 1.3.6.1.4.1.6574.1.5.3
  4679. - name: upgradeAvailable
  4680. oid: 1.3.6.1.4.1.6574.1.5.4
  4681. type: gauge
  4682. help: This oid is for checking whether there is a latest DSM can be upgraded
  4683. - 1.3.6.1.4.1.6574.1.5.4
  4684. - name: controllerNumber
  4685. oid: 1.3.6.1.4.1.6574.1.6
  4686. type: gauge
  4687. help: Synology system controller number Controller A(0) Controller B(1) - 1.3.6.1.4.1.6574.1.6
  4688. - name: storageIOIndex
  4689. oid: 1.3.6.1.4.1.6574.101.1.1.1
  4690. type: gauge
  4691. help: Reference index for each observed device. - 1.3.6.1.4.1.6574.101.1.1.1
  4692. indexes:
  4693. - labelname: storageIOIndex
  4694. type: gauge
  4695. lookups:
  4696. - labels:
  4697. - storageIOIndex
  4698. labelname: storageIODevice
  4699. oid: 1.3.6.1.4.1.6574.101.1.1.2
  4700. type: DisplayString
  4701. - labels: []
  4702. labelname: storageIOIndex
  4703. - name: storageIODevice
  4704. oid: 1.3.6.1.4.1.6574.101.1.1.2
  4705. type: DisplayString
  4706. help: The name of the device we are counting/checking. - 1.3.6.1.4.1.6574.101.1.1.2
  4707. indexes:
  4708. - labelname: storageIOIndex
  4709. type: gauge
  4710. lookups:
  4711. - labels:
  4712. - storageIOIndex
  4713. labelname: storageIODevice
  4714. oid: 1.3.6.1.4.1.6574.101.1.1.2
  4715. type: DisplayString
  4716. - labels: []
  4717. labelname: storageIOIndex
  4718. - name: storageIONRead
  4719. oid: 1.3.6.1.4.1.6574.101.1.1.3
  4720. type: counter
  4721. help: The number of bytes read from this device since boot. - 1.3.6.1.4.1.6574.101.1.1.3
  4722. indexes:
  4723. - labelname: storageIOIndex
  4724. type: gauge
  4725. lookups:
  4726. - labels:
  4727. - storageIOIndex
  4728. labelname: storageIODevice
  4729. oid: 1.3.6.1.4.1.6574.101.1.1.2
  4730. type: DisplayString
  4731. - labels: []
  4732. labelname: storageIOIndex
  4733. - name: storageIONWritten
  4734. oid: 1.3.6.1.4.1.6574.101.1.1.4
  4735. type: counter
  4736. help: The number of bytes written to this device since boot. - 1.3.6.1.4.1.6574.101.1.1.4
  4737. indexes:
  4738. - labelname: storageIOIndex
  4739. type: gauge
  4740. lookups:
  4741. - labels:
  4742. - storageIOIndex
  4743. labelname: storageIODevice
  4744. oid: 1.3.6.1.4.1.6574.101.1.1.2
  4745. type: DisplayString
  4746. - labels: []
  4747. labelname: storageIOIndex
  4748. - name: storageIOReads
  4749. oid: 1.3.6.1.4.1.6574.101.1.1.5
  4750. type: counter
  4751. help: The number of read accesses from this device since boot. - 1.3.6.1.4.1.6574.101.1.1.5
  4752. indexes:
  4753. - labelname: storageIOIndex
  4754. type: gauge
  4755. lookups:
  4756. - labels:
  4757. - storageIOIndex
  4758. labelname: storageIODevice
  4759. oid: 1.3.6.1.4.1.6574.101.1.1.2
  4760. type: DisplayString
  4761. - labels: []
  4762. labelname: storageIOIndex
  4763. - name: storageIOWrites
  4764. oid: 1.3.6.1.4.1.6574.101.1.1.6
  4765. type: counter
  4766. help: The number of write accesses to this device since boot. - 1.3.6.1.4.1.6574.101.1.1.6
  4767. indexes:
  4768. - labelname: storageIOIndex
  4769. type: gauge
  4770. lookups:
  4771. - labels:
  4772. - storageIOIndex
  4773. labelname: storageIODevice
  4774. oid: 1.3.6.1.4.1.6574.101.1.1.2
  4775. type: DisplayString
  4776. - labels: []
  4777. labelname: storageIOIndex
  4778. - name: storageIOLA
  4779. oid: 1.3.6.1.4.1.6574.101.1.1.8
  4780. type: gauge
  4781. help: The load of disk (%) - 1.3.6.1.4.1.6574.101.1.1.8
  4782. indexes:
  4783. - labelname: storageIOIndex
  4784. type: gauge
  4785. lookups:
  4786. - labels:
  4787. - storageIOIndex
  4788. labelname: storageIODevice
  4789. oid: 1.3.6.1.4.1.6574.101.1.1.2
  4790. type: DisplayString
  4791. - labels: []
  4792. labelname: storageIOIndex
  4793. - name: storageIOLA1
  4794. oid: 1.3.6.1.4.1.6574.101.1.1.9
  4795. type: gauge
  4796. help: The 1 minute average load of disk (%) - 1.3.6.1.4.1.6574.101.1.1.9
  4797. indexes:
  4798. - labelname: storageIOIndex
  4799. type: gauge
  4800. lookups:
  4801. - labels:
  4802. - storageIOIndex
  4803. labelname: storageIODevice
  4804. oid: 1.3.6.1.4.1.6574.101.1.1.2
  4805. type: DisplayString
  4806. - labels: []
  4807. labelname: storageIOIndex
  4808. - name: storageIOLA5
  4809. oid: 1.3.6.1.4.1.6574.101.1.1.10
  4810. type: gauge
  4811. help: The 5 minute average load of disk (%) - 1.3.6.1.4.1.6574.101.1.1.10
  4812. indexes:
  4813. - labelname: storageIOIndex
  4814. type: gauge
  4815. lookups:
  4816. - labels:
  4817. - storageIOIndex
  4818. labelname: storageIODevice
  4819. oid: 1.3.6.1.4.1.6574.101.1.1.2
  4820. type: DisplayString
  4821. - labels: []
  4822. labelname: storageIOIndex
  4823. - name: storageIOLA15
  4824. oid: 1.3.6.1.4.1.6574.101.1.1.11
  4825. type: gauge
  4826. help: The 15 minute average load of disk (%) - 1.3.6.1.4.1.6574.101.1.1.11
  4827. indexes:
  4828. - labelname: storageIOIndex
  4829. type: gauge
  4830. lookups:
  4831. - labels:
  4832. - storageIOIndex
  4833. labelname: storageIODevice
  4834. oid: 1.3.6.1.4.1.6574.101.1.1.2
  4835. type: DisplayString
  4836. - labels: []
  4837. labelname: storageIOIndex
  4838. - name: storageIONReadX
  4839. oid: 1.3.6.1.4.1.6574.101.1.1.12
  4840. type: counter
  4841. help: The number of bytes read from this device since boot. - 1.3.6.1.4.1.6574.101.1.1.12
  4842. indexes:
  4843. - labelname: storageIOIndex
  4844. type: gauge
  4845. lookups:
  4846. - labels:
  4847. - storageIOIndex
  4848. labelname: storageIODevice
  4849. oid: 1.3.6.1.4.1.6574.101.1.1.2
  4850. type: DisplayString
  4851. - labels: []
  4852. labelname: storageIOIndex
  4853. - name: storageIONWrittenX
  4854. oid: 1.3.6.1.4.1.6574.101.1.1.13
  4855. type: counter
  4856. help: The number of bytes written to this device since boot. - 1.3.6.1.4.1.6574.101.1.1.13
  4857. indexes:
  4858. - labelname: storageIOIndex
  4859. type: gauge
  4860. lookups:
  4861. - labels:
  4862. - storageIOIndex
  4863. labelname: storageIODevice
  4864. oid: 1.3.6.1.4.1.6574.101.1.1.2
  4865. type: DisplayString
  4866. - labels: []
  4867. labelname: storageIOIndex
  4868. - name: storageIODeviceSerial
  4869. oid: 1.3.6.1.4.1.6574.101.1.1.14
  4870. type: DisplayString
  4871. help: The name of the device we are counting/checking. - 1.3.6.1.4.1.6574.101.1.1.14
  4872. indexes:
  4873. - labelname: storageIOIndex
  4874. type: gauge
  4875. lookups:
  4876. - labels:
  4877. - storageIOIndex
  4878. labelname: storageIODevice
  4879. oid: 1.3.6.1.4.1.6574.101.1.1.2
  4880. type: DisplayString
  4881. - labels: []
  4882. labelname: storageIOIndex
