- IDEC DEBUGGER
- ### ERROR LED ##########
- Overcurrent protection function (not a thermal shutdown function).
- Overcurrent detected with 4 outputs as 1 group. (Group 1: Q0 to Q3, Group 2: Q4 to Q7, Group 3:
- Q10 to Q13, Group 4: Q14 to Q17)
- When overcurrent is detected, the 4 outputs in the corresponding group are turned off for a fixed
- period (1 s). When overcurrent is detected, a special internal relay turns on (M8172 to M8175) and
- the error LED [ERR] turns on
- ###Battery::
- Battery voltage (D8056)
- Stores the measured battery voltage in mV. The battery voltage fluctuates according to the usage environment.
- When the power is turned on, this value is 65,535 until the initial battery voltage measurement has completed.
- This value is 0 when there is a measurement error or when there is no battery.
- Battery voltage measurement (M8074)
- Shows the battery voltage measurement status.
- 0: Battery voltage measurement completed
- 1: Battery voltage being measured
- The battery voltage can also be measured by writing 1. The measured value in mV is stored in D8056. The value is reset to 0
- ######### User program execution error:: M8004
- ######### Comm error:: M8005 page 531 breakdown of Bits
- ######### Calendar Errors: M8013, M 8014
- ##### SD CARD ERROR M8255 bit set pg 492 manual
- ### REcipie err M8265
- ## D8069 thru D8099 slave device error R/O