Advertisement
Not a member of Pastebin yet?
Sign Up,
it unlocks many cool features!
- <?php
- /**
- * Observium
- *
- * This file is part of Observium.
- *
- * @package observium
- * @subpackage discovery
- * @copyright (C) 2006-2013 Adam Armstrong, (C) 2013-2019 Observium Limited
- *
- */
- // enterprises.eltek.eltekDistributedPlantV7.acDistribution.acVoltage1.0 = INTEGER: 227
- // enterprises.eltek.eltekDistributedPlantV7.acDistribution.acVoltage2.0 = INTEGER: 227
- // enterprises.eltek.eltekDistributedPlantV7.acDistribution.acVoltage3.0 = INTEGER: 0
- // .1.3.6.1.4.1.12148.9.6.1.0 = 235
- // .1.3.6.1.4.1.12148.9.6.2.0 = 235
- // .1.3.6.1.4.1.12148.9.6.3.0 = 237
- $list[] = array('oid' => '.1.3.6.1.4.1.12148.9.6.1.0', 'descr' => 'AC Voltage 1', 'index' => '1', 'type' => 'acVoltage');
- $list[] = array('oid' => '.1.3.6.1.4.1.12148.9.6.2.0', 'descr' => 'AC Voltage 2', 'index' => '2', 'type' => 'acVoltage');
- $list[] = array('oid' => '.1.3.6.1.4.1.12148.9.6.3.0', 'descr' => 'AC Voltage 3', 'index' => '3', 'type' => 'acVoltage');
- foreach ($list as $entry)
- {
- $value = snmp_get_oid($device, $entry['oid'], 'ELTEK-DISTRIBUTED-MIB');
- if (is_numeric($value))
- {
- discover_sensor('voltage', $device, $entry['oid'], $entry['index'], 'eltek-distributed-mib_acVoltage', $entry['descr'], 1, $value);
- }
- }
- // [rectifierStatusID] => 2
- // [rectifierStatusStatus] => normal
- // [rectifierStatusOutputCurrent] => 42
- // [rectifierStatusOutputVoltage] => 5430
- // [rectifierStatusTemp] => 32
- // [rectifierStatusType] => FLATPACK2 48/2000 HE
- // [rectifierStatusSKU] => 241115.105
- // [rectifierStatusSerialNo] => 1051711xxxx
- // [rectifierStatusRevisionLevel] => 2.1
- //.1.3.6.1.4.1.12148.9.5.5.2.1.1.1 = 2
- //.1.3.6.1.4.1.12148.9.5.5.2.1.2.1 = normal
- //.1.3.6.1.4.1.12148.9.5.5.2.1.3.1 = 42
- //.1.3.6.1.4.1.12148.9.5.5.2.1.4.1 = 5429
- //.1.3.6.1.4.1.12148.9.5.5.2.1.5.1 = 32
- //.1.3.6.1.4.1.12148.9.5.5.2.1.6.1 = FLATPACK2 48/2000 HE
- //.1.3.6.1.4.1.12148.9.5.5.2.1.7.1 = 241115.105
- //.1.3.6.1.4.1.12148.9.5.5.2.1.8.1 = 1051711xxxx
- //.1.3.6.1.4.1.12148.9.5.5.2.1.9.1 = 2.1
- $oids = snmpwalk_cache_oid($device, 'rectifierStatusTable', array(), 'ELTEK-DISTRIBUTED-MIB');
- foreach ($oids as $index => $entry)
- {
- if ($entry['rectifierStatusStatus'] != 'notPresent')
- {
- $descr = 'Rectifier '.$entry['rectifierStatusID']. ' ('.$entry['rectifierStatusType'].')';
- discover_sensor('voltage', $device, '.1.3.6.1.4.1.12148.9.5.5.2.1.4.'.$index, $index, 'eltek-distributed-mib_rectifierStatusOutputVoltage', $descr, 0.01, $entry['rectifierStatusOutputVoltage']);
- discover_sensor('current', $device, '.1.3.6.1.4.1.12148.9.5.5.2.1.3.'.$index, $index, 'eltek-distributed-mib_rectifierStatusOutputCurrent', $descr, 0.1, $entry['rectifierStatusOutputCurrent']);
- discover_sensor('temperature', $device, '.1.3.6.1.4.1.12148.9.5.5.2.1.5.'.$index, $index, 'eltek-distributed-mib_rectifierStatusTemp', $descr, 1, $entry['rectifierStatusTemp']);
- discover_status($device, '.1.3.6.1.4.1.12148.9.5.5.2.1.2.'.$index, 'rectifierStatusStatus.'.$index, 'eltek-distributed-mib_rectifierStatusStatus', $descr, $entry['rectifierStatusStatus']);
- }
- }
- // Note that the units measured may be in Amperes or in Deciamperes depending on global system settings,
- // but snmp output not have attribute for detect scale
- // ELTEK-DISTRIBUTED-MIB::batteryCurrent.0 = INTEGER: 1 Amperes or DeciAmperes
- // ELTEK-DISTRIBUTED-MIB::batteryChargeCurrentLimitValue.0 = INTEGER: 20 Amperes or DeciAmperes
- // or
- // ELTEK-DISTRIBUTED-MIB::batteryCurrent.0 = INTEGER: 5 Amperes or DeciAmperes
- // ELTEK-DISTRIBUTED-MIB::batteryChargeCurrentLimitValue.0 = INTEGER: 350 Amperes or DeciAmperes
- $limit = snmp_get_oid($device, 'batteryChargeCurrentLimitValue.0', 'ELTEK-DISTRIBUTED-MIB');
- $value = snmp_get_oid($device, 'batteryCurrent.0', 'ELTEK-DISTRIBUTED-MIB');
- $oid = '.1.3.6.1.4.1.12148.9.3.3.0';
- $oid_name = 'batteryCurrent';
- $descr = 'Battery Current';
- if ($limit > 100)
- {
- // Hack for detect scale, not sure if always correct
- $scale = 0.1;
- $limit *= $scale;
- } else {
- $scale = 1;
- }
- $options = ['limit_high' => $limit];
- discover_sensor_ng($device, 'current', $mib, $oid_name, $oid, '0', NULL, $descr, $scale, $value, $options);
- $rectCurrent = snmp_get_oid($device, '.1.3.6.1.4.1.12148.9.5.3.0', 'ELTEK-DISTRIBUTED-MIB');
- discover_sensor_ng($device,'current', $mib, 'rectifierTotalCurrent', '.1.3.6.1.4.1.12148.9.5.3.0', 0, NULL, 'Rectifier Total Current', 1, $rectCurrent, []);
- $rectUtilOptions = ['sensor_unit' => '%'];
- $rectUtil = snmp_get_oid($device, '.1.3.6.1.4.1.12148.9.5.4.0', 'ELTEK-DISTRIBUTED-MIB');
- discover_sensor_ng($device,'load', $mib, 'rectifierUtilization', '.1.3.6.1.4.1.12148.9.5.4.0', 0, NULL, 'Rectifier Utilization', 1, $rectUtil, $rectUtilOptions);
- // EOF