  4883. - name: spaceIOIndex
  4884. oid: 1.3.6.1.4.1.6574.102.1.1.1
  4885. type: gauge
  4886. help: Reference index for each observed device. - 1.3.6.1.4.1.6574.102.1.1.1
  4887. indexes:
  4888. - labelname: spaceIOIndex
  4889. type: gauge
  4890. lookups:
  4891. - labels:
  4892. - spaceIOIndex
  4893. labelname: spaceIODevice
  4894. oid: 1.3.6.1.4.1.6574.102.1.1.2
  4895. type: DisplayString
  4896. - labels: []
  4897. labelname: spaceIOIndex
  4898. - name: spaceIODevice
  4899. oid: 1.3.6.1.4.1.6574.102.1.1.2
  4900. type: DisplayString
  4901. help: The name of the device we are counting/checking. - 1.3.6.1.4.1.6574.102.1.1.2
  4902. indexes:
  4903. - labelname: spaceIOIndex
  4904. type: gauge
  4905. lookups:
  4906. - labels:
  4907. - spaceIOIndex
  4908. labelname: spaceIODevice
  4909. oid: 1.3.6.1.4.1.6574.102.1.1.2
  4910. type: DisplayString
  4911. - labels: []
  4912. labelname: spaceIOIndex
  4913. - name: spaceIONRead
  4914. oid: 1.3.6.1.4.1.6574.102.1.1.3
  4915. type: counter
  4916. help: The number of bytes read from this device since boot. - 1.3.6.1.4.1.6574.102.1.1.3
  4917. indexes:
  4918. - labelname: spaceIOIndex
  4919. type: gauge
  4920. lookups:
  4921. - labels:
  4922. - spaceIOIndex
  4923. labelname: spaceIODevice
  4924. oid: 1.3.6.1.4.1.6574.102.1.1.2
  4925. type: DisplayString
  4926. - labels: []
  4927. labelname: spaceIOIndex
  4928. - name: spaceIONWritten
  4929. oid: 1.3.6.1.4.1.6574.102.1.1.4
  4930. type: counter
  4931. help: The number of bytes written to this device since boot. - 1.3.6.1.4.1.6574.102.1.1.4
  4932. indexes:
  4933. - labelname: spaceIOIndex
  4934. type: gauge
  4935. lookups:
  4936. - labels:
  4937. - spaceIOIndex
  4938. labelname: spaceIODevice
  4939. oid: 1.3.6.1.4.1.6574.102.1.1.2
  4940. type: DisplayString
  4941. - labels: []
  4942. labelname: spaceIOIndex
  4943. - name: spaceIOReads
  4944. oid: 1.3.6.1.4.1.6574.102.1.1.5
  4945. type: counter
  4946. help: The number of read accesses from this device since boot. - 1.3.6.1.4.1.6574.102.1.1.5
  4947. indexes:
  4948. - labelname: spaceIOIndex
  4949. type: gauge
  4950. lookups:
  4951. - labels:
  4952. - spaceIOIndex
  4953. labelname: spaceIODevice
  4954. oid: 1.3.6.1.4.1.6574.102.1.1.2
  4955. type: DisplayString
  4956. - labels: []
  4957. labelname: spaceIOIndex
  4958. - name: spaceIOWrites
  4959. oid: 1.3.6.1.4.1.6574.102.1.1.6
  4960. type: counter
  4961. help: The number of write accesses to this device since boot. - 1.3.6.1.4.1.6574.102.1.1.6
  4962. indexes:
  4963. - labelname: spaceIOIndex
  4964. type: gauge
  4965. lookups:
  4966. - labels:
  4967. - spaceIOIndex
  4968. labelname: spaceIODevice
  4969. oid: 1.3.6.1.4.1.6574.102.1.1.2
  4970. type: DisplayString
  4971. - labels: []
  4972. labelname: spaceIOIndex
  4973. - name: spaceIOLA
  4974. oid: 1.3.6.1.4.1.6574.102.1.1.8
  4975. type: gauge
  4976. help: The load of disk (%) - 1.3.6.1.4.1.6574.102.1.1.8
  4977. indexes:
  4978. - labelname: spaceIOIndex
  4979. type: gauge
  4980. lookups:
  4981. - labels:
  4982. - spaceIOIndex
  4983. labelname: spaceIODevice
  4984. oid: 1.3.6.1.4.1.6574.102.1.1.2
  4985. type: DisplayString
  4986. - labels: []
  4987. labelname: spaceIOIndex
  4988. - name: spaceIOLA1
  4989. oid: 1.3.6.1.4.1.6574.102.1.1.9
  4990. type: gauge
  4991. help: The 1 minute average load of disk (%) - 1.3.6.1.4.1.6574.102.1.1.9
  4992. indexes:
  4993. - labelname: spaceIOIndex
  4994. type: gauge
  4995. lookups:
  4996. - labels:
  4997. - spaceIOIndex
  4998. labelname: spaceIODevice
  4999. oid: 1.3.6.1.4.1.6574.102.1.1.2
  5000. type: DisplayString
  5001. - labels: []
  5002. labelname: spaceIOIndex
  5003. - name: spaceIOLA5
  5004. oid: 1.3.6.1.4.1.6574.102.1.1.10
  5005. type: gauge
  5006. help: The 5 minute average load of disk (%) - 1.3.6.1.4.1.6574.102.1.1.10
  5007. indexes:
  5008. - labelname: spaceIOIndex
  5009. type: gauge
  5010. lookups:
  5011. - labels:
  5012. - spaceIOIndex
  5013. labelname: spaceIODevice
  5014. oid: 1.3.6.1.4.1.6574.102.1.1.2
  5015. type: DisplayString
  5016. - labels: []
  5017. labelname: spaceIOIndex
  5018. - name: spaceIOLA15
  5019. oid: 1.3.6.1.4.1.6574.102.1.1.11
  5020. type: gauge
  5021. help: The 15 minute average load of disk (%) - 1.3.6.1.4.1.6574.102.1.1.11
  5022. indexes:
  5023. - labelname: spaceIOIndex
  5024. type: gauge
  5025. lookups:
  5026. - labels:
  5027. - spaceIOIndex
  5028. labelname: spaceIODevice
  5029. oid: 1.3.6.1.4.1.6574.102.1.1.2
  5030. type: DisplayString
  5031. - labels: []
  5032. labelname: spaceIOIndex
  5033. - name: spaceIONReadX
  5034. oid: 1.3.6.1.4.1.6574.102.1.1.12
  5035. type: counter
  5036. help: The number of bytes read from this device since boot. - 1.3.6.1.4.1.6574.102.1.1.12
  5037. indexes:
  5038. - labelname: spaceIOIndex
  5039. type: gauge
  5040. lookups:
  5041. - labels:
  5042. - spaceIOIndex
  5043. labelname: spaceIODevice
  5044. oid: 1.3.6.1.4.1.6574.102.1.1.2
  5045. type: DisplayString
  5046. - labels: []
  5047. labelname: spaceIOIndex
  5048. - name: spaceIONWrittenX
  5049. oid: 1.3.6.1.4.1.6574.102.1.1.13
  5050. type: counter
  5051. help: The number of bytes written to this device since boot. - 1.3.6.1.4.1.6574.102.1.1.13
  5052. indexes:
  5053. - labelname: spaceIOIndex
  5054. type: gauge
  5055. lookups:
  5056. - labels:
  5057. - spaceIOIndex
  5058. labelname: spaceIODevice
  5059. oid: 1.3.6.1.4.1.6574.102.1.1.2
  5060. type: DisplayString
  5061. - labels: []
  5062. labelname: spaceIOIndex
  5063. - name: spaceUUID
  5064. oid: 1.3.6.1.4.1.6574.102.1.1.14
  5065. type: DisplayString
  5066. help: The uuid of space. - 1.3.6.1.4.1.6574.102.1.1.14
  5067. indexes:
  5068. - labelname: spaceIOIndex
  5069. type: gauge
  5070. lookups:
  5071. - labels:
  5072. - spaceIOIndex
  5073. labelname: spaceIODevice
  5074. oid: 1.3.6.1.4.1.6574.102.1.1.2
  5075. type: DisplayString
  5076. - labels: []
  5077. labelname: spaceIOIndex
  5078. - name: iSCSILUNInfoIndex
  5079. oid: 1.3.6.1.4.1.6574.104.1.1.1
  5080. type: gauge
  5081. help: LUN info index - 1.3.6.1.4.1.6574.104.1.1.1
  5082. indexes:
  5083. - labelname: iSCSILUNInfoIndex
  5084. type: gauge
  5085. - name: iSCSILUNUUID
  5086. oid: 1.3.6.1.4.1.6574.104.1.1.2
  5087. type: OctetString
  5088. help: LUN uuid - 1.3.6.1.4.1.6574.104.1.1.2
  5089. indexes:
  5090. - labelname: iSCSILUNInfoIndex
  5091. type: gauge
  5092. - name: iSCSILUNName
  5093. oid: 1.3.6.1.4.1.6574.104.1.1.3
  5094. type: OctetString
