- General Commands (ASDU 20) (Control direction): Availability
- − Auto-recloser On / Off: only on MiCOM P123: P123
- FUN<160>;INF<16>, TYP<20>, COT <20>
- − LEDs Reset: This command acknowledge all alarms on Front Panel on MiCOM P12x products:
- FUN<160>;INF<19>, TYP<20>, COT <20>,<ADDR> P120 to P123
- − Setting group number 1: FUN<160>;INF<23>, TYP<20>, COT <20>,<ADDR> P122-P123
- − Setting group number 2: FUN<160>;INF<24>, TYP<20>, COT <20>,<ADDR> P122-P123
- − Order TC COMM1: FUN<168>;INF <234>; TYP <20>; COT<20>,<ADDR> P122-P123
- with private option inactive: FUN<160>;INF <136>; TYP <1>; COT<20>,<ADDR>
- − Order TC COMM2: FUN<168>;INF <235>; TYP <20>; COT<20>,<ADDR> P122-P123
- with private option inactive: FUN<160>;INF <137>; TYP <1>; COT<20>,<ADDR>
- − Order TC COMM3: FUN<168>;INF <238>; TYP <20>; COT<20>,<ADDR> P122-P123
- with private option inactive: FUN<160>;INF <138>; TYP <1>; COT<20>,<ADDR>
- − Order TC COMM4: FUN<168>;INF <239>; TYP <20>; COT<20>,<ADDR> P122-P123
- with private option inactive: FUN<160>;INF <139>; TYP <1>; COT<20>,<ADDR>
- − Trip TC: FUN<168>;INF <1>; TYP <20>; COT<20>,<ADDR> P120 to P123
- with private option inactive: FUN<160>;INF <142>; TYP <1>; COT<20>,<ADDR>
- − Close TC: FUN<168>;INF <2>; TYP <20>; COT<20>,<ADDR> P120 to P123
- with private option inactive: FUN<160>;INF <143>; TYP <1>; COT<20>,<ADDR>
- After executing one of these commands, the relay sends an acknowledge message, which contains the result of command execution.
- If a state change is the consequence of the command, it must be sent in a ASDU 1 with COT 12 (remote operation).
- If the relay receive another command message from the master station before sending the acknowledge message, it will be discarded.
- Commands which are not processed by the relay are rejected with a negative acknowledge message.