Advertisement
Not a member of Pastebin yet?
Sign Up,
it unlocks many cool features!
- =========================================================
- UPS Information on 192.168.123.1
- =========================================================
- [root@localhost ~]# upsc upsunit@localhost
- battery.charge: 100
- battery.charge.low: 10
- battery.charge.warning: 50
- battery.runtime: 6360
- battery.runtime.low: 120
- battery.type: PbAc
- battery.voltage: 54.8
- battery.voltage.nominal: 24.0
- device.mfr: American Power Conversion
- device.model: Smart-UPS 2200
- device.serial: AS1308140471
- device.type: ups
- driver.name: usbhid-ups
- driver.parameter.pollfreq: 30
- driver.parameter.pollinterval: 15
- driver.parameter.port: auto
- driver.version: 2.6.5
- driver.version.data: APC HID 0.95
- driver.version.internal: 0.37
- ups.beeper.status: enabled
- ups.delay.shutdown: 20
- ups.firmware: UPS 08.3 / ID=18
- ups.mfr: American Power Conversion
- ups.mfr.date: 2013/02/19
- ups.model: Smart-UPS 2200
- ups.productid: 0003
- ups.serial: AS1308140471
- ups.status: OL
- ups.timer.reboot: -1
- ups.timer.shutdown: -1
- ups.vendorid: 051d
- =========================================================
- nut.conf on 192.168.123.1
- =========================================================
- # Network UPS Tools: example nut.conf
- #
- MODE=netserver
- ##############################################################################
- ups.conf on 192.168.123.1
- ##############################################################################
- pollinterval = 15
- [upsunit]
- driver = usbhid-ups
- #productid = 0003 #Doesn't work if enabled for some reason
- port = auto
- ##############################################################################
- upsd.conf on 192.168.123.1
- ##############################################################################
- LISTEN 127.0.0.1 3493
- ##############################################################################
- upsd.user on 192.168.123.1
- ##############################################################################
- [upsuser]
- password = password
- allowfrom = localhost
- actions = SET FSD
- instcmds = ALL
- upsmon master
- ##############################################################################
- upsmon.conf on 192.168.123.1
- ##############################################################################
- MONITOR upsunit@127.0.0.1 1 upsuser password master
- MINSUPPLIES 1
- SHUTDOWNCMD "/sbin/shutdown -h +0"
- NOTIFYCMD /usr/sbin/upssched
- POLLFREQ 5
- POLLFREQALERT 5
- HOSTSYNC 15
- DEADTIME 15
- POWERDOWNFLAG /etc/killpower
- NOTIFYFLAG ONLINE EXEC+SYSLOG
- NOTIFYFLAG ONBATT EXEC+SYSLOG
- NOTIFYFLAG LOWBATT EXEC+SYSLOG
- NOTIFYFLAG FSD EXEC+SYSLOG
- NOTIFYFLAG COMMOK EXEC+SYSLOG
- NOTIFYFLAG COMMBAD EXEC+SYSLOG
- NOTIFYFLAG SHUTDOWN EXEC+SYSLOG
- NOTIFYFLAG REPLBATT EXEC+SYSLOG
- NOTIFYFLAG NOCOMM EXEC
- RBWARNTIME 43200
- NOCOMMWARNTIME 300
- FINALDELAY 5
- MINBATTERY 35
- ##############################################################################
- upsmon.conf on 192.168.123.3
- ##############################################################################
- MONITOR upsunit@192.168.1 1 upsuser password slave
- MINSUPPLIES 1
- SHUTDOWNCMD "/sbin/shutdown -h +0"
- NOTIFYCMD /usr/sbin/upssched
- POLLFREQ 5
- POLLFREQALERT 5
- HOSTSYNC 15
- DEADTIME 15
- POWERDOWNFLAG /etc/killpower
- NOTIFYFLAG ONLINE EXEC+SYSLOG
- NOTIFYFLAG ONBATT EXEC+SYSLOG
- NOTIFYFLAG LOWBATT EXEC+SYSLOG
- NOTIFYFLAG FSD EXEC+SYSLOG
- NOTIFYFLAG COMMOK EXEC+SYSLOG
- NOTIFYFLAG COMMBAD EXEC+SYSLOG
- NOTIFYFLAG SHUTDOWN EXEC+SYSLOG
- NOTIFYFLAG REPLBATT EXEC+SYSLOG
- NOTIFYFLAG NOCOMM EXEC
- RBWARNTIME 43200
- NOCOMMWARNTIME 300
- FINALDELAY 5
- MINBATTERY 35
- ##############################################################################
- /etc/sysconfig/ups on 192.168.123.1
- ##############################################################################
- SERVER=yes
- UPSD_OPTIONS=
- POWERDOWNFLAG=/etc/killpower
- ##############################################################################
- /etc/sysconfig/ups on 192.168.123.3
- ##############################################################################
- SERVER=no
- UPSD_OPTIONS=
- POWERDOWNFLAG=/etc/killpower