  5095. help: LUN name - 1.3.6.1.4.1.6574.104.1.1.3
  5096. indexes:
  5097. - labelname: iSCSILUNInfoIndex
  5098. type: gauge
  5099. - name: iSCSILUNThroughputReadHigh
  5100. oid: 1.3.6.1.4.1.6574.104.1.1.4
  5101. type: gauge
  5102. help: LUN read throughput over 32 bits part - 1.3.6.1.4.1.6574.104.1.1.4
  5103. indexes:
  5104. - labelname: iSCSILUNInfoIndex
  5105. type: gauge
  5106. - name: iSCSILUNThroughputReadLow
  5107. oid: 1.3.6.1.4.1.6574.104.1.1.5
  5108. type: gauge
  5109. help: LUN read throughput in unsigned 32 bit - 1.3.6.1.4.1.6574.104.1.1.5
  5110. indexes:
  5111. - labelname: iSCSILUNInfoIndex
  5112. type: gauge
  5113. - name: iSCSILUNThroughputWriteHigh
  5114. oid: 1.3.6.1.4.1.6574.104.1.1.6
  5115. type: gauge
  5116. help: LUN write throughput over 32 bits part - 1.3.6.1.4.1.6574.104.1.1.6
  5117. indexes:
  5118. - labelname: iSCSILUNInfoIndex
  5119. type: gauge
  5120. - name: iSCSILUNThroughputWriteLow
  5121. oid: 1.3.6.1.4.1.6574.104.1.1.7
  5122. type: gauge
  5123. help: LUN write throughput in unsigned 32 bit - 1.3.6.1.4.1.6574.104.1.1.7
  5124. indexes:
  5125. - labelname: iSCSILUNInfoIndex
  5126. type: gauge
  5127. - name: iSCSILUNIopsRead
  5128. oid: 1.3.6.1.4.1.6574.104.1.1.8
  5129. type: gauge
  5130. help: LUN read iops - 1.3.6.1.4.1.6574.104.1.1.8
  5131. indexes:
  5132. - labelname: iSCSILUNInfoIndex
  5133. type: gauge
  5134. - name: iSCSILUNIopsWrite
  5135. oid: 1.3.6.1.4.1.6574.104.1.1.9
  5136. type: gauge
  5137. help: LUN write iops - 1.3.6.1.4.1.6574.104.1.1.9
  5138. indexes:
  5139. - labelname: iSCSILUNInfoIndex
  5140. type: gauge
  5141. - name: iSCSILUNDiskLatencyRead
  5142. oid: 1.3.6.1.4.1.6574.104.1.1.10
  5143. type: gauge
  5144. help: LUN disk latency when reading - 1.3.6.1.4.1.6574.104.1.1.10
  5145. indexes:
  5146. - labelname: iSCSILUNInfoIndex
  5147. type: gauge
  5148. - name: iSCSILUNDiskLatencyWrite
  5149. oid: 1.3.6.1.4.1.6574.104.1.1.11
  5150. type: gauge
  5151. help: LUN disk latency when writing - 1.3.6.1.4.1.6574.104.1.1.11
  5152. indexes:
  5153. - labelname: iSCSILUNInfoIndex
  5154. type: gauge
  5155. - name: iSCSILUNNetworkLatencyTx
  5156. oid: 1.3.6.1.4.1.6574.104.1.1.12
  5157. type: gauge
  5158. help: LUN transfer data network latency - 1.3.6.1.4.1.6574.104.1.1.12
  5159. indexes:
  5160. - labelname: iSCSILUNInfoIndex
  5161. type: gauge
  5162. - name: iSCSILUNNetworkLatencyRx
  5163. oid: 1.3.6.1.4.1.6574.104.1.1.13
  5164. type: gauge
  5165. help: LUN receive data network latency - 1.3.6.1.4.1.6574.104.1.1.13
  5166. indexes:
  5167. - labelname: iSCSILUNInfoIndex
  5168. type: gauge
  5169. - name: iSCSILUNIoSizeRead
  5170. oid: 1.3.6.1.4.1.6574.104.1.1.14
  5171. type: gauge
  5172. help: LUN average io size when reading - 1.3.6.1.4.1.6574.104.1.1.14
  5173. indexes:
  5174. - labelname: iSCSILUNInfoIndex
  5175. type: gauge
  5176. - name: iSCSILUNIoSizeWrite
  5177. oid: 1.3.6.1.4.1.6574.104.1.1.15
  5178. type: gauge
  5179. help: LUN average io size when writing - 1.3.6.1.4.1.6574.104.1.1.15
  5180. indexes:
  5181. - labelname: iSCSILUNInfoIndex
  5182. type: gauge
  5183. - name: iSCSILUNQueueDepth
  5184. oid: 1.3.6.1.4.1.6574.104.1.1.16
  5185. type: gauge
  5186. help: Num of iSCSI commands in LUN queue - 1.3.6.1.4.1.6574.104.1.1.16
  5187. indexes:
  5188. - labelname: iSCSILUNInfoIndex
  5189. type: gauge
  5190. - name: iSCSILUNType
  5191. oid: 1.3.6.1.4.1.6574.104.1.1.17
  5192. type: OctetString
  5193. help: LUN type - 1.3.6.1.4.1.6574.104.1.1.17
  5194. indexes:
  5195. - labelname: iSCSILUNInfoIndex
  5196. type: gauge
  5197. - name: iSCSILUNDiskLatencyAvg
  5198. oid: 1.3.6.1.4.1.6574.104.1.1.18
  5199. type: gauge
  5200. help: Average latency of LUN disk - 1.3.6.1.4.1.6574.104.1.1.18
  5201. indexes:
  5202. - labelname: iSCSILUNInfoIndex
  5203. type: gauge
  5204. - name: iSCSILUNThinProvisionVolFreeMBs
  5205. oid: 1.3.6.1.4.1.6574.104.1.1.19
  5206. type: gauge
  5207. help: Free space(MB) of thin provisioning lun's volume - 1.3.6.1.4.1.6574.104.1.1.19
  5208. indexes:
  5209. - labelname: iSCSILUNInfoIndex
  5210. type: gauge
  5211. - name: diskIndex
  5212. oid: 1.3.6.1.4.1.6574.2.1.1.1
  5213. type: gauge
  5214. help: The index of disk table - 1.3.6.1.4.1.6574.2.1.1.1
  5215. indexes:
  5216. - labelname: diskIndex
  5217. type: gauge
  5218. lookups:
  5219. - labels:
  5220. - diskIndex
  5221. labelname: diskID
  5222. oid: 1.3.6.1.4.1.6574.2.1.1.2
  5223. type: OctetString
  5224. - labels: []
  5225. labelname: diskIndex
  5226. - name: diskID
  5227. oid: 1.3.6.1.4.1.6574.2.1.1.2
  5228. type: OctetString
  5229. help: Synology disk ID The ID of disk is assigned by disk Station. - 1.3.6.1.4.1.6574.2.1.1.2
  5230. indexes:
  5231. - labelname: diskIndex
  5232. type: gauge
  5233. lookups:
  5234. - labels:
  5235. - diskIndex
  5236. labelname: diskID
  5237. oid: 1.3.6.1.4.1.6574.2.1.1.2
  5238. type: OctetString
  5239. - labels: []
  5240. labelname: diskIndex
  5241. - name: diskModel
  5242. oid: 1.3.6.1.4.1.6574.2.1.1.3
  5243. type: DisplayString
  5244. help: Synology disk model name The disk model name will be showed here. - 1.3.6.1.4.1.6574.2.1.1.3
  5245. indexes:
  5246. - labelname: diskIndex
  5247. type: gauge
  5248. lookups:
  5249. - labels:
  5250. - diskIndex
  5251. labelname: diskID
  5252. oid: 1.3.6.1.4.1.6574.2.1.1.2
  5253. type: OctetString
  5254. - labels: []
  5255. labelname: diskIndex
  5256. - name: diskType
  5257. oid: 1.3.6.1.4.1.6574.2.1.1.4
  5258. type: DisplayString
  5259. help: Synology disk type The type of disk will be showed here, including SATA,
  5260. SSD and so on. - 1.3.6.1.4.1.6574.2.1.1.4
  5261. indexes:
  5262. - labelname: diskIndex
  5263. type: gauge
  5264. lookups:
  5265. - labels:
  5266. - diskIndex
  5267. labelname: diskID
  5268. oid: 1.3.6.1.4.1.6574.2.1.1.2
  5269. type: OctetString
  5270. - labels: []
  5271. labelname: diskIndex
  5272. - name: diskStatus
  5273. oid: 1.3.6.1.4.1.6574.2.1.1.5
  5274. type: gauge
  5275. help: Synology disk status Each meanings of status represented describe below
  5276. - 1.3.6.1.4.1.6574.2.1.1.5
  5277. indexes:
  5278. - labelname: diskIndex
  5279. type: gauge
  5280. lookups:
  5281. - labels:
  5282. - diskIndex
  5283. labelname: diskID
  5284. oid: 1.3.6.1.4.1.6574.2.1.1.2
  5285. type: OctetString
  5286. - labels: []
  5287. labelname: diskIndex
  5288. - name: diskTemperature
  5289. oid: 1.3.6.1.4.1.6574.2.1.1.6
  5290. type: gauge
  5291. help: Synology disk temperature The temperature of each disk uses Celsius degree.
