- >show struct OUVP-AC 1
- VHH = 31000 ( min=15000 max=40000 def=30000 ) Overvoltage Trip Threshold
- VLL = 15000 ( min=15000 max=40000 def=30000 ) Undervoltage Trip Threshold
- TPOVD = 1 ( min=0 max=500 def=300 ) Overvoltage Trip Delay
- TPUVD = 0 ( min=0 max=500 def=300 ) Undervoltage Trip Delay
- VHL = 29000 ( min=10000 max=40000 def=30000 ) Overvoltage Reset Threshold
- VLH = 16500 ( min=10000 max=40000 def=30000 ) Undervoltage Reset Threshold
- TPOHD = 0 ( min=0 max=500 def=300 ) Protection Output Holding Delay
- THRACT = 50 ( min=10 max=50 def=30 ) Arch Restrain Act Threshold
- TRDD = 100 ( min=100 max=3000 def=2000 ) Restrain Disable Delay
- >show struct OCSCP-AC 1
- IOC1 = 735 ( min=10 max=2000 def=1000 ) Overcurrent Trip Threshold
- TPOCD = 0 ( min=0 max=500 def=250 ) Overcurrent Trip Delay
- TPOHD = 1 ( min=0 max=10000 def=5000 ) Protection Output Holding Delay
- I2_I1 = 50 ( min=10 max=50 def=25 ) Inrush Restrain Act Threshold
- TRDD = 100 ( min=100 max=5000 def=3000 ) Restrain Disable Delay