  5292. - 1.3.6.1.4.1.6574.2.1.1.6
  5293. indexes:
  5294. - labelname: diskIndex
  5295. type: gauge
  5296. lookups:
  5297. - labels:
  5298. - diskIndex
  5299. labelname: diskID
  5300. oid: 1.3.6.1.4.1.6574.2.1.1.2
  5301. type: OctetString
  5302. - labels: []
  5303. labelname: diskIndex
  5304. - name: diskRole
  5305. oid: 1.3.6.1.4.1.6574.2.1.1.7
  5306. type: OctetString
  5307. help: Synology disk role The role of the disk in system - 1.3.6.1.4.1.6574.2.1.1.7
  5308. indexes:
  5309. - labelname: diskIndex
  5310. type: gauge
  5311. lookups:
  5312. - labels:
  5313. - diskIndex
  5314. labelname: diskID
  5315. oid: 1.3.6.1.4.1.6574.2.1.1.2
  5316. type: OctetString
  5317. - labels: []
  5318. labelname: diskIndex
  5319. - name: diskRetry
  5320. oid: 1.3.6.1.4.1.6574.2.1.1.8
  5321. type: gauge
  5322. help: Synology disk retry count The count of each disk connection retries. -
  5323. 1.3.6.1.4.1.6574.2.1.1.8
  5324. indexes:
  5325. - labelname: diskIndex
  5326. type: gauge
  5327. lookups:
  5328. - labels:
  5329. - diskIndex
  5330. labelname: diskID
  5331. oid: 1.3.6.1.4.1.6574.2.1.1.2
  5332. type: OctetString
  5333. - labels: []
  5334. labelname: diskIndex
  5335. - name: diskBadSector
  5336. oid: 1.3.6.1.4.1.6574.2.1.1.9
  5337. type: gauge
  5338. help: Synology disk bad sector count The count of each disk I/O bad sector.
  5339. - 1.3.6.1.4.1.6574.2.1.1.9
  5340. indexes:
  5341. - labelname: diskIndex
  5342. type: gauge
  5343. lookups:
  5344. - labels:
  5345. - diskIndex
  5346. labelname: diskID
  5347. oid: 1.3.6.1.4.1.6574.2.1.1.2
  5348. type: OctetString
  5349. - labels: []
  5350. labelname: diskIndex
  5351. - name: diskIdentifyFail
  5352. oid: 1.3.6.1.4.1.6574.2.1.1.10
  5353. type: gauge
  5354. help: Synology disk identify fail count The count of each disk identify fails.
  5355. - 1.3.6.1.4.1.6574.2.1.1.10
  5356. indexes:
  5357. - labelname: diskIndex
  5358. type: gauge
  5359. lookups:
  5360. - labels:
  5361. - diskIndex
  5362. labelname: diskID
  5363. oid: 1.3.6.1.4.1.6574.2.1.1.2
  5364. type: OctetString
  5365. - labels: []
  5366. labelname: diskIndex
  5367. - name: diskRemainLife
  5368. oid: 1.3.6.1.4.1.6574.2.1.1.11
  5369. type: gauge
  5370. help: Synology disk remainLife The estimate remain life of each disk. - 1.3.6.1.4.1.6574.2.1.1.11
  5371. indexes:
  5372. - labelname: diskIndex
  5373. type: gauge
  5374. lookups:
  5375. - labels:
  5376. - diskIndex
  5377. labelname: diskID
  5378. oid: 1.3.6.1.4.1.6574.2.1.1.2
  5379. type: OctetString
  5380. - labels: []
  5381. labelname: diskIndex
  5382. - name: diskName
  5383. oid: 1.3.6.1.4.1.6574.2.1.1.12
  5384. type: OctetString
  5385. help: Synology disk name The name of disk which align to storage manager. -
  5386. 1.3.6.1.4.1.6574.2.1.1.12
  5387. indexes:
  5388. - labelname: diskIndex
  5389. type: gauge
  5390. lookups:
  5391. - labels:
  5392. - diskIndex
  5393. labelname: diskID
  5394. oid: 1.3.6.1.4.1.6574.2.1.1.2
  5395. type: OctetString
  5396. - labels: []
  5397. labelname: diskIndex
  5398. - name: diskHealthStatus
  5399. oid: 1.3.6.1.4.1.6574.2.1.1.13
  5400. type: gauge
  5401. help: Synology disk health status Each meanings of status represented describe
  5402. below - 1.3.6.1.4.1.6574.2.1.1.13
  5403. indexes:
  5404. - labelname: diskIndex
  5405. type: gauge
  5406. lookups:
  5407. - labels:
  5408. - diskIndex
  5409. labelname: diskID
  5410. oid: 1.3.6.1.4.1.6574.2.1.1.2
  5411. type: OctetString
  5412. - labels: []
  5413. labelname: diskIndex
  5414. - name: raidIndex
  5415. oid: 1.3.6.1.4.1.6574.3.1.1.1
  5416. type: gauge
  5417. help: The index of raid table - 1.3.6.1.4.1.6574.3.1.1.1
  5418. indexes:
  5419. - labelname: raidIndex
  5420. type: gauge
  5421. lookups:
  5422. - labels:
  5423. - raidIndex
  5424. labelname: raidName
  5425. oid: 1.3.6.1.4.1.6574.3.1.1.2
  5426. type: DisplayString
  5427. - labels: []
  5428. labelname: raidIndex
  5429. - name: raidName
  5430. oid: 1.3.6.1.4.1.6574.3.1.1.2
  5431. type: DisplayString
  5432. help: Synology raid name The name of each raid will be showed here. - 1.3.6.1.4.1.6574.3.1.1.2
  5433. indexes:
  5434. - labelname: raidIndex
  5435. type: gauge
  5436. lookups:
  5437. - labels:
  5438. - raidIndex
  5439. labelname: raidName
  5440. oid: 1.3.6.1.4.1.6574.3.1.1.2
  5441. type: DisplayString
  5442. - labels: []
  5443. labelname: raidIndex
  5444. - name: raidStatus
  5445. oid: 1.3.6.1.4.1.6574.3.1.1.3
  5446. type: gauge
  5447. help: Synology Raid status Each meanings of status represented describe below
  5448. - 1.3.6.1.4.1.6574.3.1.1.3
  5449. indexes:
  5450. - labelname: raidIndex
  5451. type: gauge
  5452. lookups:
  5453. - labels:
  5454. - raidIndex
  5455. labelname: raidName
  5456. oid: 1.3.6.1.4.1.6574.3.1.1.2
  5457. type: DisplayString
  5458. - labels: []
  5459. labelname: raidIndex
  5460. - name: raidFreeSize
  5461. oid: 1.3.6.1.4.1.6574.3.1.1.4
  5462. type: gauge
  5463. help: Synology raid freesize Free space in bytes. - 1.3.6.1.4.1.6574.3.1.1.4
  5464. indexes:
  5465. - labelname: raidIndex
  5466. type: gauge
  5467. lookups:
  5468. - labels:
  5469. - raidIndex
  5470. labelname: raidName
  5471. oid: 1.3.6.1.4.1.6574.3.1.1.2
  5472. type: DisplayString
  5473. - labels: []
  5474. labelname: raidIndex
  5475. - name: raidTotalSize
  5476. oid: 1.3.6.1.4.1.6574.3.1.1.5
  5477. type: gauge
  5478. help: Synology raid totalsize Total space in bytes. - 1.3.6.1.4.1.6574.3.1.1.5
  5479. indexes:
  5480. - labelname: raidIndex
  5481. type: gauge
  5482. lookups:
  5483. - labels:
  5484. - raidIndex
  5485. labelname: raidName
  5486. oid: 1.3.6.1.4.1.6574.3.1.1.2
  5487. type: DisplayString
  5488. - labels: []
  5489. labelname: raidIndex
  5490. - name: raidHotspareCnt
  5491. oid: 1.3.6.1.4.1.6574.3.1.1.6
  5492. type: gauge
  5493. help: Synology raid hotspare Total hotspare disks count - 1.3.6.1.4.1.6574.3.1.1.6
  5494. indexes:
  5495. - labelname: raidIndex
  5496. type: gauge
  5497. lookups:
  5498. - labels:
  5499. - raidIndex
  5500. labelname: raidName
  5501. oid: 1.3.6.1.4.1.6574.3.1.1.2
  5502. type: DisplayString
  5503. - labels: []
  5504. labelname: raidIndex
  5505. - name: upsDeviceModel
  5506. oid: 1.3.6.1.4.1.6574.4.1.1
  5507. type: DisplayString
  5508. help: Device model - 1.3.6.1.4.1.6574.4.1.1
  5509. - name: upsDeviceManufacturer
  5510. oid: 1.3.6.1.4.1.6574.4.1.2
  5511. type: DisplayString
  5512. help: Device manufacturer - 1.3.6.1.4.1.6574.4.1.2
  5513. - name: upsDeviceSerial
  5514. oid: 1.3.6.1.4.1.6574.4.1.3
  5515. type: DisplayString
  5516. help: Device serial number. - 1.3.6.1.4.1.6574.4.1.3
  5517. - name: upsDeviceType
  5518. oid: 1.3.6.1.4.1.6574.4.1.4
  5519. type: DisplayString
  5520. help: Device type (ups, pdu, scd, psu) - 1.3.6.1.4.1.6574.4.1.4
  5521. - name: upsDeviceDescription
  5522. oid: 1.3.6.1.4.1.6574.4.1.5
  5523. type: DisplayString
  5524. help: Device description. - 1.3.6.1.4.1.6574.4.1.5
  5525. - name: upsDeviceContact
  5526. oid: 1.3.6.1.4.1.6574.4.1.6
  5527. type: DisplayString
  5528. help: Device administrator name. - 1.3.6.1.4.1.6574.4.1.6
  5529. - name: upsDeviceLocation
  5530. oid: 1.3.6.1.4.1.6574.4.1.7
  5531. type: DisplayString
  5532. help: Device physical location. - 1.3.6.1.4.1.6574.4.1.7
  5533. - name: upsDevicePart
  5534. oid: 1.3.6.1.4.1.6574.4.1.8
  5535. type: DisplayString
  5536. help: Device part number. - 1.3.6.1.4.1.6574.4.1.8
  5537. - name: upsDeviceMACAddr
  5538. oid: 1.3.6.1.4.1.6574.4.1.9
  5539. type: DisplayString
  5540. help: Physical network address of the device. - 1.3.6.1.4.1.6574.4.1.9
  5541. - name: upsInfoStatus
  5542. oid: 1.3.6.1.4.1.6574.4.2.1
  5543. type: DisplayString
  5544. help: UPS status. - 1.3.6.1.4.1.6574.4.2.1
  5545. - name: upsInfoAlarm
  5546. oid: 1.3.6.1.4.1.6574.4.2.2
  5547. type: DisplayString
  5548. help: UPS alarms - 1.3.6.1.4.1.6574.4.2.2
  5549. - name: upsInfoTime
  5550. oid: 1.3.6.1.4.1.6574.4.2.3
  5551. type: DisplayString
  5552. help: Internal UPS clock time - 1.3.6.1.4.1.6574.4.2.3
  5553. - name: upsInfoDate
  5554. oid: 1.3.6.1.4.1.6574.4.2.4
  5555. type: DisplayString
  5556. help: Internal UPS clock date - 1.3.6.1.4.1.6574.4.2.4
  5557. - name: upsInfoModel
  5558. oid: 1.3.6.1.4.1.6574.4.2.5
  5559. type: DisplayString
  5560. help: UPS model - 1.3.6.1.4.1.6574.4.2.5
  5561. - name: upsInfoMfrName
  5562. oid: 1.3.6.1.4.1.6574.4.2.6.1
  5563. type: DisplayString
  5564. help: UPS manufacturer - 1.3.6.1.4.1.6574.4.2.6.1
  5565. - name: upsInfoMfrDate
  5566. oid: 1.3.6.1.4.1.6574.4.2.6.2
  5567. type: DisplayString
  5568. help: UPS manufacturing date - 1.3.6.1.4.1.6574.4.2.6.2
  5569. - name: upsInfoSerial
  5570. oid: 1.3.6.1.4.1.6574.4.2.7
  5571. type: DisplayString
  5572. help: UPS serial number - 1.3.6.1.4.1.6574.4.2.7
  5573. - name: upsInfoVendorID
  5574. oid: 1.3.6.1.4.1.6574.4.2.8
  5575. type: DisplayString
  5576. help: Vendor ID for USB devices - 1.3.6.1.4.1.6574.4.2.8
  5577. - name: upsInfoProductID
  5578. oid: 1.3.6.1.4.1.6574.4.2.9
  5579. type: DisplayString
  5580. help: Product ID for USB devices - 1.3.6.1.4.1.6574.4.2.9
  5581. - name: upsInfoFirmwareName
  5582. oid: 1.3.6.1.4.1.6574.4.2.10.1
  5583. type: DisplayString
  5584. help: UPS firmware - 1.3.6.1.4.1.6574.4.2.10.1
  5585. - name: upsInfoFirmwareAux
  5586. oid: 1.3.6.1.4.1.6574.4.2.10.2
  5587. type: DisplayString
  5588. help: Auxiliary device firmware - 1.3.6.1.4.1.6574.4.2.10.2
  5589. - name: upsInfoTemperature
  5590. oid: 1.3.6.1.4.1.6574.4.2.11
  5591. type: Float
  5592. help: UPS temperature (degrees C) - 1.3.6.1.4.1.6574.4.2.11
  5593. - name: upsInfoLoadValue
  5594. oid: 1.3.6.1.4.1.6574.4.2.12.1
  5595. type: Float
  5596. help: Load on UPS (percent) - 1.3.6.1.4.1.6574.4.2.12.1
  5597. - name: upsInfoLoadHigh
  5598. oid: 1.3.6.1.4.1.6574.4.2.12.2
  5599. type: Float
  5600. help: Load when UPS switches to overload condition (OVER) (percent) - 1.3.6.1.4.1.6574.4.2.12.2
  5601. - name: upsInfoID
  5602. oid: 1.3.6.1.4.1.6574.4.2.13
  5603. type: DisplayString
  5604. help: UPS system identifier - 1.3.6.1.4.1.6574.4.2.13
  5605. - name: upsInfoDelayStart
  5606. oid: 1.3.6.1.4.1.6574.4.2.14.1
  5607. type: gauge
  5608. help: Interval to wait before restarting the load (seconds) - 1.3.6.1.4.1.6574.4.2.14.1
  5609. - name: upsInfoDelayReboot
  5610. oid: 1.3.6.1.4.1.6574.4.2.14.2
  5611. type: gauge
  5612. help: Interval to wait before rebooting the UPS (seconds) - 1.3.6.1.4.1.6574.4.2.14.2
  5613. - name: upsInfoDelayShutdown
  5614. oid: 1.3.6.1.4.1.6574.4.2.14.3
  5615. type: gauge
  5616. help: Interval to wait after shutdown with delay command (seconds) - 1.3.6.1.4.1.6574.4.2.14.3
  5617. - name: upsInfoTimerStart
  5618. oid: 1.3.6.1.4.1.6574.4.2.15.1
  5619. type: gauge
  5620. help: Time before the load will be started (seconds) - 1.3.6.1.4.1.6574.4.2.15.1
  5621. - name: upsInfoTimerReboot
  5622. oid: 1.3.6.1.4.1.6574.4.2.15.2
  5623. type: gauge
  5624. help: Time before the load will be rebooted (seconds) - 1.3.6.1.4.1.6574.4.2.15.2
  5625. - name: upsInfoTimerShutdown
  5626. oid: 1.3.6.1.4.1.6574.4.2.15.3
  5627. type: gauge
  5628. help: Time before the load will be shutdown (seconds) - 1.3.6.1.4.1.6574.4.2.15.3
  5629. - name: upsInfoTestInterval
  5630. oid: 1.3.6.1.4.1.6574.4.2.16.1
  5631. type: gauge
  5632. help: Interval between self tests - 1.3.6.1.4.1.6574.4.2.16.1
  5633. - name: upsInfoTestResult
  5634. oid: 1.3.6.1.4.1.6574.4.2.16.2
  5635. type: DisplayString
  5636. help: Results of last self test - 1.3.6.1.4.1.6574.4.2.16.2
  5637. - name: upsInfoDisplayLanguage
  5638. oid: 1.3.6.1.4.1.6574.4.2.17
  5639. type: DisplayString
  5640. help: Language to use on front panel - 1.3.6.1.4.1.6574.4.2.17
  5641. - name: upsInfoContacts
  5642. oid: 1.3.6.1.4.1.6574.4.2.18
  5643. type: DisplayString
  5644. help: UPS external contact sensors - 1.3.6.1.4.1.6574.4.2.18
  5645. - name: upsInfoEffciency
  5646. oid: 1.3.6.1.4.1.6574.4.2.19
  5647. type: gauge
  5648. help: Efficiency of the UPS (ratio of the output current on the input current)
  5649. (percent) - 1.3.6.1.4.1.6574.4.2.19
  5650. - name: upsInfoPowerValue
  5651. oid: 1.3.6.1.4.1.6574.4.2.20.1
  5652. type: Float
  5653. help: Current value of apparent power (Volt-Amps) - 1.3.6.1.4.1.6574.4.2.20.1
  5654. - name: upsInfoPowerNominal
  5655. oid: 1.3.6.1.4.1.6574.4.2.20.2
  5656. type: Float
  5657. help: Nominal value of apparent power (Volt-Amps) - 1.3.6.1.4.1.6574.4.2.20.2
  5658. - name: upsInfoRealPowerValue
  5659. oid: 1.3.6.1.4.1.6574.4.2.21.1
  5660. type: Float
  5661. help: Current value of real power (Watts) - 1.3.6.1.4.1.6574.4.2.21.1
  5662. - name: upsInfoRealPowerNominal
  5663. oid: 1.3.6.1.4.1.6574.4.2.21.2
  5664. type: Float
  5665. help: Nominal value of real power (Watts) - 1.3.6.1.4.1.6574.4.2.21.2
  5666. - name: upsInfoBeeperStatus
  5667. oid: 1.3.6.1.4.1.6574.4.2.22
  5668. type: DisplayString
  5669. help: UPS beeper status (enabled, disabled or muted) - 1.3.6.1.4.1.6574.4.2.22
  5670. - name: upsInfoType
  5671. oid: 1.3.6.1.4.1.6574.4.2.23
  5672. type: DisplayString
  5673. help: UPS type - 1.3.6.1.4.1.6574.4.2.23
  5674. - name: upsInfoWatchdogStatus
  5675. oid: 1.3.6.1.4.1.6574.4.2.24
  5676. type: DisplayString
  5677. help: UPS watchdog status (enabled or disabled) - 1.3.6.1.4.1.6574.4.2.24
  5678. - name: upsInfoStartAuto
  5679. oid: 1.3.6.1.4.1.6574.4.2.25.1
  5680. type: DisplayString
  5681. help: UPS starts when mains is (re)applied - 1.3.6.1.4.1.6574.4.2.25.1
  5682. - name: upsInfoStartBattery
  5683. oid: 1.3.6.1.4.1.6574.4.2.25.2
  5684. type: DisplayString
  5685. help: Allow to start UPS from battery - 1.3.6.1.4.1.6574.4.2.25.2
  5686. - name: upsInfoStartReboot
  5687. oid: 1.3.6.1.4.1.6574.4.2.25.3
  5688. type: DisplayString
  5689. help: UPS coldstarts from battery (enabled or disabled) - 1.3.6.1.4.1.6574.4.2.25.3
  5690. - name: upsBatteryChargeValue
  5691. oid: 1.3.6.1.4.1.6574.4.3.1.1
  5692. type: Float
  5693. help: Battery charge - 1.3.6.1.4.1.6574.4.3.1.1
  5694. - name: upsBatteryChargeLow
  5695. oid: 1.3.6.1.4.1.6574.4.3.1.2
  5696. type: Float
  5697. help: Remaining battery level when UPS switches to LB (percent) - 1.3.6.1.4.1.6574.4.3.1.2
  5698. - name: upsBatteryChargeRestart
  5699. oid: 1.3.6.1.4.1.6574.4.3.1.3
  5700. type: Float
  5701. help: Minimum battery level for UPS restart after power-off - 1.3.6.1.4.1.6574.4.3.1.3
  5702. - name: upsBatteryChargeWarning
  5703. oid: 1.3.6.1.4.1.6574.4.3.1.4
  5704. type: Float
  5705. help: Battery level when UPS switches to Warning state (percent) - 1.3.6.1.4.1.6574.4.3.1.4
  5706. - name: upsBatteryVoltageValue
  5707. oid: 1.3.6.1.4.1.6574.4.3.2.1
  5708. type: Float
  5709. help: The magnitude of the present battery voltage. - 1.3.6.1.4.1.6574.4.3.2.1
  5710. - name: upsBatteryVoltageNominal
  5711. oid: 1.3.6.1.4.1.6574.4.3.2.2
  5712. type: Float
  5713. help: Nominal battery voltage. - 1.3.6.1.4.1.6574.4.3.2.2
  5714. - name: upsBatteryVoltageLow
  5715. oid: 1.3.6.1.4.1.6574.4.3.2.3
  5716. type: Float
  5717. help: Minimum battery voltage, that triggers FSD status . - 1.3.6.1.4.1.6574.4.3.2.3
  5718. - name: upsBatteryVoltageHigh
  5719. oid: 1.3.6.1.4.1.6574.4.3.2.4
  5720. type: Float
  5721. help: Maximum battery voltage (Ie battery.charge = 100). - 1.3.6.1.4.1.6574.4.3.2.4
  5722. - name: upsBatteryCapacity
  5723. oid: 1.3.6.1.4.1.6574.4.3.3
  5724. type: Float
  5725. help: Battery capacity (Ah) - 1.3.6.1.4.1.6574.4.3.3
  5726. - name: upsBatteryCurrent
  5727. oid: 1.3.6.1.4.1.6574.4.3.4
  5728. type: Float
  5729. help: The present battery current. - 1.3.6.1.4.1.6574.4.3.4
  5730. - name: upsBatteryTemperature
  5731. oid: 1.3.6.1.4.1.6574.4.3.5
  5732. type: Float
  5733. help: The ambient temperature at or near the UPS Battery casing. - 1.3.6.1.4.1.6574.4.3.5
  5734. - name: upsBatteryRuntimeValue
  5735. oid: 1.3.6.1.4.1.6574.4.3.6.1
  5736. type: gauge
  5737. help: Battery runtime (seconds) - 1.3.6.1.4.1.6574.4.3.6.1
  5738. - name: upsBatteryRuntimeLow
  5739. oid: 1.3.6.1.4.1.6574.4.3.6.2
  5740. type: gauge
  5741. help: Remaining battery runtime when UPS switches to LB (seconds) - 1.3.6.1.4.1.6574.4.3.6.2
  5742. - name: upsBatteryRuntimeRestart
  5743. oid: 1.3.6.1.4.1.6574.4.3.6.3
  5744. type: gauge
  5745. help: Minimum battery runtime for UPS restart after power-off (seconds) - 1.3.6.1.4.1.6574.4.3.6.3
  5746. - name: upsBatteryAlarmThreshold
  5747. oid: 1.3.6.1.4.1.6574.4.3.7
  5748. type: DisplayString
  5749. help: Battery alarm threshold - 1.3.6.1.4.1.6574.4.3.7
  5750. - name: upsBatteryDate
  5751. oid: 1.3.6.1.4.1.6574.4.3.8
  5752. type: DisplayString
  5753. help: Battery change date - 1.3.6.1.4.1.6574.4.3.8
  5754. - name: upsBatteryMfrDate
  5755. oid: 1.3.6.1.4.1.6574.4.3.9
  5756. type: DisplayString
  5757. help: Battery manufacturing date - 1.3.6.1.4.1.6574.4.3.9
  5758. - name: upsBatteryPacks
  5759. oid: 1.3.6.1.4.1.6574.4.3.10
  5760. type: gauge
  5761. help: Number of battery packs - 1.3.6.1.4.1.6574.4.3.10
  5762. - name: upsBatteryPacksBad
  5763. oid: 1.3.6.1.4.1.6574.4.3.11
  5764. type: gauge
  5765. help: Number of bad battery packs - 1.3.6.1.4.1.6574.4.3.11
  5766. - name: upsBatteryType
  5767. oid: 1.3.6.1.4.1.6574.4.3.12
  5768. type: DisplayString
  5769. help: Battery chemistry - 1.3.6.1.4.1.6574.4.3.12
  5770. - name: upsBatteryProtection
  5771. oid: 1.3.6.1.4.1.6574.4.3.13
  5772. type: DisplayString
  5773. help: Prevent deep discharge of battery - 1.3.6.1.4.1.6574.4.3.13
  5774. - name: upsBatteryEnergySave
  5775. oid: 1.3.6.1.4.1.6574.4.3.14
  5776. type: DisplayString
  5777. help: Switch off when running on battery and no/low load - 1.3.6.1.4.1.6574.4.3.14
  5778. - name: upsInputVoltageValue
  5779. oid: 1.3.6.1.4.1.6574.4.4.1.1
  5780. type: Float
  5781. help: Input voltage - 1.3.6.1.4.1.6574.4.4.1.1
  5782. - name: upsInputVoltageMax
  5783. oid: 1.3.6.1.4.1.6574.4.4.1.2
  5784. type: Float
  5785. help: Maximum incoming voltage seen - 1.3.6.1.4.1.6574.4.4.1.2
  5786. - name: upsInputVoltageMin
  5787. oid: 1.3.6.1.4.1.6574.4.4.1.3
  5788. type: Float
  5789. help: Minimum incoming voltage seen - 1.3.6.1.4.1.6574.4.4.1.3
  5790. - name: upsInputVoltageNominal
  5791. oid: 1.3.6.1.4.1.6574.4.4.1.4
  5792. type: Float
  5793. help: Nominal input voltage - 1.3.6.1.4.1.6574.4.4.1.4
  5794. - name: upsInputVoltageExtend
  5795. oid: 1.3.6.1.4.1.6574.4.4.1.5
  5796. type: DisplayString
  5797. help: Extended input voltage range - 1.3.6.1.4.1.6574.4.4.1.5
  5798. - name: upsInputVoltageFault
  5799. oid: 1.3.6.1.4.1.6574.4.4.1.6
  5800. type: Float
  5801. help: Input voltage Fault - 1.3.6.1.4.1.6574.4.4.1.6
  5802. - name: upsInputTransferReason
  5803. oid: 1.3.6.1.4.1.6574.4.4.2.1
  5804. type: DisplayString
  5805. help: Reason for last transfer to battery - 1.3.6.1.4.1.6574.4.4.2.1
  5806. - name: upsInputTransferLow
  5807. oid: 1.3.6.1.4.1.6574.4.4.2.2
  5808. type: Float
  5809. help: Low voltage transfer point - 1.3.6.1.4.1.6574.4.4.2.2
  5810. - name: upsInputTransferHigh
  5811. oid: 1.3.6.1.4.1.6574.4.4.2.3
  5812. type: Float
  5813. help: High voltage transfer point - 1.3.6.1.4.1.6574.4.4.2.3
  5814. - name: upsInputTransferLowMin
  5815. oid: 1.3.6.1.4.1.6574.4.4.2.4
  5816. type: Float
  5817. help: smallest settable low voltage transfer point - 1.3.6.1.4.1.6574.4.4.2.4
  5818. - name: upsInputTransferLowMax
  5819. oid: 1.3.6.1.4.1.6574.4.4.2.5
  5820. type: Float
  5821. help: greatest settable low voltage transfer point - 1.3.6.1.4.1.6574.4.4.2.5
  5822. - name: upsInputTransferHighMin
  5823. oid: 1.3.6.1.4.1.6574.4.4.2.6
  5824. type: Float
  5825. help: smallest settable high voltage transfer point - 1.3.6.1.4.1.6574.4.4.2.6
  5826. - name: upsInputTransferHighMax
  5827. oid: 1.3.6.1.4.1.6574.4.4.2.7
  5828. type: Float
  5829. help: greatest settable high voltage transfer point - 1.3.6.1.4.1.6574.4.4.2.7
  5830. - name: upsInputTransferBoostLow
  5831. oid: 1.3.6.1.4.1.6574.4.4.2.8
  5832. type: Float
  5833. help: Low voltage boosting transfer point - 1.3.6.1.4.1.6574.4.4.2.8
  5834. - name: upsInputTransferBoostHigh
  5835. oid: 1.3.6.1.4.1.6574.4.4.2.9
  5836. type: Float
  5837. help: High voltage boosting transfer point - 1.3.6.1.4.1.6574.4.4.2.9
  5838. - name: upsInputTransferTrimLow
  5839. oid: 1.3.6.1.4.1.6574.4.4.2.10
  5840. type: Float
  5841. help: Low voltage trimming transfer point - 1.3.6.1.4.1.6574.4.4.2.10
  5842. - name: upsInputTransferTrimHigh
  5843. oid: 1.3.6.1.4.1.6574.4.4.2.11
  5844. type: Float
  5845. help: High voltage trimming transfer point - 1.3.6.1.4.1.6574.4.4.2.11
  5846. - name: upsInputSensitivity
  5847. oid: 1.3.6.1.4.1.6574.4.4.3
  5848. type: DisplayString
  5849. help: Input power sensitivity - 1.3.6.1.4.1.6574.4.4.3
  5850. - name: upsInputQuality
  5851. oid: 1.3.6.1.4.1.6574.4.4.4
  5852. type: DisplayString
  5853. help: Input power quality - 1.3.6.1.4.1.6574.4.4.4
  5854. - name: upsInputCurrentValue
  5855. oid: 1.3.6.1.4.1.6574.4.4.5.1
  5856. type: Float
  5857. help: Input current (A) - 1.3.6.1.4.1.6574.4.4.5.1
  5858. - name: upsInputCurrentNominal
  5859. oid: 1.3.6.1.4.1.6574.4.4.5.2
  5860. type: Float
  5861. help: Nominal input current (A) - 1.3.6.1.4.1.6574.4.4.5.2
  5862. - name: upsInputFrequencyValue
  5863. oid: 1.3.6.1.4.1.6574.4.4.6.1
  5864. type: Float
  5865. help: Input line frequency (Hz) - 1.3.6.1.4.1.6574.4.4.6.1
  5866. - name: upsInputFrequencyNominal
  5867. oid: 1.3.6.1.4.1.6574.4.4.6.2
  5868. type: Float
  5869. help: Nominal input line frequency (Hz) - 1.3.6.1.4.1.6574.4.4.6.2
  5870. - name: upsInputFrequencyLow
  5871. oid: 1.3.6.1.4.1.6574.4.4.6.3
  5872. type: Float
  5873. help: Input line frequency low (Hz) - 1.3.6.1.4.1.6574.4.4.6.3
  5874. - name: upsInputFrequencyHigh
  5875. oid: 1.3.6.1.4.1.6574.4.4.6.4
  5876. type: Float
  5877. help: Input line frequency high (Hz) - 1.3.6.1.4.1.6574.4.4.6.4
  5878. - name: upsInputFrequencyExtend
  5879. oid: 1.3.6.1.4.1.6574.4.4.6.5
  5880. type: DisplayString
  5881. help: Extended input frequency range - 1.3.6.1.4.1.6574.4.4.6.5
  5882. - name: upsOutputVoltageValue
  5883. oid: 1.3.6.1.4.1.6574.4.5.1.1
  5884. type: Float
  5885. help: Output voltage (V) - 1.3.6.1.4.1.6574.4.5.1.1
  5886. - name: upsOutputVoltageNominal
  5887. oid: 1.3.6.1.4.1.6574.4.5.1.2
  5888. type: Float
  5889. help: Nominal output voltage (V) - 1.3.6.1.4.1.6574.4.5.1.2
  5890. - name: upsOutputFrequencyValue
  5891. oid: 1.3.6.1.4.1.6574.4.5.2.1
  5892. type: Float
  5893. help: Output frequency (Hz) - 1.3.6.1.4.1.6574.4.5.2.1
  5894. - name: upsOutputFrequencyNominal
  5895. oid: 1.3.6.1.4.1.6574.4.5.2.2
  5896. type: Float
  5897. help: Nominal output frequency (Hz) - 1.3.6.1.4.1.6574.4.5.2.2
  5898. - name: upsOutputCurrentValue
  5899. oid: 1.3.6.1.4.1.6574.4.5.3.1
  5900. type: Float
  5901. help: Output current (A) - 1.3.6.1.4.1.6574.4.5.3.1
  5902. - name: upsOutputCurrentNominal
  5903. oid: 1.3.6.1.4.1.6574.4.5.3.2
  5904. type: Float
  5905. help: Nominal output current (A) - 1.3.6.1.4.1.6574.4.5.3.2
  5906. - name: upsAmbientTemperatureValue
  5907. oid: 1.3.6.1.4.1.6574.4.6.1.1
  5908. type: Float
  5909. help: Ambient temperature (degrees C) - 1.3.6.1.4.1.6574.4.6.1.1
  5910. - name: upsAmbientTemperatureAlarm
  5911. oid: 1.3.6.1.4.1.6574.4.6.1.2
  5912. type: DisplayString
  5913. help: Temperature alarm (enabled/disabled) - 1.3.6.1.4.1.6574.4.6.1.2
  5914. - name: upsAmbientTemperatureHigh
  5915. oid: 1.3.6.1.4.1.6574.4.6.1.3
  5916. type: Float
  5917. help: Temperature threshold high (degrees C) - 1.3.6.1.4.1.6574.4.6.1.3
  5918. - name: upsAmbientTemperatureLow
  5919. oid: 1.3.6.1.4.1.6574.4.6.1.4
  5920. type: Float
  5921. help: Temperature threshold low (degrees C) - 1.3.6.1.4.1.6574.4.6.1.4
  5922. - name: upsAmbientTemperatureMax
  5923. oid: 1.3.6.1.4.1.6574.4.6.1.5
  5924. type: Float
  5925. help: Maximum temperature seen (degrees C) - 1.3.6.1.4.1.6574.4.6.1.5
  5926. - name: upsAmbientTemperatureMin
  5927. oid: 1.3.6.1.4.1.6574.4.6.1.6
  5928. type: Float
  5929. help: Minimum temperature seen (degrees C) - 1.3.6.1.4.1.6574.4.6.1.6
  5930. - name: upsAmbientHumidityValue
  5931. oid: 1.3.6.1.4.1.6574.4.6.2.1
  5932. type: Float
  5933. help: Ambient relative humidity (percent) - 1.3.6.1.4.1.6574.4.6.2.1
  5934. - name: upsAmbientHumidityAlarm
  5935. oid: 1.3.6.1.4.1.6574.4.6.2.2
  5936. type: DisplayString
  5937. help: Relative humidity alarm (enabled/disabled) - 1.3.6.1.4.1.6574.4.6.2.2
  5938. - name: upsAmbientHumidityHigh
  5939. oid: 1.3.6.1.4.1.6574.4.6.2.3
  5940. type: Float
  5941. help: Relative humidity threshold high (percent) - 1.3.6.1.4.1.6574.4.6.2.3
  5942. - name: upsAmbientHumidityLow
  5943. oid: 1.3.6.1.4.1.6574.4.6.2.4
  5944. type: Float
  5945. help: Relative humidity threshold low (percent) - 1.3.6.1.4.1.6574.4.6.2.4
  5946. - name: upsAmbientHumidityMax
  5947. oid: 1.3.6.1.4.1.6574.4.6.2.5
  5948. type: Float
  5949. help: Maximum relative humidity seen (percent) - 1.3.6.1.4.1.6574.4.6.2.5
  5950. - name: upsAmbientHumidityMin
  5951. oid: 1.3.6.1.4.1.6574.4.6.2.6
  5952. type: Float
  5953. help: Minimum relative humidity seen (percent) - 1.3.6.1.4.1.6574.4.6.2.6
  5954. - name: upsDriverName
  5955. oid: 1.3.6.1.4.1.6574.4.7.1
  5956. type: DisplayString
  5957. help: Driver name - 1.3.6.1.4.1.6574.4.7.1
  5958. - name: upsDriverVersion
  5959. oid: 1.3.6.1.4.1.6574.4.7.2
  5960. type: DisplayString
  5961. help: Driver version (NUT release) - 1.3.6.1.4.1.6574.4.7.2
  5962. - name: upsDriverVersionData
  5963. oid: 1.3.6.1.4.1.6574.4.7.3
  5964. type: DisplayString
  5965. help: Driver version data - 1.3.6.1.4.1.6574.4.7.3
  5966. - name: upsDriverVersionInternal
  5967. oid: 1.3.6.1.4.1.6574.4.7.4
  5968. type: DisplayString
  5969. help: Internal driver version (if tracked separately) - 1.3.6.1.4.1.6574.4.7.4
  5970. - name: upsDriverPollInterval
  5971. oid: 1.3.6.1.4.1.6574.4.7.5
  5972. type: gauge
  5973. help: Poll interval setup in configuration file - 1.3.6.1.4.1.6574.4.7.5
  5974. - name: upsDriverPort
  5975. oid: 1.3.6.1.4.1.6574.4.7.6
  5976. type: DisplayString
  5977. help: Port setup in configuration file - 1.3.6.1.4.1.6574.4.7.6
  5978. - name: upsDriverPollFrequency
  5979. oid: 1.3.6.1.4.1.6574.4.7.7
  5980. type: gauge
  5981. help: Poll frequency - 1.3.6.1.4.1.6574.4.7.7
  5982. - name: upsDriverProductID
  5983. oid: 1.3.6.1.4.1.6574.4.7.8
  5984. type: DisplayString
  5985. help: Product ID - 1.3.6.1.4.1.6574.4.7.8
  5986. - name: upsDriverSnmpVersion
  5987. oid: 1.3.6.1.4.1.6574.4.7.9
  5988. type: DisplayString
  5989. help: Snmp version - 1.3.6.1.4.1.6574.4.7.9
  5990. - name: upsServerInfo
  5991. oid: 1.3.6.1.4.1.6574.4.8.1
  5992. type: DisplayString
  5993. help: Server information - 1.3.6.1.4.1.6574.4.8.1
  5994. - name: upsServerVersion
  5995. oid: 1.3.6.1.4.1.6574.4.8.2
  5996. type: DisplayString
  5997. help: Server version - 1.3.6.1.4.1.6574.4.8.2
  5998. - name: diskSMARTInfoIndex
  5999. oid: 1.3.6.1.4.1.6574.5.1.1.1
  6000. type: gauge
  6001. help: SMART info index - 1.3.6.1.4.1.6574.5.1.1.1
  6002. indexes:
  6003. - labelname: diskSMARTInfoIndex
  6004. type: gauge
  6005. - name: diskSMARTInfoDevName
  6006. oid: 1.3.6.1.4.1.6574.5.1.1.2
  6007. type: DisplayString
  6008. help: SMART info device name - 1.3.6.1.4.1.6574.5.1.1.2
  6009. indexes:
  6010. - labelname: diskSMARTInfoIndex
  6011. type: gauge
  6012. - name: diskSMARTAttrName
  6013. oid: 1.3.6.1.4.1.6574.5.1.1.3
  6014. type: DisplayString
  6015. help: SMART attribute name - 1.3.6.1.4.1.6574.5.1.1.3
  6016. indexes:
  6017. - labelname: diskSMARTInfoIndex
  6018. type: gauge
  6019. - name: diskSMARTAttrId
  6020. oid: 1.3.6.1.4.1.6574.5.1.1.4
  6021. type: gauge
  6022. help: SMART attribute ID - 1.3.6.1.4.1.6574.5.1.1.4
  6023. indexes:
  6024. - labelname: diskSMARTInfoIndex
  6025. type: gauge
  6026. - name: diskSMARTAttrCurrent
  6027. oid: 1.3.6.1.4.1.6574.5.1.1.5
  6028. type: gauge
  6029. help: SMART attribute current value - 1.3.6.1.4.1.6574.5.1.1.5
  6030. indexes:
  6031. - labelname: diskSMARTInfoIndex
  6032. type: gauge
  6033. - name: diskSMARTAttrWorst
  6034. oid: 1.3.6.1.4.1.6574.5.1.1.6
  6035. type: gauge
  6036. help: SMART attribute worst value - 1.3.6.1.4.1.6574.5.1.1.6
  6037. indexes:
  6038. - labelname: diskSMARTInfoIndex
  6039. type: gauge
  6040. - name: diskSMARTAttrThreshold
  6041. oid: 1.3.6.1.4.1.6574.5.1.1.7
  6042. type: gauge
  6043. help: SMART attribute threshold value - 1.3.6.1.4.1.6574.5.1.1.7
  6044. indexes:
  6045. - labelname: diskSMARTInfoIndex
  6046. type: gauge
  6047. - name: diskSMARTAttrRaw
  6048. oid: 1.3.6.1.4.1.6574.5.1.1.8
  6049. type: gauge
  6050. help: SMART attribute raw value - 1.3.6.1.4.1.6574.5.1.1.8
  6051. indexes:
  6052. - labelname: diskSMARTInfoIndex
  6053. type: gauge
  6054. - name: diskSMARTAttrStatus
  6055. oid: 1.3.6.1.4.1.6574.5.1.1.9
  6056. type: DisplayString
  6057. help: SMART attribute status - 1.3.6.1.4.1.6574.5.1.1.9
  6058. indexes:
  6059. - labelname: diskSMARTInfoIndex
  6060. type: gauge
  6061. - name: serviceInfoIndex
  6062. oid: 1.3.6.1.4.1.6574.6.1.1.1
  6063. type: gauge
  6064. help: Service info index - 1.3.6.1.4.1.6574.6.1.1.1
  6065. indexes:
  6066. - labelname: serviceInfoIndex
  6067. type: gauge
  6068. lookups:
  6069. - labels:
  6070. - serviceInfoIndex
  6071. labelname: serviceName
  6072. oid: 1.3.6.1.4.1.6574.6.1.1.2
  6073. type: DisplayString
  6074. - labels: []
  6075. labelname: serviceInfoIndex
  6076. - name: serviceName
  6077. oid: 1.3.6.1.4.1.6574.6.1.1.2
  6078. type: DisplayString
  6079. help: Service name - 1.3.6.1.4.1.6574.6.1.1.2
  6080. indexes:
  6081. - labelname: serviceInfoIndex
  6082. type: gauge
  6083. lookups:
  6084. - labels:
  6085. - serviceInfoIndex
  6086. labelname: serviceName
  6087. oid: 1.3.6.1.4.1.6574.6.1.1.2
  6088. type: DisplayString
  6089. - labels: []
  6090. labelname: serviceInfoIndex
  6091. - name: serviceUsers
  6092. oid: 1.3.6.1.4.1.6574.6.1.1.3
  6093. type: gauge
  6094. help: Number of users using this service - 1.3.6.1.4.1.6574.6.1.1.3
  6095. indexes:
  6096. - labelname: serviceInfoIndex
  6097. type: gauge
  6098. lookups:
  6099. - labels:
  6100. - serviceInfoIndex
  6101. labelname: serviceName
  6102. oid: 1.3.6.1.4.1.6574.6.1.1.2
  6103. type: DisplayString
  6104. - labels: []
  6105. labelname: serviceInfoIndex
  6106.  
Advertisement